Page 85

3. Installation

Caution The maximum permitted current per pin on the supply is: 16 A. Note that with system supply via pin 3 (0 V), the sum of both currents from pin 1 and pin 2 flows via pin 2. M18 plug: 16A 7/8 plug, 4−pin: 12 A*) 7/8 plug, 5−pin: 12 A*) *) limited by the specifications of the connected plug nector. Please note that with system supply with 4 pin plug via pin 0 V", the sum of both currents of the operating and load voltages flows.

Additional supply for outputs type CPX−GE−EV−Z or CPX−GE−EV−Z−7/8−... (optional) Current consumption of load voltage supply for outputs Current consumption of all simultaneously activated electric outputs which are supplied via the additional supply (internal consumption at logic 1) 1)

_____ x _____A

Load current of simultaneously activated outputs supplied via the additional supply

+ _____ A

Current consumption of the technology modules supplied 2)

+ _____ A

Sum of the current consumption of the load voltage

= _____ A

Total current consumption of the additional supply

+ _____ A = _____ A

1) Internal consumption at logical 1 see technical specifications for the output module 2) Including further modules and components supplied via the technology module

Table for calculating the current consumption of the additional supply for the outputs (Pin assignment, see

Festo P.BE−CPX−SYS−EN en 0503b

3−11

Page 86

3. Installation

Additional supply for valves of type CPX−GE−EV−V or CPX−GE−EV−V−7/8−4POL (optional) Current consumption of load voltage supply for valves Current consumption of all simultaneously energised valve coils

A

Sum of the current consumption of the load voltage

= _____ A

Total current consumption of the additional supply

+ ______ A = ______ A

1) Depends on current consumption of valve type (see technical specifications for the valves)

Table for calculating the current consumption of the additional supply (Pin assignment, see Information on the power supply concept of the CPX terminal can be found in section 1.1.3.

3−12

Festo P.BE−CPX−SYS−EN en 0503b

Page 87

3. Installation

3.1.5

Connecting the operating voltage

Please note Check within the framework of your EMERGENCY STOP circuit, to ascertain the measures necessary for putting your machine/system into a safe state in the event of an EMERGENCY STOP (e.g. switching off the operating voltage for the valves and output modules, switching off the pressed air).

Please note With CPX terminals with Midi/Maxi pneumatics, or CPX−CP interface: · Note that the lower tolerance range of the pneumatics must be observed when the operating and load voltage supplies are provided by a power unit. Tolerance ranges: Midi/Maxi pneumatics: ± 10 % CPA pneumatics or CPX−CP interface: + 10 /− 15 % MPA pneumatics: ± 25 % Check the load voltage of the outputs while your system is operating. Make sure that the load voltage of the outputs lies within the permitted tolerance even during full−load ation. Recommendation: Use a closed−loop power unit.

Festo P.BE−CPX−SYS−EN en 0503b

3−13

Page 88

3. Installation

Caution Short circuits can cause damage. Protect the system supply and the additional supplies each with an external fuse: M18 plug, 4−pin: 16 A 7/8 plug, 5−pin: 12 A*) 7/8 plug, 5−pin: 12 A*) *) limited by the specifications of the connected plug connector.

Manifold base

Description

System supply type CPX−GE−EV−S...

The following components are supplied with + 24 V DC: The operating voltage for the internal electronics of the CPX terminal and the sensors connected to the input modules V DC, tolerance + 25/− 25 %). Load voltage for the outputs of the output modules and, if applicable, valve solenoid coils (+ 24 V DC) Tolerance: without pneumatics: ± 25 %, with Midi/Maxi pneumatics: ± 10 %, with CPA pneumatics or CPX−CP interface: + 10/− 15 %. with MPA pneumatics: ± 25 %.

Additional supply of the electric outputs type CPX−GE−EV−Z...

The following components are supplied with + 24 V DC: Load voltage for the integrated output module and, if applicable, for the subsequent output modules on the right (+ 24 V DC, tolerance + 25/− 25 %).

Additional supply of the valves type CPX−GE−EV−V... 1)

The following are supplied with + 24 V DC: The load voltage for the valve solenoid coils (+ 24 V DC). Tolerance: with Midi/Maxi pneumatics: ± 10 %, with CPA pneumatics or CPX−CP interface: + 10/− 15 %. with MPA pneumatics:1) ± 25 %.

1) Additional supply type CPX−GE−EV−V is not permitted with MPA pneumatic modules with MPA electronic modules type VMPA...−FB−EMS−... (see the manual for the CPX I/O modules).

3−14

Festo P.BE−CPX−SYS−EN en 0503b

Page 89

3. Installation

Plug

Pin assignment of manifold base with

1 2 4 M18

System supply type CPX−GE−EV−S...

Additional supply type CPX−GE−EV−Z...

Valve supply type CPX−GE−EV−V...

