Page 21
Chapter 4 – Installation for Fanuc 11/12
Part Programs
4. NOTE: Before backing up the Part Programs, check to see if there are any programs listed in the 8000’s or 9000’s. If there are, make sure the Program Protect Parameter, NC parameter 2201--bit 0, must be a 0 for the 9000 series part-programs and parameter 11--bit 0 must be a 0 for the 8000 series programs. This will allow ALL part-programs, macros and common variables (in the Setting Screen) to be properly output Make the computer ready to receive the programs.
Select EDIT Mode.
Press the PRGRM function key.
Press PUNCH + ALL
All of the programs will be punched out.
Tool Offsets
5. Make the computer ready to receive the Tool Offset data.
Confirm that EDIT Mode is selected.
Press the OFFSET function key.
Press PUNCH + TOOL
The Tool Offsets will be punched out.
Macro Variables
6. Punch out an MACRO (500 and above) variables if present as well.
Fanuc 11 Quickload – BMU Mounted on MME in Slot Next to Power Supply
M100700D Page 19
Page 22
Chapter 4 – Installation for Fanuc 11/12
Quick-Load Procedures for Fanuc 11/12 Time Needed: Tools Needed: Components: Control:
1 hour (approx.) 1 Philips Screwdriver 1 MME memory board Fanuc 11A, 11B and 12
Before starting the installation, power on the control and verify that the machine tool is in good working order.
Important!
Make sure that you have a current backup of the NC parameters, Tool Offsets, Pitch Error Compensation, and Part Programs. For instructions on downloading your control’s information, refer to previous section entitled “Backup Your Control”. 1. Inspect the Memex Memory Engine (MME) for any damage during shipping. Also check that the “CNC Type” jumpers have been set to either Fanuc 11 or 12.
Remove the Bubble memory
Install the MME memory.
2. With the Fanuc control powered off and the Emergency Stop (E-STOP) button depressed, gain access to the main masterboard. Find the Bubble Memory Unit (BMU) board on the right-hand side of the masterboard, and carefully remove it with a Philips screw driver. Carefully place the BMU in the anti-static box supplied, and set it aside. 3. Install the MME in the slot where the BMU was removed once again using the Philips screwdriver. 4. With the 7 + 9 keys depressed on the front MDI panel, power on the
CAUTION!
control. This action will cause the control to start-up and immediately clear the entire memory of the MME. If the control will not power on at this point, check that the cabinet door interlock is bypassed. When the control powers on, it will eventually show the IPL Screen. 5. Power off the control.
MME Quickload!
6. Mount the original BMU onto the blue “BMU” connector found on the MME board. Screw down the top screw into the MME to secure the BMU properly.
M100700D Page 20
Page 23
Chapter 4 – Installation for Fanuc 11/12
Copy the Data
7. Power on the control. It should start-up normally with the original BMU in control. During this process parameter data is being relocated to the appropriate memory areas in the MME. To ensure a complete transfer, view the parameter screen, tool offset screen, part program screen,…etc. If it all looks normal, release the E-STOP button. 8. Power off the control and carefully remove the BMU. Set the BMU aside in the anti-static bag provided.
Check the Parameters
9. Power the control and check the functionality of the machine at this point. Re-Zero the axes, test the spindle, test the tool changing mechanism (be sure you get the tool you request and that it goes into the correct pocket), check out any pallet changers and other peripherals. Caution: Keep your rapid and feed rate overrides low. The machine may not behave the way you might expect it to. If abnormalities in the operation are noticed, check all of the system parameters in case they may not have been properly restored by the Quick-Load (if so go to step 14). 10. Initiate a Parameter Sentry “SAVE” operation to save your parameters to non-volatile memory. It is best to do this when there are no part programs present as the directory that is saved should be clear of entries. (Note that powering on in IPL mode and clearing files “3 INPUT”, then “7input” is needed) 11. Test your machine thoroughly. You can proceed to the section of this manual entitled “Verify Your Control” for assistance.
