For the Banner SC22-3E
Page 96
SC22-3/-3E Safety Controller Instruction Manual Complementary (2 or 3 terminals) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time.
24V
S1
S2
Complementary (PNP device) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.
OFF
ON
S1
S2
10.5 Two-Hand Control The Safety Controller may be used as an initiation device for most powered machinery when machine cycling is controlled by a machine operator. Using a two-hand control system makes the operator, in effect, a “hostage” while the hazard is present, thus limiting or preventing exposure to the hazard. The Two-Hand Control (THC) actuators must be positioned so that hazardous motion is completed or stopped before the operator can release one or both of the buttons and reach the hazard (see Two-Hand Control Safety Distance (Minimum Distance) on page 97). The Safety Controller safety inputs used to monitor the actuation of the hand controls for two-hand control comply with the functionality of Type III requirements of IEC 60204-1 and ISO 13851 (EN 574) and the requirements of ANSI NFPA79 and ANSI B11.19 for two-hand control, which include: • Simultaneous actuation by both hands within a 500 ms time frame • When this time limit is exceeded, both hand controls must be released before operation is initiated • Continuous actuation during a hazardous condition • Cessation of the hazardous condition if either hand control is released • Release and re-actuation of both hand controls to re-initiate the hazardous motion or condition (anti-tie down) • The appropriate performance level of the safety-related function (Control Reliability, Category/Performance level, or appropriate regulation and standard, or Safety Integration Level) as determined by a risk assessment See Two-Hand Control (THC) on page 33 for more information. WARNING: Point-of-Operation Guarding When properly installed, a two-hand control device provides protection only for the hands of the machine operator. It may be necessary to install additional safeguarding, such as safety light screens, additional two-hand controls, and/or hard guards, to protect all individuals from hazardous machinery. Failure to properly guard hazardous machinery can result in a dangerous condition which could lead to serious injury or death. CAUTION: Hand Controls The environment in which hand controls are installed must not adversely affect the means of actuation. Severe contamination or other environmental influences may cause slow response or false On conditions of mechanical or ergonomic buttons. This may result in exposure to a hazard. The level of safety achieved (for example, ISO 13849-1 Category) depends in part on the circuit type selected. See TwoHand Control Hookup Options on page 98. Consider the following when installing hand controls:
96 www.bannerengineering.com - Tel: 763.544.3164
Page 97
SC22-3/-3E Safety Controller Instruction Manual • • • • • •
Failure modes, such as a short circuit, a broken spring, or a mechanical seizure, that may result in not detecting the release of a hand control Severe contamination or other environmental influences that may cause a slow response when released or false ON condition of the hand control(s), for example, sticking of a mechanical linkage Protection from accidental or unintended operation, for example, mounting position, rings, guards, or shields Minimizing the possibility of defeat, for example, hand controls must be far enough apart so that they cannot be operated by the use of one arm - typically, not less than 550 mm (21.7 in) in a straight line, per ISO 13851 The functional reliability and installation of external logic devices Proper electrical installation per NEC and NFPA79 or IEC 60204
When used in a single-cycle or single-stroke mode, the machine control must provide an anti-repeat feature so that the operator must release the two-hand control actuators after each machine cycle, before a new cycle can be initiated. In addition to the anti-repeat of the machine control, the Safety Controller input(s) can also be used to halt a machine cycle and help in providing Anti-Repeat Control. CAUTION: Install Hand Controls to Prevent Accidental Actuation Total protection for the two-hand control system from defeat is not possible. However, the user is required by U.S. and International standards to arrange and protect hand controls to minimize the possibility of defeat or accidental actuation. CAUTION: Machine Control Must Provide Anti-Repeat Control Appropriate anti-repeat control must be provided by the machine control and is required by U.S. and International standards for single-stroke or single-cycle machines. This Banner device can be used to assist in accomplishing anti-repeat control, but a risk assessment must be accomplished to determine the suitability of such use.
