Page 115
SC22-3/-3E Safety Controller Instruction Manual
10.11.10 Mute Timing Sequences Power Safety Light Screen Mute Enable Mute Sensor 1
< 3s
Mute Sensor 2 Max. Time
Backdoor Timer
Max. Time
Safety Output Mute cycle ends due to the expiration of the Backdoor Timer
Mute cycle prevented due to open Mute Enable input
Figure 68. Timing logic: two mute sensors, mute enable, safety light screen, and limited mute time. Mutable safety device configured for Auto Reset. Power Safety Light Screen Mute Enable Mute Sensor 1 < 3s
Mute Sensor 2 Mute Sensor 3
< 3s
Mute Sensor 4 Backdoor Timer
Max. Time
Max. Time
Safety Output
Figure 69. Timing logic: four mute sensors, mute enable, safety light screen, and limited mute time. Optical screen configured for Auto Reset.
Power 2-Hand Inputs Mute Enable Mute Sensor 1 < 3s
< 3s
Mute Sensor 2 Backdoor Timer
Max. Time
Max. Time
Safety Output Mute cycle prevented due to open Mute Enable input Output remains OFF when mute cycle expires, even though THC is ON
Output remains OFF until THC is cycled
Figure 70. Timing logic: two mute sensors, ME, two-hand control, and limited mute time
NOTE: When a two-hand control is muted the outputs remain On until one of the mute sensors opens, another safety input device causes a stop, the mute time limit (backdoor timer) expires, a lockout occurs, or the Module loses power. Both hand control actuators must be released in order to start another cycle.