You are done… 12. If an error has occurred during the installation of your MME it is possible an alternative method may have to be used. Follow steps 1 through 4 as per the above directions but before continuing with step 5 complete the following extra steps. 13. Remove the Option Jumper #2 on the MME board. This will limit the Parameter Sentry system to protecting the System Label only. Following are the steps required to correctly write the System Label. After you follow through with the remainder of the Quick-Load procedure, you will have to restore the over-written System Label with backed up version that is guarded by Parameter Sentry. 14. With the . + - keys depressed on the front MDI panel, power on the control. When the control powers on it will eventually show the IPL M100700D Page 21
Page 24
Chapter 4 – Installation for Fanuc 11/12
Screen 15. At the prompt, you will enter 9
9 then INPUT . Use the input button to the right of the MDI keypad. 16. Press Y to initialize the system label. 17. Enter the number you wrote down from parameter 9000 on the parameter sheet, for the No. of Axes. Beginning with parameter 9100, enter the HEX value of each parameter for the option numbers that need to be entered. If you incorrectly enter a number at this point, you will have to press INPUT through the remaining Options, then go back and begin the process again. 18. When you reach the end press Y to clear the files.
19. Go back to the IPL menu and press 6 to End IPL. If you should get any alarm in the 900’s, call our toll free tech support line. 20. At this point initiate a Parameter Sentry save by moving the toggle switch on the right side of the MME towards the SAVE position, then pressing the Push Button. The SAVE light should momentarily light up. See Using the MME Parameter Sentry System for more detail. 21. Complete steps 8 through 10 above then continue. Once the following steps have been completed continue with 11 to 13 above. 22. Power on the control while holding . + - . This will again get you into the IPL screen. 23. Initiate a Parameter Sentry restore operation by moving the toggle switch on the right side of the MME towards the RESTORE position, then pressing the Push Button. The RESTORE light beside the toggle switch should momentarily light up. 24. Power off the control, then replace Option Jumper #2 on the MME. (continue with step 6 to 11 as per above in this section)
M100700D Page 22
Page 25
Chapter 4 – Installation for Fanuc 11/12
Manual Installation Procedures for Fanuc 11/12 Time Needed: Tools Needed: Components: Controls:
2 hours (approx.) 1 Philips Screwdriver 1 MME memory board Fanuc 11A, 11B and 12
Before starting the installation, power on the control and verify that the machine tool is in good working order.
Important!
Make sure that you have a current backup of the NC parameters, Tool Offsets, Pitch Error Compensation, and Part Programs. For instructions on downloading your control’s information, refer to previous section entitled “Backup Your Control”. 1. Inspect the Memex Memory Engine (MME) for any damage during shipping. Also check that the “CNC Type” jumpers have been set to either the Fanuc 11 or 12 (depending on control type).
2. With the Fanuc control powered off and the Emergency Stop (E-STOP) Remove the button depressed, gain access to the main masterboard. Find the Bubble Bubble memory
Memory Unit (BMU) board on the right-hand side of the masterboard, and carefully remove it with a Philips screw driver. Carefully place the BMU in the anti-static box supplied, and set it aside.
Install the MME memory.
3. Install the MME in the slot where the BMU was removed once again using the Philips screwdriver. 4. With the 7 + 9 keys depressed on the front MDI panel, power on the
CAUTION!
control. This action will cause the control to start-up and immediately clear the entire memory of the MME. If the control will not power on at this point, check that the cabinet door interlock is bypassed. When the control powers on, it will eventually show the IPL Screen. 5. At the prompt, you will enter 9
9 then INPUT . Use the input button to the right of the MDI keypad. 6. Press Y to initialize the system label.
M100700D Page 23
Page 26
Chapter 4 – Installation for Fanuc 11/12
7. Enter the number you wrote down from parameter 9000 on the parameter sheet, for the No. of Axes. Beginning with parameter 9100, enter the HEX value of each parameter for the option numbers that need to be entered. If you incorrectly enter a number at this point, you will have to press INPUT through the remaining Options, then go back and begin the process again. 8. When you reach the end press Y to clear the files.