10.5.1 Two-Hand Control Safety Distance (Minimum Distance) Both hand controls must be located far enough away from the nearest hazard point that the operator cannot reach the hazard with a hand or other body part before the hazardous motion ceases. This is the “separation distance” (“safety distance”), and may be calculated as follows. WARNING: Location of Touch Button Controls Hand controls must be mounted a safe distance from moving machine parts, as determined by the appropriate standard. It must not be possible for the operator or other non-qualified persons to relocate them. Failure to establish and maintain the required safety distance may result in serious injury or death. U.S. Applications The Safety Distance formula, as provided in ANSI B11.19: Part-Revolution Clutch Machinery (the machine and its controls allow the machine to stop motion during the hazardous portion of the machine cycle) Ds = K x (Ts + Tr + Th) For Full-Revolution Clutch Machinery (the machine and its controls are designed to complete a full machine cycle) Ds = K x (Tm + Tr + Th) Ds the Safety Distance (in inches)
K the OSHA/ANSI recommended hand-speed constant (in inches per second), in most cases is calculated at 63 in/sec, but may vary between 63 in/sec to 100 in/sec based on the application circumstances; not a conclusive determination; consider all factors, including the physical ability of the operator, when determining the value of K to be used Th the response time of the slowest hand control from the time when a hand disengages that control until the switch opens; Th is usually insignificant for purely mechanical switches. However, Th should be considered for safety distance calculation when using electronic or electromechanical (powered) hand controls. For Banner Self-checking Touch Buttons (STBs) the response time is 0.02 seconds www.bannerengineering.com - Tel: 763.544.3164
97
Page 98
SC22-3/-3E Safety Controller Instruction Manual
U.S. Applications Tm the maximum time (in seconds) the machine takes to cease all motion after it has been tripped. For full revolution clutch presses with only one engaging point, Tm is equal to the time necessary for one and one-half revolutions of the crankshaft. For full revolution clutch presses with more than one engaging point, Tm is be calculated as follows: Tm = (1/2 + 1/N) x Tcy N = number of clutch engaging points per revolution Tcy = time (in seconds) necessary to complete one revolution of the crankshaft
Tr
Ts the response time of the Safety Controller as measured from the time a stop signal from either hand control. The Safety Controller response time is obtained from the Configuration Summary in the PC Interface. the overall stop time of the machine (in seconds) from the initial stop signal to the final ceasing of all motion, including stop times of all relevant control elements and measured at maximum machine velocity Ts is usually measured by a stop-time measuring device. If the specified machine stop time is used, add at least 20% as a safety factor to account for brake system deterioration. If the stop-time of the two redundant machine control elements is unequal, the slower of the two times must be used for calculating the separation distance
European Applications The Minimum Distance Formula, as provided in ISO 13855: S = (K x T) + C S the Minimum Distance (in millimeters) K the ISO 13855 recommended hand-speed constant (in millimeters per second), in most cases is calculated at 1600 mm/sec, but may vary between 1600 to 2500 mm/sec based on the application circumstances; · not a conclusive determination; consider all factors, including the physical ability of the operator, when determining the value of K to be used. T the overall machine stopping response time (in seconds), from the physical initiation of the safety device to the final ceasing of all motion C the added distance due to the depth penetration factor equals 250 mm, per ISO 13855. The ISO 13855 C factor may be reduced to 0 if the risk of encroachment is eliminated, but the safety distance must always be 100 mm or greater
10.5.2 Two-Hand Control Hookup Options The device is shown not actuated (Off state). See ISO 13851 for a complete explanation of “Type” designations and ISO 13849-1 Category requirements. Dual-Channel (2, 3, or 4 terminals) 24V
This circuit is a Type IIIa Two-Hand Control circuit as described by ISO 13851, and typically meets ISO 13849-1 Category 1 requirements. Type IIIb and Category 3 may be achieved if redundant contacts from each hand control are used in each channel, for example, two each in series (as shown in image D), or with a 3-terminal hookup that uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal hookups can detect a short between channels when the contacts are open if the short is present for more than 2 seconds. The 4-terminal circuit can detect a short circuit between channels or to another source of power (image C).
98 www.bannerengineering.com - Tel: 763.544.3164
A.
B. 24V
C.
D.
Page 99
SC22-3/-3E Safety Controller Instruction Manual Dual-Channel (PNP device) OFF
OFF
OFF
ON
OFF
S1
S2
This circuit is a Type IIIa Two-Hand Control circuit as described by ISO 13851, and typically meets ISO 13849-1 Category 1 requirements. The Safety Controller does not provide short circuit detection between channels in this configuration.
