The text of a manual · part 17 of 18

SC22-3/-3E Safety Controller Instruction Manual: 11 Ethernet Reference

Pages 116 to 119 of 122, from SC22-3/-3E Safety Controller Instruction Manual

The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Banner SC22-3E

Page 116

SC22-3/-3E Safety Controller Instruction Manual

11 Ethernet Reference The Industrial EtherNet Guide provides details and examples to aid in the setup and connection to your PLC. Contact Banner Engineering for this guide and the EDS files for the SC22-3E controller. Information on Ethernet functionality can also be found in the following sections of this manual: Ethernet-Compatible Model on page 9: Description of supported Ethernet protocols Personal Computer Interface (PCI) on page 14: Accessing Ethernet functionality Virtual Status Outputs on page 17: See Warning SC22-3 Safety Controller Starter Kit Models on page 21: SC22-3E model options and accessory Ethernet cordsets Network Interface (Model SC22-3E only) on page 23: Network Interface specifications Virtual Status Outputs on page 49 : Detailed description, including the Auto Configure function Configuration Tools on page 50: Descriptions of PCI icons and fields Build a Configuration on page 51: Examples of the Ethernet support documents

11.1 Ethernet Setting Access To access the Ethernet settings, click on the Network Settings icon of the PCI and check the Enable Network Interface box (see figure below). By default, the Safety Controller communicates using Modbus/TCP and EtherNet/IP. IP Address. The factory default IP address for the Safety Controller is: 192.168.0.254 Subnet Mask. The factory default Subnet Mask for the Safety Controller is: 255.255.255.0 Gateway Address. By default, the Safety Controller Gateway Address is disabled. Link Speed and Duplex Mode Options. The following speed and duplex options are available. The factory default setting is Auto Negotiate; other options, available by drop-down list, are: 100 Mbps / Full Duplex 100 Mbps / Half Duplex 10 Mbps / Full Duplex 10 Mbps / Half Duplex Reset Advanced Network Settings. This will cause the advanced network settings to revert back to the factory default settings. Ethernet TCP. Default port: 502 (TCP502); Device ID: 1

Figure 71. Ethernet Settings Menu (advanced view shown)

11.2 EtherNet/IP Assembly Objects Input (T->O) Assembly Objects The following Instance IDs are supported: • •

116

Instance ID 100 (0x64) with a size (data length) of four 16-bit words. Instance ID 100 is used to access basic information about the Virtual Status Outputs. Instance ID 101 (0x65) with a size (data length) of forty-two 16-bit words. Instance ID 101 is used to access advanced information (inclusive of the basic information) about the Virtual Status Outputs. www.bannerengineering.com - Tel: 763.544.3164

Page 117

SC22-3/-3E Safety Controller Instruction Manual •

Instance ID 102 (0x66) with a size (data length) of one hundred forty 16-bit words. Instance ID 102 is used to access fault log information (it provides no Virtual Status Output information). The format of the fault log information starts with a time stamp and may be found in the appropriate Fault Log Support file (see section Support Files on page 117).

Output (O->T) Assembly Object The Output Assembly Object is not implemented. However, some EtherNet/IP clients require one. If this is the case, use Instance ID 112 (0x70) with a data length of two 16-bit words. Configuration Assembly Object The Configuration Assembly Object is not implemented. However, some EtherNet/IP clients require one. If this is the case, use Instance ID 128 (0x80) with a data length of 0.

11.3 Support Files During installation of the PCI, the following support files are copied to the computer’s Program Files directory (C:\Program Files\Banner Engineering\Banner SC\Network Tables), in both .csv and .pdf formats. These files contain network communication information and fault diagnostic information. To access the files, use your computer’s navigation tools (for example, “My Computer” or Windows Explorer). Any references in this section to files are referring to these support files. All of these files are also available on www.bannerengineering.com. • Fault Index Table (applies to all protocols) • MB Fault Log • MB System Info • EIP Fault Log • EIP Fault Log Explicit Messages • EIP System Info Explicit Messages • PCCC Fault Log • PCCC System Info An additional file is included with a .eds format. This file is a simple text file used by network configuration tools to help identify products and easily commission them on a network.

11.3.1 Retrieving Current Fault Information To retrieve information via network communications about a fault that currently exists, use the following procedure: 1. Read the Fault Flag location. If this location is set, then a fault exists. 2. Read the Fault Index location. The number in this location provides an index value used with a Fault Index Table file that contains fault diagnostic information. 3. Access the data in the Fault Index Table file using the Fault Index number. The data in the file provides a specific fault number, a short fault description, a longer fault description, and a remedy.