9. Go back to the IPL menu and press 6 to End IPL. If you should get any alarm in the 900’s, call our toll free tech support line. 10. Locate the Parameter Write Enable (PWE), parameter 8000 in the Settings (service) Screen, and change it to a 1 to enable PWE in MDI mode. 11. Now serially reload the remaining parameters or if need be re-enter these by hand from your parameter tape, list, or backup. 12. Once the NC parameters are reloaded, power off the control then power it on again. Turn on the PWE parameter again (8000), then press the NC/PC button and reload all of the PC parameters. When you are confident that all of the parameters are correct, turn off the power. 13. Power on the control and release the E-Stop. The control should start-up normally. Check the functionality of the machine at this point. Re-zero the axes, test the spindle, test the tool changing mechanism, check out any pallet changers and any peripherals. 14. Once the machine has been proven, now would be a good time to do a Parameter Sentry save. This will save a backup copy of all your critical machine parameters. Refer to the Using the parameter Sentry System sheet for more detailed instructions. 15. Now reload your Programs and Tool Offset data, your control should be fully operational, with the enhanced performance of the MME.
M100700D Page 24
Page 27
Chapter 4 – Installation for Fanuc 11/12
Installation Checklist for Fanuc 11/12 Check Machine - Power On - Check for Machine Problems Before You Start. Backup Parameters and Programs. Power Off. Depress E-STOP Mount MME. Power On the Control with 7 + 9 Enter 9
9 depressed, to erase MME.
in IPL menu.
Enter the Number of axes and all of the Option data. Press 6 to End IPL . Set PWE then restore the base Service Parameters. Reload the remaining NC Parameters. Power OFF then ON. Set PWE, then reload the PC Parameters. Add in any MACRO Variables, tool offsets or MACRO part programs if needed. Power OFF then ON. Check parameters and machine operation thoroughly. At this complete state, you can optionally save your parameters with the on-board Parameter Sentry System “save” feature. Complete.
M100700D Page 25
Page 28
Chapter 5 – Appendix
Appendix Technical Summary for Fanuc 6 PUNCHING: Punch NC Parameters Punch Pitch Error Compensation Punch All Programs Tool Offsets
-
EDIT mode, PARAM screen, key “P-9999”, Punch EDIT mode, PARAM screen, key “P-9998”, Punch EDIT mode, PGRM screen, key “O-9999”, Punch EDIT mode, OFSET screen, key “P-9999”, Punch
READING: Load NC Parameters Load Pitch Error Compensation Load All Programs
-
EDIT, E-Stop, PWE, PARAM screen, key “P-9999”, Read EDIT, E-Stop, PWE, PARAM screen, key “P-9998”, Read EDIT mode, PGRM screen, Mem. Protect Key, key “O-9999”, Read
CLEARING: Delete Directory and Programs Delete Entire BMU
-
Power On holding “RESET” + “DELETE” PWE enabled, Power On holding “0”+”DELETE”
Fanuc 6A Masterboard: A20B-0007-0010 Parameter 2.5 7.7 9.1 24.0 25
Software: 99x
Function 1= punch 0=no punch 1=LF,CR,CR 0=CR,LF 1=ISO 0=EIA 1=2 0=1 9600 = 1111 1111 4800 = 1110 1111 2400 = 1100 1111 1200 = 1100 1110 600 = 1100 1100 300 = 1000 1100
Maximum Memory: 320 Meters Description Punch Option Enable End of line on punch Format (choose ISO) Stop Bits Baud Rate for Serial Port
Fanuc 6B (early version) Masterboard: A20B-0008-0410 Software: 900 Level Maximum Memory: 901/06 or later 902/06 or later Parameter (.bit) 2.5 3.3 7.7 310-313.4 310-313.5 310-313.7
Function 1= punch 1=ISO 1=LF,CR,CR 1=2 1=Not Used 1=Tape Feed
0=no punch 0=EIA 0=CR,LF 0=1 0=DC Codes 0=No Feed
320 Meters (128k) 1280 Meters (512k) 1280 Meters (512k)
Description Punch Option Enable Format (choose ISO) End of line on punch Stop Bits (leave at 0 - for standard Fanuc E-7-1) Software handshaking (leave at 0 for serial) Punches tape feed at start of file (leave at 0)