2x Complementary (4 or 5 terminals) This circuit is a Type IIIc Two-Hand Control circuit as described by ISO 13851, and typically meets ISO 13849-1 Category 4 requirements. In the actuated condition (S1 closed/S2 open), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. Select this option if using Banner Selfchecking Touch Button models STBVR81… See Safety Input Device Properties on page 27.
24V
S1
S2
S3
S4
2x Complementary (PNP device) This circuit is a Type IIIc Two-Hand Control circuit as described by ISO 13851, and typically meets ISO 13849-1 Category 4 requirements. In the actuated condition (S1 On/S2 Off), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. Select this option if using Banner Selfchecking Touch Buttons models STBVP6… See Safety Input Device Properties on page 27.
ON
10.6 Safety Mat The Safety Controller may be used to monitor pressure-sensitive safety mats and safety edges. The purpose of the Safety Mat input of the Safety Controller is to verify the proper operation of 4-wire presence-sensing safety mats. Multiple mats may be connected in series to one Controller, 150 ohms maximum per input (see Safety Mat Hookup Options on page 100). Important: The Controller is not designed to monitor 2-wire mats, bumpers, or edges (with or without sensing resistors). The controller monitors the contacts (contact plates) and the wiring of one or more safety mat(s) for failures and prevents the machine from restarting if a failure is detected. A reset routine after the operator steps off the safety mat may be provided by the Safety Controller, or, if the Controller is used in auto-reset mode, the reset function must be provided by the machine control system. This prevents the controlled machinery from restarting automatically after the mat is cleared. WARNING: Application of Safety Mats Safety Mat application requirements vary for the level of control reliability or category and performance level as described by ISO 13849-1 and ISO 13856. While Banner Engineering always recommends the highest level of safety in any application, the user is responsible to safely install, operate, and maintain each safety system per the manufacturer's recommendations and comply with all relevant laws and regulations. Do not use safety mats as a tripping device to initiate machine motion (such as in a presencesensing device initiation application), due to the possibility of unexpected start or re-start of the machine cycle resulting from failure(s) within the mat and the interconnect cabling. Do not use a safety mat to enable or provide the means to allow the machine control to start hazardous motion by simply standing on the safety mat (for example, at a control station). This type of application uses reverse/negative logic and certain failures (for example, loss of power to the Module) can result in a false enable signal.
www.bannerengineering.com - Tel: 763.544.3164
99
Page 100
SC22-3/-3E Safety Controller Instruction Manual
10.6.1 Safety Mat Requirements The following are minimum requirements for the design, construction, and installation of four-wire safety mat sensor(s) to be interfaced with the Safety Controller. These requirements are a summary of standards ISO 13856-1, ANSI/RIA R15.06 and ANSI B11.19. The user must review and comply with all applicable regulations and standards.
Safety Mat System Design and Construction The safety mat system sensor, Safety Controller, and any additional devices must have a response time that is fast enough to reduce the possibility of an individual stepping lightly and quickly over the mat’s sensing surface (less than 100 to 200 ms, depending on the relevant standard). For a safety mat system, the minimum object sensitivity of the sensor must detect, at a minimum, a 30 kg (66 lb) weight on an 80 mm (3.15 in) diameter circular disk test piece anywhere on the mat’s sensing surface, including joints and junctions. The effective sensing surface or area must be identifiable and can comprise one or more sensors. The safety mat supplier should state this minimum weight and diameter as the minimum object sensitivity of the sensor. User adjustments to actuating force and response time are not allowed (ISO 13856-1). The sensor should be manufactured to prevent any reasonably foreseeable failures, such as oxidation of the contact elements which could cause a loss in sensitivity. The environmental rating of the sensor must meet a minimum of IP54. When the sensor is specified for immersion in water, the sensor’s minimum enclosure level must be IP67. The interconnect cabling may require special attention. A wicking action may result in the ingress of liquid into the mat, possibly causing a loss of sensor sensitivity. The termination of the interconnect cabling may need to be located in an enclosure that has an appropriate environmental rating. The sensor must not be adversely affected by the environmental conditions for which the system is intended. The effects of liquids and other substances on the sensor must be taken into account. For example, long-term exposure to some liquids can cause degradation or swelling of the sensor’s housing material, resulting in an unsafe condition. The sensor’s top surface should be a lifetime non-slip design, or otherwise minimize the possibility of slipping under the expected operating conditions. The four-wire connection between the interconnect cables and the sensor must withstand dragging or carrying the sensor by its cable without failing in an unsafe manner, such as broken connections due to sharp or steady pulls, or continuous flexing. If such connection is not available, an alternative method must be employed to avoid such failure, for example, a cable which disconnects without damage and results in a safe situation.
