Page 75

Installation

Chapter 3

Festo P.BE−CPX−SYS−EN en 0503b

3−1

Page 76

3. Installation

Contents

3.

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3−1

3.1

General instructions on installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−4 3.1.1 Connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−4 3.1.2 Settings for configuring the CPX field bus node . . . . . . . . . . . . . . . 3−7 3.1.3 Settings for configuring the pneumatics . . . . . . . . . . . . . . . . . . . . . 3−8 3.1.4 Selecting the power unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−9 3.1.5 Connecting the operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . 3−13 3.1.6 Connecting the field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−20

3−2

Festo P.BE−CPX−SYS−EN en 0503b

Page 77

3. Installation

Contents of this chapter

Further information

This chapter contains general instructions on installing CPX terminals. The following information in particular belongs here:

Accessories (connecting cables, sockets, power units)

Calculating the current consumption

Connecting the operating and load voltage supplies

Information on the power supply concept of the CPX terminal can be found in section 1.1.3. Important installation instructions on observing the UL quirements when the product is operated in every region of the United States and Canada, can be found in the UL−specific brief operating instructions. The relevant technical tions listed there also apply here. Installation instructions on the field bus node as well as on the I/O modules can be found in the manual for the relevant module or field bus node. Instructions on installing the pneumatic components can be found in the relevant pneumatics manual.

Festo P.BE−CPX−SYS−EN en 0503b

3−3

Page 78

3. Installation

3.1

General instructions on installation Please note Note the following if your application requires fulfilment of the specifications of the Recognized Component Marks for Canada and the United States": Rules for observing the UL approval can be found in the UL−specific brief operating instructions. The relevant technical specifications listed there also apply here. The technical specifications in this documentation may show different values.

Warning Sudden unexpected movement of the connected actuators and uncontrolled movements of loose tubing can cause injury to human beings or damage to property. Before carrying out installation and maintenance work, switch off the following: the compressed air supply the operating and load voltage supplies.

3.1.1

Connecting cable

Field bus cable

Use a suitable cable for your field bus system. Refer to the manual for your controller for the type of cable to be used. Also take into account here the distance and the field bus baud rate.

Operating voltage cable

Use a cable for the operating voltage with sufficient cross− sectional area. Avoid long distances between the power unit and the CPX terminal. Long operating voltage cables reduce the voltage supplied by the power unit. If necessary, ascertain the suitable cross−sectional area of the cable and the maximum permitted cable length in accordance with the general rule in section A.2.

3−4

Festo P.BE−CPX−SYS−EN en 0503b

Page 79

3. Installation

Preparing the connecting cable Caution The position of the pins on the plug is different from that on the socket. Pin assignment of the field bus interface see manual for the CP field bus node". Pin assignment of the sensor and actuator connections of input and output modules see manual CPX I/O ules". The operating voltage and load voltage connections are in the form of plugs. The pin assignment can be found in the following chapters. Use plugs and sockets from the Festo supply programme which match the outer diameter of the cables used.

Festo P.BE−CPX−SYS−EN en 0503b

3−5

Page 80

3. Installation

Preparing the plugs

Connect the plugs and cables as follows (example):

1. Open the plugs/sockets as follows:

1 Cable 2 Strain relief

·

Power supply socket: Insert the mains power socket into the operating age connection of the CPX terminal. Unscrew the housing of the socket. Then remove the connecting part of the socket which is inserted in the operating voltage connection.

·

Field bus socket and sensor plug (only with PG...): Loosen the centre knurled nut.

1 2

3 Housing 4 Connecting part

3

4 Individual parts of the socket and cable exit 2. Open the strain relief on the rear part of the housing. Then pass the cable through. 3. Remove 5 mm of insulation from the end of the cable and fit end sleeves on the strands. 4. Connect the ends of the conductors.

3−6

Festo P.BE−CPX−SYS−EN en 0503b

Page 81

3. Installation

5. Replace the connecting part on the housing of the plug/socket. Pull the cable back so that there are no loops inside the housing. 6. Tighten the strain relief.

3.1.2

Settings for configuring the CPX field bus node The reaction of the CPX terminal can be adapted to various requirements. Important application−specific settings can be made here with DIL switches directly on the field bus node.