1: 24 VEL/SEN 2: 24 VVAL/24 VOUT 3: 0 VEL/SEN / 0 VVAL/0 VOUT 4: Earth/ground connection

1: Not connected 2: 24 VOUT 3: 0 VOUT

1: Not connected 2: 24 VVAL 3: 0 VVAL

4: Earth/ground connection

4: Earth/ground connection

1: 24 VVAL / 24 VOUT 2: 24 VEL/SEN 3: Earth/ground connection 4: 0 VEL/SEN / 0 VVAL / 0 VOUT (leading)

1: 24 VOUT 2: not connected 3: Earth/ground connection 4: 0 VOUT (leading)

1: 24 VVAL 2: not connected 3: Earth/ground connection 4: 0 VVAL (leading)

1: 0 VVAL / 0 VOUT 2: 0 VEL/SEN 3: Earth/ground connection (leading) 4: 24 VEL/SEN 5: 24 VVAL / 24 VOUT

1: 0 VOUT 2: Not connected 3: Earth/ground connection (leading) 4: Not connected 5: 24 VOUT

3 3 4

1 7/8"−4POL 2

2 1 3 4 7/8"−5POL 5 VEL/SEN VOUT VVAL

Operating voltage for electronics/sensors Load voltage for outputs Load voltage for valves

Pin assignment system supply, additional supply and valve supply

Festo P.BE−CPX−SYS−EN en 0503b

3−15

Page 90

3. Installation

Potential equalisation The CPX terminal has two earthing connections for potential equalisation:

Pin 4 (M18 plug) or pin 3 (7/8" plug) of the power supply connection of the system supply (incoming)

Pin 4 (M18 plug) or pin 3 (7/8" plug) of the load voltage connection of the additional supply (incoming)

Earth connection on the left−hand end plate (see

Please note · Always connect the earth potential to pin 4 (M18 plug) or pin 3 (7/8" plug) of the load and operating voltage connections. · Connect the earth connection of the left−hand end plate to the earth potential with low impedance (short cable with large cross−sectional area). · With low−impedance connections you can ensure that the earth connection at the left−hand end plate and the earth connection at pin 4 (M18 plug) or pin 3 (7/8" plug) have the same potential and that there are no equalising currents. In this way you can avoid faults due to electromagnetic influences and ensure electromagnetic compatibility in accordance with EMC guidelines.

3−16

Festo P.BE−CPX−SYS−EN en 0503b

Page 91

3. Installation

Connection example 1

The diagram below shows as an example the connection of a common supply for pins 1 and 2 (M18 plug). Please note here that:

The lower tolerance 24 V DC + 10/− 15 % must be observed.

Both connections for potential equalisation are connected and that equalising currents must be prevented.

The load voltage at pin 2 of the M18 plug (valves and puts) can be switched off separately.

External vibrations depending on application; maximum value in sum for both fuses 16 A.

1 Potential 4DO equalisation

4DO

2 External fuses 3 The load voltage of the valves and outputs can be switched off separately

M18 3 1 2 4

ÖÖ Ö ÖÖ Ö ÖÖ Ö ÖÖ Ö

4 Earth connection pin 4 is designed for 16 A

AC

5 Connection for system supply

PE

1

DC

PE

2

3

1

4

5

Example Connecting a common power supply and the potential equalisation (system supply with M18 plug)

Festo P.BE−CPX−SYS−EN en 0503b

3−17

Page 92

3. Installation

Connection example 2

The following diagram shows the connection with system supply and an additional supply each for electric outputs and valves.

1

2

8DI

M18 1

3

4DO

4DO

4

4DO

M18

M18 2 3 4

ÖÖ ÖÖ ÖÖ ÖÖ ÖÖ ÖÖ ÖÖ

4DO

1 2 3 4

1 2 3 4

24V

AC DC

PE

0V

PE

1

1

1

1 Potential equalisation 2 Manifold base with system supply type CPX−GE−EV−S 3 Manifold base with additional supply for outputs of type CPX−GE−EV−Z 4 Manifold base with additional supply for outputs of type CPX−GE−EV−V Example Additional load supplies with a common power supply (all plies with M18 plugs)

3−18

Festo P.BE−CPX−SYS−EN en 0503b

Page 93

3. Installation

Connection example 3

1

The following diagram shows as an example the connection with electrical isolation of the power supply. Manifold sub− bases with 5−pin 7/8" plugs are used to do this.

2

3 8DI−D

4DO

4 8DO

8DO MPA

8A

7/8" 1 2 3 4 5

8A

7/8" 1 2 3 4 5

24V AC

DC

0V

PE

24V AC

DC

0V

PE

1 Potential equalisation 2 Manifold base with system supply type CPX−GE−EV−S−7/8−5POL 3 Manifold base with additional supply for outputs type CPX−GE−EV−Z−7/8−5POL 4 MPA pneumatic modules with electrical isolation (type VMPA...−FB−EMG−...) Example − Electrical isolation of the power supply with separate power unit by a manifold sub−base with 5−pin 7/8" plugs (basic circuit diagram)

Festo P.BE−CPX−SYS−EN en 0503b

3−19

Page 94

3. Installation

3.1.6

Connecting the field bus

Please note A description of the field bus connection of your node can be found in the manual for the appropriate CPX field bus node.

3−20

Festo P.BE−CPX−SYS−EN en 0503b