10.6.2 Safety Mat Hookup Options Pressure-sensitive mats and pressure-sensitive floors must meet the requirements of the category for which they are specified and marked. These categories are defined in ISO 13849-1. The safety mat, its Safety Controller, and any output signal switching devices must meet, at a minimum, the Category 1 safety requirements. See ISO 13856-1 (EN 1760-1) and ISO 13849-1 for relevant requirement details. The Safety Controller is designed to monitor 4-wire safety mats and is not compatible with two-wire devices (mats, sensing edges, or any other devices with two wires and a sensing resistor). 4-Wire This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements depending on the safety rating and installation of the mat(s). The Safety Controller enters a Lockout mode when an open wire, a short to 0 V, or a short to another source of power is detected.
10.6.3 Safety Mat Installation The mounting surface quality and preparation for the safety mat must meet the requirements stated by the sensor’s manufacturer. Irregularities in the mounting surfaces may impair the function of the sensor and should be reduced to an acceptable minimum. The mounting surface should be level and clean. Avoid the collection of fluids under or around the sensor. Prevent the risk of failure due to a build-up of dirt, turning chips, or other material under the sensor(s) or the associated hardware. Special consideration should be given to joints between the sensors to ensure that foreign material does not migrate under or into the sensor. Any damage (cuts, tears, wear, or punctures) to the outer insulating jacket of the interconnect cable or to any part of the exterior of the safety mat must be immediately repaired or replaced. Ingress of material (including dirt particles, insects, fluid, moisture, or turning-chips), which may be present near the mat, may cause the sensor to corrode or to lose its sensitivity.
100 www.bannerengineering.com - Tel: 763.544.3164
Page 101
SC22-3/-3E Safety Controller Instruction Manual Routinely inspect and test each safety mat according to the manufacturer’s recommendations. Do not exceed operational specifications, such as the maximum number of switching operations. Securely mount each safety mat to prevent inadvertent movement (creeping) or unauthorized removal. Methods include, but are not limited to, secured edging or trim, tamper-resistant or one-way fasteners, and recessed flooring or mounting surface, in addition to the size and weight of large mats. Each safety mat must be installed to minimize tripping hazards, particularly towards the machine hazard. A tripping hazard may exist when the difference in height of an adjacent horizontal surface is 4 mm (1/8 in) or more. Minimize tripping hazards at joints, junctions, and edges, and when additional coverings are used. Methods include a ground-flush installation of the mat, or a ramp that does not exceed 20° from horizontal. Use contrasting colors or markings to identify ramps and edges. Position and size the safety mat system so that persons cannot enter the hazardous area without being detected, and cannot reach the hazard before the hazardous conditions have ceased. Additional guards or safeguarding devices may be required to ensure that exposure to the hazard(s) is not possible by reaching over, under, or around the device’s sensing surface. A safety mat installation must take into account the possibility of easily stepping over the sensing surface and not being detected. ANSI and international standards require a minimum depth of field of the sensor surface (the smallest distance between the edge of the mat and hazard) to be from 750 to 1200 mm (30 to 48 in), depending on the application and the relevant standard. The possibility of stepping on machine supports or other physical objects to bypass or climb over the sensor also must be prevented.
Safety Mat Safety Distance (Minimum Distance) As a stand-alone safeguard, the safety mat must be installed at a safety distance (minimum distance) so that the exterior edge of the sensing surface is at or beyond that distance, unless it is solely used to prevent start/restart, or solely used for clearance safeguarding (see ANSI B11.19, ANSI/RIA R15.06, and ISO 13855).
