MASTER FORMAT, ANALOG INPUT AS SETPOINT ASSUMPTIONS

Oo Apump delivers 15 gallons/minute when the motor rotates at 1725 RPMs.

oO An analog POT connected to the M-Drive analog input produces a 5 volt DC level when the motor rotates at 1725 RPMs.

© Both Setpoint and the Tach are to indicate gallons per minute.

To accomplish these objectives, program the M-Drive as follows:

Control Parameter

CP-84

CP-61

CP-63

CP-31

CP-34

CP-20

CP-22

Parameter Title

Analog Function

Primary Scaling Format

Primary Display Format

PPR Feedback

Primary RPM MAX Feedback

Primary Setpoint Engn. Units

Primary Display Engn. Units

Entered

Data Remarks

4 Allocates Analog Input as CP-1 (Setpoint 1) replacement.

1 Designates Master as the Primary Scaling Format.

1 Designates Master as the Primary Display Format

60 Designates the value used as a multiplier to obtain the desired authority of the analog input.

1725 Designates maximum RPM of Feedback sensor shaft.

30.00 Designates the maximum setpoint engineering units at the maximum analog level of 10 VDC.

15.00 Designates the maximum display engineering units.

Page 8-9

Page 86 read from a scan by OCR; it may hold reading errors

MASTER FORMAT, ANALOG INPUT AS FEEDBACK ASSUMPTIONS

O Apump delivers 15 gallons/minute when the motor rotates at 1725 RPMs.

© An analog tach connected to the M-Drive analog input produces a 10 volt DC level when the motor is to rotate 1725 RPMs.

0 Both Setpoint and the Tach are to indicate gallons per minute.

To accomplish these objectives, program the M-Drive as follows:

Control Parameter Entered

Parameter Title Data Remarks

CP-84 Analog 2 Allocates Analog Input as feedback frequency Function replacement

CP-61 Primary 1 Designates Master as the Primary Scaling Scaling Format Format

CP-63 Primary 1 Designates Master as the Primary Display Display Format Format

CP-31 PPR 60 Not Entered. Automatically entered by the Feedback M-Drive and cannot be altered.

CP-34 Primary 4095 Not Entered. Automatically entered by the RPM MAX M-Drive and cannot be altered. Feedback

CP-20 Primary 15.00 Designates the maximum setpoint engineering Setpoint units. Engn. Units

CP-22 Primary 15.00 Designates the maximum display engineering Display units. Engn. Units

FOLLOWER FORMAT, ANALOG INPUT AS EXTERNAL REFERENCE ASSUMPTIONS

Oo The Setpoint and Tach are to reflect the flow ratio in gallons/minute of B to A.

Q The Motor/Pump combination used for Component A delivers 10 gallons /minute at 1725 RPMs.

QO The Motor/Pump combination used for Component B delivers 30 gallons/minute at 1725 RPMs.

Page 8-10

Page 87 read from a scan by OCR; it may hold reading errors

0 An analog tach produces 10 VDC when the motor on Component A is at 1725 RPMs. 0 A930 tooth gear is used for the follower feedback (Component B)

CALCULATIONS

1. Determine the flow ratio that exists when both components are flowing at maximum rates.

I/minute mponent B

= 3.000

10 Gal/minute (Component A)

To accomplish the above objectives, program the M-Drive as follows:

Control Parameter

CP-84

CP-62

CP-64

CP-37

CP-36

CP-31

CP-30

CP-21

CP-23

Parameter Entered Title Data Analog 1 Function Secondary 2 Scaling

Format Secondary 2 Display

Format Secondary 1725 RPM

Feedback Max

Secondary 4095 RPM

External

Ref. MAX

PPR 30 Feedback

PPR 60 External Reference

Secondary 3.000 Setpoint Engn. Units

Secondary 3.000 Display Engn. Units

Remarks

Allocates the analog input as ext. ref. freq. replacement

Designates Follower as the Secondary setpoint scaling format

Designates Follower as the Secondary display scaling format

Maximum RPM of the shaft which the feedback sensor monitors

Not Entered. Automatically entered by the M-Drive and cannot be altered.

