SC22-3/-3E Safety Controller Instruction Manual Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

10.8 Rope (Cable) Pull Rope (cable) pull emergency stop switches use steel wire rope; they provide emergency stop actuation continuously over a distance, such as along a conveyor. Rope pull emergency stop switches have many of the same requirements as emergency stop push buttons, such as positive (direct) opening operation, as described by IEC 60947-5-1. See Emergency Stop Push Buttons on page 102 for additional information. It is recommended to use rope pull emergency stop switches that have the capability not only to react to a pull in any direction, but also to a slack or a break of the rope. Typically, this is accomplished by separate contacts within the switch. When the rope is properly tensioned, both contacts of the switch are closed. When the rope is pulled, the positive-break contacts open. If the rope breaks or goes slack, the second set of contacts opens (see Rope/Cable Pull Hookup Options on page 105). Some rope pull emergency stop switches provide a latching function that requires a manual reset after actuation. If using a switch that does not provide a latching function after the rope is released, a separate latching circuit is required, which can be provided by the Safety Controller.

10.8.1 Rope/Cable Pull Installation Guidelines • • • • • • •

• • • •

•

The wire rope should be easily accessible and visible along its entire length. Markers or flags may be fixed on the rope to increase its visibility Mounting points, including support points, must be rigid The rope should be free of friction at all supports. Pulleys are recommended. Use pulleys when routing the rope around a corner, or whenever direction is changed, even slightly Never run rope through conduit or other tubing Never attach weights to the rope Temperature affects rope tension. The rope expands (lengthens) when temperature increases, and contracts (shrinks) when temperature decreases. Significant temperature variations require frequent checks of the tension adjustment. Do not exceed the manufacturer’s recommended maximum rope length Mount the switch securely on a solid, stationary surface The anchor point for rope must be solid and stationary, and be able to withstand the constant tension of the rope Each rope pull emergency stop installation should be tested and inspected for proper operation at suitable intervals as determined by the user’s risk assessment, based upon severity of the operating environment and the frequency of switch actuations Pulleys and other moving parts associated with the rope should be periodically lubricated

10.8.2 Rope/Cable Pull Hookup Options The device is shown in the armed (Run) state. Single-Channel (1 terminal, 2 terminals, or PNP device) This circuit typically meets ISO 13849-1 Category 2 requirements, depending on the safety rating and the installation of the device. At a minimum, a safety-rated device must be used to achieve Category 2. The 1terminal and the PNP device circuits cannot detect a short circuit to another source of power. The two-terminal circuit uses pulse monitoring and can detect a short circuit to another source of power. Fault Exclusion must be used to achieve a higher level of safety circuit integrity.

www.bannerengineering.com - Tel: 763.544.3164

24V

105

Page 106

SC22-3/-3E Safety Controller Instruction Manual Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

24V

Dual-Channel (PNP device) ON

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

ON

Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

Complementary (2 or 3 terminals) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

24V

S1

S2

S1

S2

Complementary (PNP device) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

ON

OFF

S1

S2

10.9 Enabling Device An enabling device is a manually operated control which, when continuously actuated, allows a machine cycle to be initiated in conjunction with a start control. Standards that cover the design and application of enabling devices include: ISO 12100-1/-2, IEC 60204-1, ANSI/NFPA 79, ANSI/RIA R15.06, and ANSI B11.19. See section Enabling Devices on page 34 for more information.

10.9.1 Enabling Device Guidelines Depending on the application, the use of the enabling device may require supervision and allow only limited machine operation when the individual actuating the device is exposed to a hazardous situation. When the enabling device is in use, the control of the machine motion must be prevented from other sources that would override the function of the enabling device. Simply actuating the enabling device must not create a hazard. An enabling device allows a hazardous situation when continuously actuated in one position only. In any other position, the hazard must be eliminated and the start function inhibited.