Settings on the CPX node

CPX terminals can be coupled to various field buses. ing is made via the CPX node which is adapted to suit the relevant field bus. The following settings can be made pending on the CP node used:

The field bus configuration (e.g. field bus address)

Error reaction of the CPX terminal

Diagnostic reaction of the CPX terminal

Depending on the node used, the settings can be made, if necessary, with DIL switches on the node. The DIL switches are behind an easily accessible cover on the node. Information on the method of procedure as well as on the setting possibilities on your CPX field bus node can be found in the manual for the field bus node.

Festo P.BE−CPX−SYS−EN en 0503b

3−7

Page 82

3. Installation

3.1.3

Settings for configuring the pneumatics Pneumatics of type 12 (CPA) and type 03 (Midi/Maxi) From a technical viewpoint, the pneumatic interfaces for and type 12 represent electric modules with digital outputs. Detailed information on the pneumatic interfaces can be found in the manual for the CPX I/O modules.

Caution When the pneumatics have been converted or extended, the number of output addresses occupied by the matics must be set on a DIL switch on the pneumatic interface. The DIL switch is situated under the transparent cover on the pneumatic interface. Pneumatics of type 32 (MPA) From the technical point of view, the individual MPA matic modules each represent an electric module with digital outputs for controlling the valves fitted. In the case of VMPA1−FB−...−8, 8 digital outputs will always be assigned and in the case of VMPA2−FB−...−4, 4 digital outputs will always be assigned.

3−8

Festo P.BE−CPX−SYS−EN en 0503b

Page 83

3. Installation

3.1.4

Selecting the power unit

Warning · In order to provide the electric supply, use only PELV circuits as per IEC/DIN EN 60204−1 (Protective Extra−Low Voltage, PELV). Take into account also the general requirements for PELV circuits as per IEC/DIN EN 60204−1. · Use only power packs which guarantee reliable electrical isolation of the operating voltage as per IEC/DIN By the use of PELV power units, protection against electric shock (protection against direct and indirect contact) is anteed in accordance with IEC/DIN EN 60204−1 (electrical equipment of machines, general requirements). The current consumption of a CPX terminal depends on the number and type of integrated modules and components. Recommendation: ·

Used closed−loop power units.

·

When selecting the power units, check that they have sufficient output. If required, ascertain here the current requirement according to the following table.

Please note Select a power unit which provides sufficient output for later extensions to the CPX terminal.

Information on the power supply concept of the CPX terminal can be found in section 1.1.3.

Festo P.BE−CPX−SYS−EN en 0503b

3−9

Page 84

3. Installation

Calculation

The following tables show how to calculate the current sumption of the system supply and the additional supplies. The values specified have been rounded up. Please refer to the relevant technical specifications for the current tion of the valves and modules.

System supply type CPX−GE−EV−S or CPX−GE−EV−S−7/8−... Current consumpt. of the operat. voltage supply for the electronics and sensors Current consumption of the field bus node approx. 200 mA

Maximum current consumption of the CPX modules supplied via the system supply (internal electronics) 1)

+ _____ A

Current consumption of the sensors supplied via the system supply manufacturer’s specifications)

+ _____ A

Current consumption of the technology modules supplied 2)

+ _____ A

Sum of the current consumption of the operating voltage

= _____ A

______ A

Current consumption of the the load voltage supply for the valves and outputs Current consumption of all simultaneously activated electric outputs which are supplied via the system supply (internal consumption at logic 1) 3)

_____ x _____A

Load current of simultaneously activated outputs supplied via the system supply.

+ _____ A

Current consumption of all simultaneously energized valve coils

+ _____ A

Current consumption of the technology modules supplied 2)

+ _____ A

Sum of the current consumption of the load voltage

= _____ A

Total current consumption of the system supply

+ _____ A = _____ A

1) See technical specifications of the I/O modules, pneumatic modules and MPA modules 2) Including further modules and components supplied via the technology module 3) Internal consumption at logical 1 see technical specifications for the output module 4) Depends on current consumption of valve type (see technical specifications for the valves)

Table for calculating the current consumption of the system supply (Pin ment, see 3−10

Festo P.BE−CPX−SYS−EN en 0503b