Ds K(Ts + Tr)
Dpf
Hazardous Zone or Area
The safety distance (minimum distance) required for an application depends on several factors, including the speed of the hand (or individual), the total system stopping time (which includes several response time components), and the depth penetration factor. Refer to the relevant standard to determine the appropriate distance or means to ensure that individuals cannot be exposed to the hazard(s).
Safety Mat
Figure 64. Determining safety distance for the safety mat
U.S. Applications The Safety Distance formula, as provided in ANSI B11.19: Ds = K x (Ts + Tr) + Dpf Ds Tr the Safety Distance (in inches) the response time of the Safety Controller as measured from the time a stop signal from either hand control. The Safety Controller response time is obtained from the Configuration Summary in the PC Interface.
K the OSHA/ANSI recommended hand-speed constant (in inches per second), in most cases is calculated at 63 in/sec, but may vary between 63 in/sec to 100 in/sec based on the application circumstances; not a conclusive determination; consider all factors, including the physical ability of the operator, when determining the value of K to be used Ts the overall stop time of the machine (in seconds) from the initial stop signal to the final ceasing of all motion, including stop times of all relevant control elements and measured at maximum machine velocity Ts is usually measured by a stop-time measuring device. If the specified machine stop time is used, add at least 20% as a safety factor to account for brake system deterioration. If the stop-time of the two redundant machine control elements is unequal, the slower of the two times must be used for calculating the separation distance
Dpf the added distance due to the penetration depth factor equals 48 in, per ANSI B11.19 www.bannerengineering.com - Tel: 763.544.3164
101
Page 102
SC22-3/-3E Safety Controller Instruction Manual
European Applications The Minimum Distance Formula, as provided in ISO 13855: S = (K x T) + C S the Minimum Distance (in millimeters) K the ISO 13855 recommended hand-speed constant (in millimeters per second), in most cases is calculated at 1600 mm/sec, but may vary between 1600 to 2500 mm/sec based on the application circumstances; · not a conclusive determination; consider all factors, including the physical ability of the operator, when determining the value of K to be used. T the overall machine stopping response time (in seconds), from the physical initiation of the safety device to the final ceasing of all motion C the added distance due to the depth penetration factor equals 1200 mm, per ISO 13855
10.7 Emergency Stop Push Buttons The Safety Controller safety inputs may be used to monitor emergency stop push buttons.
10.7.1 Safety Circuit Integrity Levels The application requirements for emergency stop buttons vary for the level of control reliability or safety category per ISO 13849-1. While Banner Engineering always recommends the highest level of safety in any application, the user is responsible to safely install, operate, and maintain each safety system and comply with all relevant laws and regulations. The safety performance (integrity) must reduce the risk from identified hazards as determined by the machine’s risk assessment. See Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles on page 86 for guidance if the requirements as described by ISO 13849-1 need to be implemented. In addition to the requirements stated in this section, the design and installation of the interlocking device must comply with In addition to the requirements stated in this section, the design and installation of the Emergency Stop device must comply with ANSI NFPA79 or ISO 13850. WARNING: Emergency Stop Functions Do not mute or bypass any Emergency Stop device. ANSI NFPA79 and IEC/EN 60204-1 require that the Emergency Stop function remain active at all times. Muting or bypassing the safety outputs will render the emergency stop function ineffective. The Safety Controller Emergency Stop configuration prevents muting or bypassing of the EStop input(s). However, the user still must ensure that the E-Stop device remains active at all times. WARNING: Reset Routine Required U.S. and international standards require that a reset routine be performed after clearing the cause of a stop condition (for example, arming an E-stop button, closing an interlocked guard, etc.). Allowing the machine to restart without actuating the normal start command/device can create an unsafe condition which may result in serious injury or death.