106 www.bannerengineering.com - Tel: 763.544.3164

Page 107

SC22-3/-3E Safety Controller Instruction Manual Many standards require the use of three-position devices due to an individual’s reaction to either release or tighten the grip in an emergency situation. • Position #1: the Off function of the switch (actuator is not operated) • Position #2: the enabling function (actuator is operated in its midpoint) • Position #3: the Off function of the switch (actuator is operated past its midpoint) The release or compression past the midpoint-enabled position (Position #2) of the device must initiate an immediate stopping of hazardous motion or situation. It is required that the enabling device is released and re-actuated before the machine motion is reinitiated. Two-position types (if allowed) are: • •

Position #1: the Off function of the switch (actuator is not operated) Position #2: the enabling function (actuator is operated)

The stop function must be either a functional stop Category 0 or a Category 1 (see ANSI NFPA79 Section 9). The design and installation of the enabling device must consider the ergonomic issues (force, posture, etc.) of sustained activation. A visual confirmation that the device is active may be required. Only trained and qualified individuals are allowed to operate the enabling device if it is bypassing other safeguards. Safe work procedures must include, but are not limited to, the use of the device, the associated hazards, and the task requiring the use of the device. If more than one individual is safeguarded by the use of the enabling device, all individuals must have their own device. Each enabling device must be concurrently operated before machine motion can be initiated. The method to return the machine to production mode must be located outside the hazardous area, where it cannot be reached from within that area and is guarded against unintended operation. In addition, the reset switch operator must have the full view of the entire guarded area and verify that the area is clear of individuals during the reset procedure.

10.9.2 Enabling Device Hookup Options The device is shown in the actuated position (Stop state). Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

24V

Dual-Channel (PNP device)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

OFF

OFF

Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

www.bannerengineering.com - Tel: 763.544.3164

107

Page 108

SC22-3/-3E Safety Controller Instruction Manual Complementary (2 or 3 terminals) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time.

24V

S1

S2

Complementary (PNP device) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

OFF

ON

S1

S2

OFF

ON

OFF

S1

S2

2x Complementary (4 or 5 terminals) This circuit meets ISO 13849-1 Category 3 or Category 4 requirements depending on the safety rating and the design and installation of the enabling device. This circuit can detect a short circuit between channels. In the guard closed condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

24V

S1

S2

2x Complementary (PNP device) This circuit meets ISO 13849-1 Category 3 or Category 4 requirements depending on the safety rating design and installation of the enabling device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. Safety Input Device Properties on page 27.

ON

10.10 Bypass Switches (Bypassing Safeguards) The Safety Controller may be used to monitor switches that initiate the bypassing of a safeguarding device. Bypassing or overriding a safeguarding device is the manual interruption or suspension of the normal function of a safeguard under supervisory control. It is typically accomplished by selecting a bypass mode of operation using a key switch to facilitate machine setup, web alignment/adjustments, robot teach, and process troubleshooting. See Bypass Function on page 36 for more information.

10.10.1 Requirements of Bypassing Safeguards Requirements to bypass a safeguarding device include8: • The bypass function must be temporary • The means of selecting or enabling the bypass must be capable of being supervised • Automatic machine operation must be prevented by limiting range of motion, speed, or power (used inch, jog, or slow-speed modes). Bypass mode must not be used for production • Supplemental safeguarding must be provided. Personnel must not be exposed to hazards • The means of bypassing must be within full view of the safeguard to be bypassed • Initiation of motion should only be through a hold-to-run type of control • All emergency stops must remain active 8 This summary was compiled from sources including ANSI NFPA79, ANSI/RIA R15.06, ISO 13849-1, IEC60204-1, and ANSI B11.19.

108 www.bannerengineering.com - Tel: 763.544.3164

Page 109

SC22-3/-3E Safety Controller Instruction Manual • • • • •

The means of bypassing must be employed at the same level of reliability as the safeguard Visual indication that the safeguarding device has been bypassed must be provided and be readily observable from the location of the safeguard Personnel must be trained in the use of the safeguard and in the use of the bypass Risk assessment and risk reduction (per the relevant standard) must be accomplished The reset, actuation, clearing, or enabling of the safeguarding device must not initiate hazardous motion or create a hazardous situation

Bypassing a safeguarding device should not be confused with muting, which is a temporary, automatic suspension of the safeguarding function of a safeguarding device during a non-hazardous portion of the machine cycle. Muting allows for material to be manually or automatically fed into a machine or process without issuing a stop command. Another term commonly confused with bypassing is blanking, which desensitizes a portion of the sensing field of an optical safeguarding device, such as disabling one or more beams of a safety light curtain so that a specific beam break is ignored.

Safe Working Procedures and Training Safe work procedures provide the means for individuals to control exposure to hazards through the use of written procedures for specific tasks and the associated hazards. The user must also address the possibility that an individual could bypass the safeguarding device and then either fail to reinstate the safeguarding or fail to notify other personnel of the bypassed condition of the safeguarding device; both cases could result in an unsafe condition. One possible method to prevent this is to develop a safe work procedure and ensure personnel are trained and correctly follow the procedure.

