Page 37
1. Summary of components
Manifold base
Description Type CPX−GE−EV Manifold base without supply
Manifold bases of the CPX valve terminal − part 2
Manifold sub−base with system supply type CPX−GE−EV−S...
The operating and load voltages for the CPX terminal are supplied via this manifold sub−base. The voltages are plied via an M18 or 7/8" plug and can be used for further electric modules and for the valves. If sub−bases with additional supply are not required, the manifold sub−base with the system supply can be fitted in any desired position. If sub−bases with additional supply are required, these must always be placed to the right of the system supply (see also
Manifold sub−base with additional supply for electric outputs type CPX−GE−EV−Z...
The additional load voltage for the electric outputs is plied via this manifold sub−base. The load voltage for the output modules is also supplied via an M18 or 7/8" plug and can be switched off separately. This manifold sub−base must always be placed to the right of the system supply. The use of a manifold sub−base with additional supply for electric outputs causes the following (see also
Festo P.BE−CPX−SYS−EN en 0503b
The load voltage for electric output modules will be interrupted to the previous module on the left.
The load voltage supplied will be available to the grated module and, where applicable, to the following modules on the right.
1−21
Page 38
1. Summary of components
Manifold base with additional supply for valves type CPX−GE−EV−V...
The operating and load voltage supplies for the valves will be transmitted further.
Several additional supplies for electric outputs in a CPX terminal are possible.
This manifold base enables the electrically isolated supply of load voltage for the valves. The load voltage for the valves, which is also supplied via an M18 or 7/8" plug, can be switched off separately. This manifold base must also always be placed to the right of a system supply. The use of a manifold base with additional supply for valves causes the following (see also
The load voltage for the valves will be interrupted at the previous module on the left.
The load voltage supplied is available for the following modules:
subsequent pneumatic modules/valves to the right
CP modules which are connected to the fitted CPX−CP interface and to those CPX−CP interfaces subsequently fitted to the right
The operating and load voltage supplies for the electric outputs will be transmitted further.
Note the following warning if you use MPA pneumatics:
Caution Damage to components and functional damage! It is not permitted to supply voltage to MPA pneumatic modules with electronic modules without electrical tion via a manifold base for valve supply type CPX−GE−EV−V. · If your MPA pneumatics are fitted with electronic ules of type VMPA1−FB−EMS−8 or VMPA2−FB−EMS−8, you must actuate the MPA pneumatics only by means of the system supply module type CPX−GE−EV−S. 1−22
Festo P.BE−CPX−SYS−EN en 0503b
Page 39
1. Summary of components
Please note that MPA electronic modules may only be fed through the following supply. MPA electronic module
Permitted supply modules
VMPA...−FB−EMS−8 (without electrical isolation)
System supply (CPX−GE−EV−S)
VMPA...−FB−EMS−8 (with electrical isolation)
System supply (CPX−GE−EV−S) Valve supply (CPX−GE−EV−V) 1)
1) If a 4−pin system supply is used, the electrical isolation will no longer be effective.
Permitted supply modules for MPA electronic modules On electronic modules with electrical isolation type VMPA...−FB−EMG−..., Vel/sen and Vval are completely electrically isolated. In conjunction with a manifold sub−base with valve supply type CPX−GE−EV−V or a 5−pin connector plug (7/8"), it is therefore possible to switch off the valve supply voltage at all poles. Further information on MPA electronic modules can be found in the manual for the CPX I/O modules.
Manifold sub−base type CPX−GE−EV
Festo P.BE−CPX−SYS−EN en 0503b
This sub−base serves for the electrical linking of modules which do not require a separate load supply.
1−23
Page 40
1. Summary of components
The operating voltage supplied (internal electronics/inputs) as well as the load voltage (valves/outputs) are transmitted further in the manifold sub−bases via so−called contact rails. The following diagram provides an overview (M18 plug): CPX−GE−EV−S
CPX−GE−EV
CPX−GE−EV−Z
0 Vval 24 Vval
0 Vout 24 Vout
CPX−GE−EV−V 0 Vval 24 Vval
2
0 Vout 24 Vout
3
0 Vel/sen 24 Vel/sen
6
1
FE
4 5 M18 1 2 3 4 FE
1 Load voltage for valves (24 Vval and 0 Vval)
2 Load voltage for digital outputs (24 Vout and 0 Vout)
3 Operating voltage for electronics and
M18 1 2 3 4 n.c. FE
M18 1 2 3 4 n.c. FE
4 Functional earth (FE) 5 Further rails for internal functions 6 Connected to FE connection on sensors (24 Vel/sen and 0 Vel/sen) Basic representation of the power supply concept for manifold sub−bases with M18 plugs.