10.7.2 Emergency Stop Push Button Requirements As shown in the following circuit figures, the E-stop switch must provide one or two contacts for safety which are closed when the switch is armed. When activated, the E-stop switch must open all its safety-rated contacts, and must require a deliberate action (such as twisting, pulling, or unlocking) to return to the closed-contact, armed position. The switch must be a positive-opening (or direct-opening) type, as described by IEC 60947-5-1. A mechanical force applied to such a button (or switch) is transmitted directly to the contacts, forcing them to open. This ensures that the switch contacts open whenever the switch is activated. Standards ANSI NFPA 79, ANSI B11.19, IEC/EN 60204-1, and ISO 13850 specify additional Emergency Stop switch device requirements, including the following:
102 www.bannerengineering.com - Tel: 763.544.3164
Page 103
SC22-3/-3E Safety Controller Instruction Manual • • •
•
Emergency stop push buttons must be located at each operator control station and at other operating stations where emergency shutdown is required Stop and Emergency stop push buttons must be continuously operable and readily accessible from all control and operating stations where located. Do not mute or bypass any E-stop button Actuators of emergency stop devices must be colored red. The background immediately around the device actuator must be colored yellow. The actuator of a push-button-operated device must be of the palm or mushroom-head type The Emergency stop actuator must be a self-latching type NOTE: Some applications may have additional requirements; the user is responsible to comply with all relevant regulations.
Safety Circuit Integrity Levels and Multiple E-Stop Buttons The safety performance (integrity) must reduce the risk from identified hazards as determined by the machine’s risk assessment. See Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles on page 86 for guidance if the requirements as described by ISO 13849-1 need to be implemented. In addition to ANSI NFPA 79 and IEC/EN 60204-1, the design and the installation of the emergency stop device (switch, button, or rope-pull) must be such that the possibility of a catastrophic failure of the device resulting in the loss of the safety function is excluded. The device must comply with ISO 13850 requirements such that the fault exclusions of ISO 13849-2 are applicable. Electromechanical devices that have contacts designed in accordance to IEC 60947-5-1 Annex K and that are installed according to manufacturer’s instructions are expected to open when the emergency stop device is actuated. WARNING: Multiple Switching Devices Whenever two or more devices are connected to the same safety module (controller): •
•
Contacts of the corresponding pole of each switch must be connected together in series. Never connect the contacts of multiple switches in parallel. Such a parallel connection defeats the switch contact monitoring ability of the Module and creates an unsafe condition which may result in serious injury or death. Each device must be individually actuated (engaged), then released (or re-armed) and the safety module reset. This allows the module to check each switch and its wiring to detect faults.
This check must be performed during the prescribed checkouts. Failure to test each device individually in this manner may result in undetected faults and create an unsafe condition which may result in serious injury or death.
Category 2 E-Stop Circuit A single-channel emergency stop application typically provides a Category 2 level of circuit performance, because a short circuit could cause the loss of the safety function. The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of undetected faults or failures that result in a loss of the safety function.
Figure 65. Category 2 E-stop circuit www.bannerengineering.com - Tel: 763.544.3164
103
Page 104
SC22-3/-3E Safety Controller Instruction Manual
Category 3 E-Stop Circuit A dual-channel hookup switching +24V dc is typically a Category 3 application, because a single failure does not result in a loss of safety. A loss of the switching action in one channel is detected by the actuation of the E-stop button, the opening of the second channel, and the monitoring function of the safety inputs. However, a short circuit between input channels or safety outputs may not be detected. Note that an accumulation of faults may cause the loss of the safety function. The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of undetected faults or catastrophic failures that result in a loss of the safety function.
Figure 66. Category 3 E-stop circuit
Category 4 E-Stop Circuit The self-monitoring safety inputs can be interfaced to achieve a Category 4 application. The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of catastrophic failures or faults that result in a loss of the safety function.
Figure 67. Category 4 E-stop circuit
Emergency Stop Hookup Options The device is shown in the armed (Run) state. Single-Channel (1 terminal, 2 terminals, or PNP device) This circuit typically meets ISO 13849-1 Category 2 requirements, depending on the safety rating and the installation of the device. At a minimum, a safety-rated device must be used to achieve Category 2. The 1terminal and the PNP device circuits cannot detect a short circuit to another source of power. The two-terminal circuit uses pulse monitoring and can detect a short circuit to another source of power. Fault Exclusion must be used to achieve a higher level of safety circuit integrity.
24V
Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.
24V
Dual-Channel (PNP device)
This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.
104 www.bannerengineering.com - Tel: 763.544.3164
ON
ON