Lockout/Tagout Hazardous energy (lockout/tagout) must be controlled in machine maintenance and servicing situations in which the unexpected energization, start up, or release of stored energy could cause injury. Refer to OSHA 29CFR 1910.147, ANSI 2244.1, ISO 14118 , ISO 12100 or other relevant standards to ensure that bypassing a safeguarding device does not conflict with the requirements that are contained within the standards. WARNING: Limit Use of Bypass Function The Bypass function is not intended for production purposes; it is to be used only for temporary or intermittent actions, such as to clear the defined area of a safety light screen if material becomes "stuck". When Bypass is used, it is the user's responsibility to install and use it according to relevant standards (such as ANSI NFPA79 or IEC/EN60204-1).

10.10.2 Bypass Switch Hookup Options The device is shown in the not actuated (Off) state. Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

24V

Dual-Channel (PNP device)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

OFF

OFF

Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

www.bannerengineering.com - Tel: 763.544.3164

109

Page 110

SC22-3/-3E Safety Controller Instruction Manual Complementary (2 or 3 terminals) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time.

24V

S1

S2

Complementary (PNP device) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

OFF

ON

S1

S2

OFF

ON

OFF

S1

S2

2x Complementary (4 or 5 terminals) This circuit meets ISO 13849-1 Category 3 or Category 4 requirements depending on the safety rating and the design and installation of the enabling device. This circuit can detect a short circuit between channels. In the guard closed condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

24V

S1

S2

2x Complementary (PNP device) This circuit meets ISO 13849-1 Category 3 or Category 4 requirements depending on the safety rating design and installation of the enabling device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. Safety Input Device Properties on page 27.

ON

10.11 Mute Sensor Pair 10.11.1 Muting Function OSHA and ANSI standards require the user to arrange, install, and operate the safety system so that personnel are protected and the possibility of defeating the safeguard is minimized. To mute the primary safeguard appropriately, the design of a muting system must: 1. Identify the non-hazardous portion of the machine cycle 2. Involve the selection of the proper muting devices 3. Include proper mounting and installation of those devices The Safety Controller can monitor and respond to redundant signals that initiate the mute. The mute then suspends the safeguarding function by ignoring the state of the input device to which the muting function has been assigned. This allows an object or person to pass through the defined area of a safety light screen without generating a stop command. This should not be confused with blanking, which disables one or more beams in a safety light screen resulting in larger resolution. The mute function may be triggered by a variety of external devices. This feature provides a variety of options to design the system to meet the requirements of a specific application.

110 www.bannerengineering.com - Tel: 763.544.3164

Page 111

SC22-3/-3E Safety Controller Instruction Manual A pair of muting devices must be triggered simultaneously (within 3 seconds of one another). This reduces the chance of common mode failures or defeat. Directional muting, in which sensor pair 1 is required to be blocked first, also may reduce the possibility of defeat. See Mute Function on page 34 for more information. WARNING: Muting Limitations Muting is allowed only during the non-hazardous portion of the machine cycle. A muting application must be designed so that no single component failure can prevent the stop command or allow subsequent machine cycles until the failure is corrected (per OSHA 1910.217(c)(3)(iii)(d), and ANSI B11.19). WARNING: Mute Inputs Must Be Redundant It is not acceptable to use a single switch, device, or relay with two N.O. contacts for the mute inputs. This single device, with multiple outputs, may fail so that the System is muted at an inappropriate time. This may result in a hazardous situation.

10.11.2 Muting Function Requirements The beginning and the end of a mute cycle must be triggered by outputs from either pair of muting devices, depending on the application. The mute device pairs both must have normally open contacts, or have PNP outputs, both of which fulfill the Muting Device Requirements. These contacts must close (conduct) when the switch is actuated to initiate the mute, and must open (not conduct) when the switch is not actuated and in a power-off condition. The Controller monitors the mute devices to verify that their outputs turn ON within 3 seconds of each other. If the inputs do not meet this simultaneity requirement, a mute condition cannot occur. Several types and combinations of mute devices can be used, including, but not limited to photoelectric sensors, inductive proximity sensors, limit switches, positive-driven safety switches, and whisker switches.