11.3.2 Retrieving Fault Log Information To retrieve information via network communications about faults contained in the fault log, the following procedure may be used: 1. Read the number in the Seconds Since Power-up location in the appropriate System Info file. The number indicates, in seconds, how long the Safety Controller has been ON. 2. Compute the real time that the Safety Controller powered up (hour, minute, second) by using the Seconds Since Power-up number with a real time reference. 3. Read the number in the Time Stamp location in the Fault Log file. The number indicates, in seconds, when the fault happened, relative to a power-up. 4. Compute the real time when the fault occurred by using the Time Stamp number with the power-up time of the Safety Controller, computed in Step 2. 5. Read the Fault Index location in the Fault Log file. The number provides an index value used with a Fault Index Table file that contains fault diagnostic information. 6. Access the data in the Fault Index Table file using the Fault Index number. The data in the file provides a specific fault number, a short fault description, a longer fault description, and a remedy.

www.bannerengineering.com - Tel: 763.544.3164

117

Page 118

SC22-3/-3E Safety Controller Instruction Manual

11.4 Table Row and Column Descriptions The following are table row and column descriptions (listed in alphanumeric order) for the register maps found on the PCI, the computer, and the Banner website. 3X/4X (Modbus/TCP) This column lists the offset for a 30000 Input register or a 40000 Holding register. Corresponds to Virtual Output # (Fault Log File) In the Fault Log file, this provides another way to link the fault to an input, output, or system via a Virtual Status Output (if assigned). If, for example, VSO7 is assigned to track a gate switch which has a fault in the wiring, this number will be 7. If Virtual Status Outputs are not assigned, this number will be 0. Data Type UINT unsigned integer - 16 bits

UDINT unsigned double integer - 32 bits

Word bit string - 16 bits

Dword bit string - 32 bits

String

Two ASCII characters per Word (see String Format below)

Octet reads as each byte translated to decimal separated by a dot

Hex reads as each nibble translated to hex, paired, and then separated by a space

Date Code Format (System Info File) YYWWL - Two ASCII characters for the year, followed by two characters for the week indicating the date of manufacture. This is followed by a letter code for the manufacturing location. See “String Format” below for more details. Fault Flag (Advanced View) If the particular input or output being tracked causes a lockout, a flag associated with that virtual output will be set to 1. In Modbus/TCP, this can be read as a Discrete input, Input register, or Holding register. Fault Index (Advanced View) If the Fault Flag bit is set for this virtual output, this index number provides a pointer to a particular fault code and message in the Fault Index Table which is provided in a .csv or .pdf file on the CD that came with the Safety Controller. Function The function that determines the state of that virtual output. This function is assigned during configuration of the virtual outputs using the PCI software. Name of I/O/system (Fault Log File) If the fault is system related, the name “System” or “Internal” will be used. Otherwise, the name of the input or output associated with the fault will be given. Refer to “String Format” below for more details. Operating Mode (System Info File) 0

Reserved

1

Reserved

2

Manual Power-up Mode ― waiting for System Reset

3

Normal Operating Mode (including if I/O faults are present)

4

Configuration Mode

5

Waiting for System Reset (exiting Configuration Mode)

6

System Lockout

REG:BIT Indicates the offset from 30000 or 40000 followed by the specific bit in the register. Reserved Banner has reserved these registers for internal use. Seconds Since Power-up (System Info File) The time in seconds since power was applied to the Safety Controller. May be used in conjunction with the time stamp in the Fault Log and a real time clock reference to establish a time that a fault occurred. 118 www.bannerengineering.com - Tel: 763.544.3164

Page 119

SC22-3/-3E Safety Controller Instruction Manual SO1/2/3 is OFF Due to… (Advanced View) A bit will be set high if the input device associated with this virtual output is a reason why the output is off. String Format (Ethernet/IP and PCCC Protocol) The default format Ethernet/IP string format has a 32 bit length preceding the string (suitable for ControlLogix). When configuring the network settings using the PCI, you may click Advanced to change this setting to a 16 bit length which corresponds to the standard CIP “String”. Note, however, that when reading an Input Assembly that includes a string with a 16 bit length, the string length will be preceded by an extra 16 bit word (0x0000). The string itself is packed ASCII (2 characters per word). In some systems, the character order may appear reversed or out of order. For example, the word “System” may read out as “yStsme”. The advanced network settings option in the PCI also allows you to “Swap” characters so that it reads correctly. String Format (Modbus/TCP Protocol) The string format is packed ASCII (2 characters per word). In some systems, the character order may appear reversed or out of order. For example, the word “System” may read out as “yStsme”. The advanced settings option in the PCI allows you to “Swap” characters so that it reads correctly. While the string length is provided, it is usually not required for Modbus/TCP systems. Note that if you use string length for Modbus/TCP, the length format corresponds to the settings used for Ethernet/IP. Time Stamp (Fault Log File) This is the time since power up, in seconds, when the fault occurred. To use this information, such as for fault analysis, refer to section Support Files on page 117. Virtual Status Output The reference designator associated with a particular Virtual Status Output, for example, VO10 is Virtual Status Output 10. VO Status This identifies the location of a bit indicating the status of a Virtual Status Output. In the case of Modbus/TCP, the state of the Virtual Status Output can be read as a discrete input, as part of an input register or holding register. The register given is the offset from 30000 or 40000 followed by the bit location within the register.

www.bannerengineering.com - Tel: 763.544.3164

119