Number of teeth on the gear or number of lines on the encoder used for feedback

Not Entered. Automatically entered by the M-Drive and cannot be altered.

Page 8-11

Page 88 read from a scan by OCR; it may hold reading errors

OFFSET FORMAT, ANALOG INPUT AS AUX FREQUENCY INTRODUCTION The Offset Speed Control format differs from Follower Format in two respects:

1. Offset provides for a second process variable in addition to the External Reference Frequency.

2. Offset allows the programmer to specify a speed difference (or offset) from the normally calculated Follower speed.

Consequently, the Offset Format motor speed is controlled by four variables: Ratio Setpoint, External Reference Frequency, Analog Input as Aux (Offset) Frequency, and the user specified offset.

Appendix B lists the actual formulas used to calculate the motor speed for both Follower Format and Offset Format.

OFFSET FORMAT EXAMPLE

Figure 8-2 below illustrates a simple web process. Note that this application contains a loop which is controlled by a dancer POT. The example uses a dancer POT on the Analog Input. Depending on the output value, the M-Drive adjusts the speed of the Follower Motor up or down as required to maintain the dancer POT position.

Follower J3=5 be ' | J3-2 “ M-Drive 33-5 Master M-Drive J4-16

Dancer POT

Figure 8-2: Web Process illustrating Offset Format with Analog Input Page 8-12

Page 89 read from a scan by OCR; it may hold reading errors

Recall that in this case two inputs are used by the Follower M-Drive to determine the required follower Motor RPM: Line Speed (the external reference supplied by the Master Motor Feedback), and dancer POT position (the analog input). Also note that it is possible to control the gain on the POT displacement from the center position and to bias or offset the result with the user specified constant. The Tach is explained later in this chapter.

This example uses Secondary Mode, but the Primary Mode would work as well.

ASSUMPTIONS

© Nip rolls in Figure 8-1 are 1 foot in circumference O Follower Motor is to draw the web at the same linear Speed as the Master

(1800 feet per minute at 1800 RPM)

oooc$c$o

Both gears have 60 teeth Master is scaled as per chapter six (Page 6-5)

Desired Follower Setpoint is 1.000

POT output range is 0 - 10 Volts (5 volts = dancer centered)

Full scale authority of the dancer POT is 10% of full speed (l.e., a 10 Volt change in analog input should result in a 180 RPM change in the follower motor speed).

Ignoring the dancer pot, first program the M-Drive to follow at the proper line speed:

Control Parameter Entered

Parameter Title Data Remarks

CP-62 Secondary 3 Designates Secondary as Offset Format Scaling Format

CP-37 Secondary 1800 Maximum RPM of the shaft which the feedback RPM Feedback Sensor is monitoring (normal operation) Maximum

CP-36 Secondary 1800 Maximum RPM of the shaft which the external RPM External reference sensor is monitoring Reference (normal operation) Maximum

CP-21 Secondary 1.000 Desired setpoint when the Ext. Ref. and Setpoint Feedback shafts are rotating at the speeds Engineering entered at CP-37 and CP-36 Units

CP-31 PPR 60 Number of teeth on the gear or number of lines Feedback on the encoder used for feedback

CP-30 PPR Ext 60 Number of teeth on the gear or number of lines Ref. on the encoder used for external reference

Page 8-13

Page 90 read from a scan by OCR; it may hold reading errors

The next step is to program the analog input which represents the Dancer POT position. Two characteristics of this input must be controlled: Offset and Gain. The Offset determines which equivalent frequency will have no effect on the M-Drive’s speed (i.e., which position the dancer POT stabilizes at). The Gain determines how large an impact on the speed a given change in the analog input will have.

The output of the analog converter is 4095 when the analog input is at 10 Volts. To obtain the equivalent frequency value, a data entry of 4095 is made for the Maximum AUX RPM parameter and 60 for the PPR parameter. This would give the dancer 100% authority at the 10 volt level.