M100700D Page 26
Page 29
Chapter 5 – Appendix
Parameter 310-313.0-3
318.7 319.7 340 341
Function 9600 = xxxx 1010 4800 = xxxx 1001 2400 = xxxx 1000 1200 = xxxx 0111 600 = xxxx 0110 300 = xxxx 0101 1=Not Editable 0=Editable 1=Not editable 0=Editable 2=Serial 2=Serial
Description Baud Rate for Serial Port for Fanuc 6B
Protect 9000 series programs from editing Protect 8000 series programs from editing Input Device Select Output Device Select
Fanuc 6-B2 (or Fanuc 6B Level 2) Masterboard: A16B-1000-0030 Software Versions: (Power up in E-Stop to check software version) 320 Meters Memory Maximum -Mxx (06, 14, 15, 16, 21, 22, 25, 26, 27, 28, 30, 31, 33 Ver 06, 35, 40, 42, 44, 46, 81, 83 & 85) 1280 Meter Maximum -Mxx (01 to 05, 07 to 12, 33, 37, 39, 45, 1A to 1D, 47 to 7C, 87 to F3) Standard Fanuc Serial Port: (DB-25 Female) 1 = Frame Ground 2 = Transmit Data 3 = Receive Data 4 = Ready To Send 5 = Clear To Send
6 = Data Set Ready 7 = Signal Ground 8 = Carrier Detect 20= Error (Data Terminal Ready) 25= +24 Volts
The usual software handshaking cable configuration has 2,3 & 7 connected through, with 4&5 jumpered (hardware handshake lines) and pins 6,8 & 20 jumpered on the Fanuc side only. Bubble Memory Board Sizes (for all): A87L-0001-0015 A87L-0001-0016 A87L-0001-0017 A87L-0001-0105 A87L-0001-0018 A87L-0001-0084 A87L-0001-0085 A87L-0001-0086
20 M 40 M 80 M 80 M 320 M 320 M 640 M 1280 M
8K 16 K 32 K 32 K 128 K 128 K 256 K 512 K
Remember to check SETTING Screen Data. Tool Offsets can be downloaded but the G10/G11 option must be enabled (set parameter 3.1 to a 1) to reloaded them. They are loaded serially into program memory, then executed like a regular Part Program. NOTE: Parameters are listed as “P” “number.bit” (e.g. P 2 bit 5 is P2=xx1x xxxx)
M100700D Page 27
Page 30
Chapter 5 – Appendix
Technical Summary for Fanuc 11/12 PUNCHING: Punch NC Parameters Punch Pitch Error Compensation Punch All Programs Tool Offsets
-
EDIT mode, SERVICE screen, key PUNCH - ALL EDIT mode, SERVICE screen, key PUNCH - PITCH EDIT mode, PRGRM screen, key PUNCH - ALL EDIT mode, OFFSET screen, key PUNCH - TOOL
READING: Load NC Parameters Load Pitch Error Compensation Load All Programs
-
EDIT, E-Stop, PWE, PARAM screen, key READ - ALL EDIT, E-Stop, PWE, PARAM screen, key READ - PITCH EDIT mode, PGRM screen, Mem. Protect Key, key READ - ALL
CLEARING: Delete Directory and Programs Delete Entire BMU
-
EDIT mode, PRGRM screen, key DELETE - PROGRAM - ALL PWE enabled, Power On holding “7” + “9”
Fanuc 11A Masterboard: A20B-0007-0010 Software: 99x Parameter 0.2 0.3 0.4
Function 1=Without 1=LF 1=EIA
Maximum Memory: 320 Metres
0=With 0=LF,CR,CR 0=ISO
Description Parity Bit End of line on punch Punch Code Format (choose ISO)
See parameters 5111 and 5112 for STOP BITS and BAUD RATE information. 20
Input device interface number for foreground 0: Tape Reader 1: RS-232-C interface 1 2: RS-232-C interface 2 3: RS-232-C interface 3 10: Remote (DNC) 11: 20mA current type interface (ASR33, ASR44) 13: RS-422 interface
21
Output device interface number for foreground (Same as 20 except no Tape Reader option)
22
Input device interface number for background (Same as 20)
23
Output device interface number for background (Same as 20 except no Tape Reader option)
5001 5002 5003 5011 5013
I/O device No. to be connected to RS232C interface 1 I/O device No. to be connected to RS232C interface 2 I/O device No. to be connected to RS232C interface 3 I/O device No. to be connected to ASR33/44 interface I/O device No. to be connected to RS422 interface
5110
Specifications number of I/O device corresponding to device number 1 M100700D Page 28