Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 25

Modular electrical terminal CPX, pages 1 to 10

Pages 1 to 10 of 246

The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Festo CPX-EPL-EV

Page 1 read from a scan by OCR; it may hold reading errors

Modular electrical terminal CPX

FESTO

Page 2

Terminal CPX Key features

Key features Installation concept

Electrical components

Assembly

Operation

Choice of several valve terminal types for different applications: – MPA-S – MPA-L Economical from the smallest configuration up to the maximum number of modules Up to 9 electrical input/output modules plus bus nodes and pneumatic interface/electronic modules for valves Extensive range of functions and connection options for the electrical modules Choice of connection technology for technically and economically optimised connections Can be used as a dedicated remote I/O module

High operating voltage tolerance (±25%) Choice of M18, 7/8” or AIDA pushpull connection for power supply Open to all fieldbus protocols and Ethernet Optional function and technology modules for preprocessing IT services and TCP/IP such as remote maintenance, remote diag­ nostics, web server, text message and e-mail alert Digital inputs and outputs, 4-/8-/16-way, optionally available with individual channel diagnostics Analogue inputs and outputs, 2-/4-way, optionally with HART protocol Pressure inputs Temperature inputs Controllers for pneumatic and electrical axes IP65 and IP67 or IP20

Wall or H-rail mounting, also on mobile systems Conversions/extensions are possible at any time, individual linking with CPX metal design Modular system offering a range of configuration options Fully assembled and tested unit Lower selection, ordering, assembly and commissioning costs thanks to the central CPX terminal Choice of pneumatic components for optimised control loop system design Decentralised, subordinate CPI installation system improves cycle times by up to 30% Safe and convenient earthing thanks to earthing plate

Fast troubleshooting thanks to an extensive selection of LEDs (some of which are multi-coloured) on the bus node and on all I/O modules Supports module and channeloriented diagnostics On-the-spot diagnostics in plain text via handheld device Fieldbus/Ethernet remote diagnostics Innovative diagnostic support with integrated web server/web monitor or maintenance tool with USB adapter for PC Optimised commissioning thanks to parameterisable functions Reliability of service with connec­ tion blocks and modules that are quick to replace without changing the wiring

2

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 3

Terminal CPX Key features Pneumatic variants of the CPX terminal The electrical CPX terminal is a modular peripheral system for valve terminals.

The system is specifically designed so that the valve terminal can be adapted to suit different applications.

The modular system design lets you configure the number of valves, inputs and additional outputs to suit the application.

With valve terminal – decentralised

With valve terminal MPA-S – centralised

With valve terminal VTSA – centralised

In metal design with valve terminal VTSA – centralised

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

3

Page 4

Terminal CPX Key features Variants of the CPX terminal controller (with bus node, without preprocessing) Bus node Different bus nodes are used to integrate the terminal in the control systems of various manufacturers. The CPX terminal can therefore be operated on over 90% of the most commonly used fieldbus systems: PROFIBUS DP PROFINET INTERBUS

DeviceNet CANopen CC-Link Integration in universal networks based on Ethernet opens up new possibilities. Faster data trans­ mission, real-time capability and above all additional IT services such

Bus node as file transfer, web server, web moni­ tor as integrated website in the CPX terminal, text message/e-mail alerts, etc. open up a wide range of synergies. These include standardised and universal communication technology across all areas, including operating level, management level and field level in the production environment, with protection to IP65, IP67. The following protocols are supported: EtherNet/IP Modbus/TCP PROFINET POWERLINK EtherCAT Sercos III

Industrial Ethernet bus node PLC

PLC

Industrial Ethernet

Fieldbus

IT services: Web E-mail File transfer

Communication with higher-order controller via fieldbus No preprocessing

Fieldbus protocol dependent on CPX bus node used Up to 90 I/Os, depending on the bus node used

Connection to a higher-order controller directly via EtherNet/IP, Modbus/TCP, POWERLINK, EtherCAT or PROFINET

No preprocessing Monitoring via Ethernet and web applications Up to 300 I/Os

-H- Note Every electrical connection can be combined with an appropriate number of I/O modules and/or pneumatic components, depending on its address capacity.

4

Likewise, every pneumatic variant of the CPX terminal can be operated with every electrical connection variant.

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 5

Terminal CPX Key features Variants of the CPX terminal controller (with preprocessing in the control block) Control block The optional Front End Controllers CPX-CEC enable access via Ether­ net, in parallel with a bus node, as well as autonomous preprocessing. Access via Modbus/TCP and EasyIP is also possible.

With control block in stand-alone mode

Commissioning, programming and diagnostics using the Festo software tool FST 4.1 with hardware configurator. With control block in Festo EasyIP mode

CoDeSys/FST

Industrial Ethernet IT services: Web E-mail File transfer

Decentralised controller with direct machine mounting Interaction options via CPX-MMI or Front End Display Downloading of programs via Ethernet (or via the programming interface) Supports full expansion of all CPX peripherals More than 300 I/Os

2018/04 – Subject to change

Beneficial application areas: Stand-alone individual workstations Interlinked, stand-alone sub-systems Automation using IT technology

Fast preprocessing of the CPX peripherals in the control block Exchange of any data between the control blocks via EasyIP Remote diagnostics

è Internet: www.festo.com/catalogue/...