1−24
Festo P.BE−CPX−SYS−EN en 0503b
Page 41
1. Summary of components
Manifold sub−bases with 7/8" plugs are available with either 4 or 5 pins. The 5−pin plug facilitates electrical isolation of the load voltage supply for outputs/valves for the operating tage of electronics/sensors. The following diagram gives an overview. CPX−GE−EV−S− 7/8−5POL
CPX−GE−EV
CPX−GE−EV−Z− 7/8−5POL
1
0 VVAL 24 VVAL 0 VOUT 24 VOUT
0 VOUT 24 VOUT
3
0 VEL/SEN 24 VEL/SEN
6
2
FE
4 5 7/8"−5POL
0 VVAL/OUT 0 VEL/SEN FE 24 VEL/SEN 24 VVAL/OUT
1 2 3 4 5
1 Load voltage for valves
1
2 3 4 5
0 VOUT n.c. FE n.c. 24 VOUT
7/8"−5POL
4 Functional earth (FE)
(24 Vval and 0 Vval)
2 Load voltage for digital outputs (24 Vout and 0 Vout)
3 Operating voltage for electronics and
5 Further rails for internal functions 6 Connected to FE connection on sensors (24 Vel/sen and 0 Vel/sen) Basic representation of the power supply concept for manifold sub−bases with 5−pin 7/8" plugs. You can find the pin assignment for connections to the fold sub−bases in
Festo P.BE−CPX−SYS−EN en 0503b
1−25
Page 42
1. Summary of components
Special features concerning the use of the The CPX−CP interface connects the internal current rails and 0 Vval of the CPX valve terminal. This means that the electrical isolation of the operating voltage for the tronics/sensors (Vel/sen) and the load supply for the valves (Vval) will no longer be effective until the next additional ply for valves following the CPX interface. Further information on the voltage supply for the in conjunction with the CPX−CP interface can be found in the manual for the CPX−CP interface in the chapter Installation" section Voltage supply concept forming voltage zones".
1−26
Festo P.BE−CPX−SYS−EN en 0503b
Page 43
1. Summary of components
1.2
Commissioning, diagnosis and operating functions The system reaction of the CPX terminal can usually be adapted to the relevant application. For this purpose, the provides extensive functions for commissioning, diagnosis and operation.
Commissioning and operating functions The reaction of the CPX terminal can be adapted to individual requirements by parameterisation. By means of access to the internal parameters, e.g. the following reactions of the CPX terminal can be influenced:
the reaction of the outputs and valves to field bus communication faults (fail−safe settings)
the reaction to fault elimination the debouncing times for digital input signals the signal extension for digital input signals the force settings (force signal status)
the working method of the diagnostic memory.
The CPX terminal is supplied from the factory with preset parameters.
Caution A different parameterisation will result in a different tion. Check especially when replacing CPX terminals to see which settings are necessary and make sure that these settings, where applicable, are carried out (e.g. in the start−up phase by the higher−order PLC/IPC).
Festo P.BE−CPX−SYS−EN en 0503b
1−27
Page 44
1. Summary of components
Information on the module−specific parameters, which are supported by the module used, can be found in the manual for the relevant module. Basic information on the different parameters can be found in Appendix C in this manual.
Diagnostic functions Extensive diagnostic information can be accessed depending on the field bus used. Status bits
Common diagnostic messages (global error messages) are displayed by means of 8 internal inputs (8 status bits).
I/O diagnostic interface
With field buses which do not possess extensive diagnostic functions, the diagnostic information of the CPX terminals is available via the so−called I/O diagnostic interface. The I/O diagnostic interface enables bus−independent access to nostic information, data and parameters via internal digital I/Os (16 inputs and 16 outputs).
Diagnostic memory
Faults which occur during operation are entered in a tic memory. The first 40 or the last 40 entries are saved, as well as the relevant time measured from the moment the power supply was switched on.
Field bus specific diagnostic functions
Special diagnostic functions or communication services are available, depending on the field bus used. For example communication services on:
1−28 the DPVI (PROFIBUS)
the PCP channel (Interbus)
SDO access (CANopen)
etc.
Festo P.BE−CPX−SYS−EN en 0503b