Mute Device Requirements The muting devices must, at a minimum, comply with the following requirements: 1. There must be a minimum of two independent hard-wired muting devices. 2. The muting devices must have one of the following: normally open contacts, PNP outputs (both of which must fulfill the input requirements listed in the Specifications), or a complementary switching action. At least one of these contacts must close when the switch is actuated, and must open (or not conduct) when the switch is not actuated or is in a power-off state. 3. The activation of the inputs to the muting function must come from separate sources. These sources must be mounted separately to prevent an unsafe muting condition resulting from misadjustment, misalignment, or a single common mode failure, such as physical damage to the mounting surface. Only one of these sources may pass through, or be affected by, a PLC or a similar device. 4. The muting devices must be installed so that they cannot be easily defeated or bypassed. 5. The muting devices must be mounted so that their physical position and alignment cannot be easily changed. 6. It must not be possible for environmental conditions, such as extreme airborne contamination, to initiate a mute condition. 7. The muting devices must not be set to use any delay or other timing functions unless such functions are accomplished so that no single component failure prevents the removal of the hazard, subsequent machine cycles are prevented until the failure is corrected, and no hazard is created by extending the muted period.

Examples of Muting Sensors and Switches WARNING: Avoid Hazardous Installations Two or four independent position switches must be properly adjusted or positioned so that they close only after the hazard no longer exists, and open again when the cycle is complete or the hazard is again present. If the switches are improperly adjusted or positioned, injury or death may result. The user is responsible to satisfy all local, state, and national laws, rules, codes, and regulations relating to the use of safety equipment in any particular application. Make sure that all appropriate agency requirements have been met and that all installation and maintenance instructions contained in the appropriate manuals are followed.

www.bannerengineering.com - Tel: 763.544.3164

111

Page 112

SC22-3/-3E Safety Controller Instruction Manual

Photoelectric Sensors (Opposed Mode) Opposed-mode sensors should be configured for dark operate (DO) and have open (non-conducting) output contacts in a power Off condition. Both the emitter and receiver from each pair should be powered from the same source to reduce the possibility of common mode failures.

Photoelectric Sensors (Polarized Retroreflective Mode) The user must ensure that false proxying (activation due to shiny or reflective surfaces) is not possible. Banner low profile sensors with linear polarization can greatly reduce or eliminate this effect. Use a sensor configured for light operate (LO or N.O.) if initiating a mute when the retroreflective target or tape is detected (home position). Use a sensor configured for dark operate (DO or N.C.) when a blocked beam path initiates the muted condition (entry/exit). Both situations must have open (non-conducting) output contacts in a power Off condition.

Positive-Opening Safety Switches Two (or four) independent switches, each with a minimum of one closed safety contact to initiate the mute cycle, are typically used. An application using a single switch with a single actuator and two closed contacts may result in an unsafe situation.

Inductive Proximity Sensors Typically, inductive proximity sensors are used to initiate a muted cycle when a metal surface is detected. Do not use twowire sensors due to excessive leakage current causing false On conditions. Use only three- or four-wire sensors that have discrete PNP or hard-contact outputs that are separate from the input power.

10.11.3 Muting Device Hookup Options The Controller provides configuration options for the muting devices. One or two pairs of muting devices (typically sensors or switches) must be used; these pairs are designated M1-M2 and M3-M4. In the circuit diagrams below, it is assumed that each contact or output is being generated by an individual device for category 3 and category 4. To meet category 4 requirements for the category 3 hookups shown, design or otherwise eliminate the possibility of a short circuit between muting sensors (input channels); see Fault Exclusion on page 88. Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

24V

Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

Dual-Channel (PNP device)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

112 www.bannerengineering.com - Tel: 763.544.3164

OFF

OFF

Page 113

SC22-3/-3E Safety Controller Instruction Manual Complementary (2 or 3 terminals) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time.

24V

S1

S2

Complementary (PNP device) OFF

ON

S1

S2

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. See Safety Input Device Properties on page 27.

10.11.4 Mute Enable (ME) The Mute Enable input is a non-safety-rated input. When the input is closed, the Safety Controller allows a mute condition to occur; opening this input while the System is muted will have no effect. Typical uses for Mute Enable include: • Allowing the machine control logic to create a period of time for muting to begin • Inhibiting muting from occurring • Reducing the chance of unauthorized or unintended bypass or defeat of the safety system

Simultaneity Timer Reset Function The Mute Enable input can also be used to reset the simultaneity timer of the mute sensor inputs. If one input is active for longer than three seconds before the second input becomes active, the simultaneity timer prevents a mute cycle from occurring. This could be due to a normal stoppage of an assembly line that may result in blocking one mute device and the simultaneity time running out. If the ME input is cycled (closed-open-closed) while one mute input is active, the simultaneity timer is reset, and if the second mute input becomes active within three seconds, a normal mute cycle begins. The timing requirement for the closed-open-closed is similar to the manual reset function. Initially, the input needs to be active (closed) for longer than 1/4 second, then open for longer than 1/4 second, but not longer than 2 seconds, and then must re-close to reset the simultaneity timer. The function can reset the timer only once per mute cycle (all mute inputs M1-M4 must open before another reset can occur).