No higher-order controller is required More than 300 I/Os per CPX control block

5

Page 6

Terminal CPX Key features Variants of the CPX terminal controller (with preprocessing in the control block) With control block as remote controller on Ethernet Remote controller on Ethernet as the preprocessing unit for decentralised, stand-alone subsystems using IT technology.

With control block as remote controller on the fieldbus Fieldbus remote controller (combina­ tion with bus nodes for INTERBUS, PROFIBUS DP, PROFINET, CANopen, DeviceNet, CC-Link, POWERLINK,

Sercos III or EtherCAT) as the prepro­ cessing unit for decentralised, standalone subsystems.

PLC

PLC

Fieldbus Industrial Ethernet

Industrial Ethernet

IT services: Web E-mail File transfer

IT services: Web E-mail File transfer

Connection to a higher-order controller via Ethernet, no further bus node is required Monitoring via Ethernet and web applications

6

Preprocessing of the CPX peripherals by CPX control block More than 300 I/Os

è Internet: www.festo.com/catalogue/...

Fast preprocessing of the CPX peripherals in the control block Communication with higher-order controller via fieldbus Optional additional monitoring via Ethernet and web applications

Downloading of programs via programming interface More than 300 I/Os, bus node is only used for communication with the higher-order PLC Two bus nodes for redundant communication configuration

Subject to change – 2018/04

Page 7

Terminal CPX Key features Variants of the CPX terminal controller (with preprocessing in the control block) With control block as CANopen fieldbus master PLC

Industrial Ethernet

Properties: Connection to a higher-order controller via Ethernet, no further bus node is required Monitoring via Ethernet Preprocessing of the CPX peripherals by CPX control block More than 300 I/Os Up to 128 stations with repeater technology on CANopen

Operating modes: Remote controller on Ethernet Control block in Festo EasyIP mode

IT services: File transfer

CPX with CEC-C1 as CANopen master

CANopen

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

7

Page 8

Terminal CPX Key features Connection of inputs and outputs to the CPX terminal Digital and analogue CPX I/O modules

Electrical connection The connection technology for sen­ sors and additional actuators offers a wide range of digital and analogue input and output modules and is freely selectable – as appropriate to your standard or application. Plastic or metal connection blocks can be combined as required: Metal design – M12-5POL

Plastic design: – M12-5POL – M12-5POL with quick lock and metal thread – M12-8POL – M8-3POL – M8-4POL – Sub-D – Harax® – CageClamp® (with cover also to IP65, IP67) – Screw terminal / spring-loaded terminal

Several CP interface modules can be combined in one CPX terminal (depending on the controller used).

Combination of centralised CPX I/O modules and decentrally mounted I/O modules of the CPI installation system.

With CPX-CP interface

Up to 4 strings per CP interface possible Up to 4 subordinate CP modules can be combined in one string

Up to 32 I/Os can be connected per string Modules with M8, M12 and terminal connection

Combined centralised and decentralised electrical connection (valve terminal with CP interface/output module) Scalable to different requirements within a system One control interface in the system, reduces installation complexity with closely and widely spaced actuators Enables an optimum electrical and pneumatic control chain

8

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 9

-V- New CPX-CTEL-2 Terminal CPX Key features Connection of inputs and outputs to the CPX terminal with CPX-CTEL interface Up to 4 devices with individual electronic fuse protection per CPX­CTEL master Max. 64 inputs/64 outputs per I-Port interface The maximum length of a string is 20 m Input modules with 16 digital inputs (3-pin M8 and 5-pin M12 connection technology) Valve terminals with I-Port interface (up to 48 solenoid coils, different valve functions)

Several CPX­CTEL masters can be combined in one CPX terminal (depending on the controller used). Combination of central CPX I/O mod­ ules and decentrally mounted I/O modules with I-Port interface.

Up to 2 individual electronically protected IO-Link devices per CPX-CTEL-2 interface Max. 16-byte inputs/ 16-byte outputs per IO-Link device The maximum length of a string is 20 m

Several CPX-CTEL-2 interface modules can be combined on one CPX terminal (depending on the controller used). Combination of central CPX I/O modules and decentrally mounted I/O modules with IO-Link interface.

With CPX-CTEL-2 interface

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

9

Page 10

Terminal CPX Key features Connection of inputs and outputs to the CPX terminal Electrical drives with CPX-CM-HPP axis interface

Max. 4 individual electric axes, per CPX-CM-HPP No programming required

Standardised communication with the drives via the Festo Handling and Positioning Profile (FHPP)

The control component is indepen­ dent of the bus node used

Quick configuration and diagnos­ tics via the operator unit CPX-MMI

Pneumatic drives with CPX-CMAX/CMPX

CPX-CMAX

CPX-CMPX

Position and force control, directly actuated or selected from one of 64 configurable positioning profiles. Configurable record continuation enables simple functional sequences to be realised. The auto-identification function identifies each station with its device data on the controller.

Actuation of a brake or clamping unit via the proportional directional control valve VPWP. Up to 7 modules (max. 7 axes) can be operated in parallel and independently of each other. Commissioning via the Festo configuration software FCT or via fieldbus.

10

è Internet: www.festo.com/catalogue/...

Fast travel between the mechanical end stops of the cylinder, stopping gently and without impact in the end position. Fast commissioning via control panel, fieldbus or handheld unit. Improved downtime control. Actuation of a brake or clamping unit via the proportional directional control valve VPWP.

Max. 9 end-position controllers can be actuated depending on the fieldbus. All system data can be read and written via the fieldbus, including the mid positions, for example.

Subject to change – 2018/04