Recall that the authority or gain of the dancer POT was assumed to be 10%. To accomplish this, entries are made indicating that the maximum expected equivalent Auxiliary Frequency is 40,950 Hz when if fact it will never exceed the 4095 output of the analog converter. This provides the 10 to 1 reduction needed.

(CP-32 = 60 * 100% trim desired)

Control Parameter Entered

Parameter Title Data Remarks

CP-84 Analog 3 Allocates analog input as offset frequency Function replacement (must be entered first).

CP-38 Secondary 4095 Not Entered. Automatically entered by the RPM Auxil. M-Drive and cannot be altered. Maximum

CP-32 PPR Aux. 600 These two entries imply the 40,950 Hz Ref. as required

The last step is to enter an offset so that a centered POT (5 Volts) has no effect. This offset depends on the gain and is calculated using the formula:

-| AX * Rimx * Pf C= Ramx * Pa Where: C= the required offset Rimx = the maximum RPM of the feedback shaft (CP-37) in the example. Pf = PPR of the gear on the feedback shaft (CP-31) Ramx = the maximum equivalent RPM of the auxiliary shaft (CP-38 from above) Pa = equivalent PPR of the gear on the auxiliary shaft (CP-32 from above) AX = the equivalent frequency at which the POT is to be neutralized: 5 Volts * 4095 = 2048 10 Volts

Page 8-14

Page 91 read from a scan by OCR; it may hold reading errors

Replacing the variables with the example numbers, the Offset is then calculated. Note the minus sign in front of the right-hand expression.

- 2048 * 1800 * 60 C= 4095 * 600 C= -90 Control Parameter Entered Parameter Title Data Remarks CP-78 Secondary 90 Programming is complete Negative Offset

CP-77 and CP-78 work together in that CP-77 is a plus offset and CP-78 is a negative offset. Note that only one of these parameters can have a non-zero value at a time. Whenever an entry is made at one location, the M-Drive automatically sets the other to zero. Codes CP-75 and CP-76 work the same but are in the Primary Parameter group.

Page 8-15

Page 92 read from a scan by OCR; it may hold reading errors

ANALOG INPUT AS A SETPOINT

The Analog Input can also be used to replace one of the four setpoints, CP-1 through CP- 4. When the Analog Input is patched as a setpoint source, the setpoint value equals the Engineering Unit setpoint value (CP-20 or CP-21) when the Analog Input is at its maximum value (10 VDC or 20 mA).

For example, consider the following assumptions: oO The M-Drive selected setpoint is CP-1 0 The Engineering Units (CP-20) are 1000 gallons/minute Oo The Analog Input is at 5.0 Volts (50%)

CALCULATIONS SV = Al* EU Almax Where

SV = Setpoint Value Al = Analog Input level Aimax = 10 VDC or 20 mA EU = Engineering Units

Substituting the assumptions into the formula:

SV = 5.0 * 1000 = 500. 10.0

Thus, the Setpoint Value is 500 gallons/minute. This value can be observed at CP-1 when the analog input is patched as the setpoint source (i.e., when CP-84 equals 4).

ANALOG OUTPUT

The Analog Output can be used to provide an analog signal indicating the status of any of the M-Drive monitor variables or control parameters. To allocate the Analog Output to the desired variable or parameter, enter the code number for that variable into CP-80. For example, if it was desired to bring the Tach value out the Analog Output, a value of 40 should be entered for CP-80.

To range the Analog Output for the desired signal level, enter the maximum variable value for the selected variable corresponding to the maximum analog output into CP-81. For example, if the Tach value of 2000 was desired for the maximum analog output level (10 VDC or 20 mA), then a value of 2000 should be entered into CP-81. Note that negative variable values will produce negative analog signals.

The Analog Output is intended for monitoring M-Drive variables and system performance.

Caution should be exercised when using the Analog Output for cascade control as the Analog Output response is damped to approximately 1 HZ.

Page 8-16