10.11.5 Mute Lamp Output (ML) Some applications require that a lamp (or other means) is used to indicate when the safety device, for example, a light screen, is muted; the Safety Controller provides this through the status outputs. If a monitored output signal is required (see Warning below), status outputs O9 and O10 can be configured for a monitored output. The monitored output prevents the initiation of a mute after an indicator failure is detected. If the application requires compliance with UL 61496, Lamp Monitoring must be selected and the lamp used must meet applicable requirements. WARNING: Indication that the safety device is muted must be provided and be readily observable. Failure of this indication should be detectable and prevent the next mute, or operation of the indicator should be verified at suitable intervals. Lamp monitoring must be selected if the application requires compliance with UL 61496.

www.bannerengineering.com - Tel: 763.544.3164

113

Page 114

SC22-3/-3E Safety Controller Instruction Manual

10.11.6 Muting Time Limit (Backdoor Timer) The muting time limit (Backdoor Timer) allows the user to select a maximum period of time that muting is allowed to occur. This feature hinders the intentional defeat of the muting devices to initiate an inappropriate mute. It is also useful for detecting a common mode failure that would affect all mute devices in the application. The timer begins when the second muting device makes the simultaneity requirement (within 3 seconds of the first device), and allows a mute to continue for the predetermined time. After the timer expires, the mute ends despite what the signals from the mute devices indicate. If the input device being muted is in an Off state, the mapped OSSD outputs turn Off and must be manually reset (if the input device is configured for manual reset). WARNING: Muting Time Limit An infinite time for the backdoor timer (disabling) should be selected only if the possibility of an inappropriate or unintended mute cycle is minimized, as determined and allowed by the machine’s risk assessment. The user is responsible to make sure that this does not create a hazardous situation.

10.11.7 Mute on Power-Up If selected (see Mute Function on page 34), the Mute on Power-Up function initiates a mute when: • Power is applied • The Mute Enable input is closed (if configured) • The safety device inputs are active (closed) • Either M1-M2 or M3-M4 (but not all four) are closed If Normal or Automatic Power-Up mode is configured and all other mut conditions are satisfied, a mute event will start immidiately. If Manual Power-Up mode is configured and all other mute conditions are satisfied, the first valid system reset will result in a mute event WARNING: Mute on Power-Up The Mute on Power-Up function should be used only in applications where: • •

Muting the System (M1 and M2 closed) when power is applied is required, and Using it does not, in any situation, expose personnel to any hazard.

10.11.8 Corner Mirrors, Optical Safety Systems, and Muting Mirrors are typically used with safety light screens and single-/multiple-beam safety systems to guard multiple sides of a hazardous area. If the safety light screen is muted, the safeguarding function is suspended on all sides. It must not be possible for an individual to enter the guarded area without being detected and a stop command issued to the machine control. This supplemental safeguarding is normally provided by an additional device(s) that remains active while the Primary Safeguard is muted. Therefore, mirrors are typically not allowed for muting applications.

10.11.9 Multiple Presence-Sensing Safety Devices Muting multiple presence-sensing safety devices (PSSDs) or a PSSD with multiple sensing fields is not recommended unless it is not possible for an individual to enter the guarded area without being detected and a stop command issued to the machine control. As with the use of corner mirrors (see Corner Mirrors, Optical Safety Systems, and Muting on page 114 ), if multiple sensing fields are muted, the possibility exists that personnel could move through a muted area or access point to enter the safeguarded area without being detected. For example, in an entry/exit application where a pallet initiates the mute cycle by entering a cell, if both the entry and the exit PSSDs are muted, it may be possible for an individual to access the guarded area through the “exit” of the cell. An appropriate solution would be to mute the entry and the exit with separate safeguarding devices. WARNING: Guarding Multiple Areas Do not safeguard multiple areas with mirrors or multiple sensing fields, if personnel can enter the hazardous area while the System is muted, and not be detected by supplemental safeguarding that will issue a stop command to the machine.