The text of a spec sheet · part 19 of 25
Modular electrical terminal CPX, pages 181 to 190
Pages 181 to 190 of 246
The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-EPL-EV
Page 181
Terminal CPX Technical data – Counter module, digital Function The counter module has two channels. Depending on the parameterisation, these can independently be used as counter inputs or as incremental value encoder inputs or SSI. The counter module additionally has one output per channel. The outputs can either be controlled by a counter channel or an incremental value en coder channel, i.e. through an event such as "Comparative value reached". Alternatively, outputs can also be controlled via process data.
Application Continuous counting One-off counting to count limit One-off counting to count limit, return to load value Periodic counting Measurement of frequencies Measurement of rotational speeds Measurement of duty cycle Measurement of position Measurement of speed Measurement with pulse generators Measurement with pulse generators and direction encoders Measurement with incremental encoders Measurement with SSI absolute encoders
Description Applications Recording travel and speed of a conveyor Position and speed synchronisation of conveyors and pick & place applications Counting goods e.g. in packaging installations
Systems for filling by weight and volume Monitoring motor speeds Measuring equipment for determining the position of axis systems (linear, rotational)
Control of fast-switching valves Control of the opening time of a valve Activation of semiconductor relays
Temperature monitoring and rotational speed control for drives Change of direction in fast drives Control of motors with pulse-width modulation (PWM)
24 V incremental encoder, singleended, with two 90° phase offset tracks
24 V pulse generator with or without direction level 24 V direct current motors
Absolute encoder with SSI interface (13 bits to 25 bits)
Supported devices 5 V incremental encoder, singleended or differential, with two 90° phase offset tracks
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
181
Page 182
Terminal CPX Technical data – Counter module, digital General technical data Type Number
CPX-2ZE2DA Inputs Outputs Inputs Outputs
Max. power supply per module Max. power supply per channel Max. cable length Fuse protection (short circuit) Intrinsic current consumption at nominal operating voltage Operating voltage Nominal value Permissible range Electrical isolation, inputs Channel – channel Channel – internal bus Electrical isolation, outputs Channel – channel Channel – internal bus Characteristic curve Inputs Outputs Switching level Signal 0 Signal 1 Input debounce time Switching logic
Inputs Outputs
LED displays
Group diagnostics Channel diagnostics Channel status Module diagnostics
[mm] [mm]
2 2 2 10 5 (adjustable, 20 W lamp load) 30 Internal electronic fuse per channel Typically 35 24 18 … 30 No No No Yes, using an intermediate supply To IEC 1131-2, Type 02 IEC 1131-T2 5 11 0.1 (0.2 μs, 0.4 μs, 0.8 μs, 1 μs, 2 μs, 4 μs, 8 μs, 10 μs, 50 μs, 100 μs, 500 μs, 1 ms, 3 ms, 10 ms, 20 ms parameterisable) Positive logic (PNP) Negative logic (NPN) Positive logic (PNP) Push-pull driver 1 2 10 2 Operating mode-dependent diagnostics Switch-on/off delay Frequency output Speed measurement Pulse output Pulse train Rotational speed measurement Frequency measurement Duty cycle measurement Engine operating mode Determination of position Pulse width modulation One-off counting Continuous counting Periodic counting IP65, IP67 –5 … +50 –20 … +70 UL - Recognized (OL) Plastic RoHS-compliant 50 50 x 107 x 50
[g]
130
[A] [A] [A] [m] [mA] [V DC] [V DC]
[V DC] [V DC] [μs]
Diagnostics Parameterisation
Protection class to EN 60529 Temperature range
Operation Storage/transport
Certification Housing material information Note on materials Grid dimension Dimensions (incl. interlinking block and connection block) WxLxH Product weight
182
[°C] [°C]
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 183
Terminal CPX Technical data – Counter module, digital Connection and display components CPX-2ZE2DA 3
1
2
Pin allocation Inputs/outputs
1 Status LEDs (green) For allocation to inputs è Pin allocation for module 2 Status LEDs (yellow, red) For allocation to outputs è Pin allocation for module 3 Error LED (red) (module error)
CPX-2ZE2DA Channel 0 X1.0: Input X1.1: Input X1.2: Input X1.3: Input
Channel 1 X5.0: Input X5.1: Input X5.2: Input X5.3: Input
X2.0: X2.1: X2.2: X2.3:
Input Input 5 V DC 0V
X6.0: X6.1: X6.2: X6.3:
Input Input 5 V DC 0V
X3.0: X3.1: X3.2: X3.3:
24 V DC 0V 24 V DC for digital input DI Digital input DI
X7.0: X7.1: X7.2: X7.3:
24 V DC 0V 24 V DC for digital input DI Digital input DI
X4.0: X4.1: X4.2: X4.3:
0 V for digital input DI Digital output DO Reference potential for DO FE
X8.0: X8.1: X8.2: X8.3:
0 V for digital input DI Digital output DO Reference potential for DO FE
-H- Note The allocation and designation of inputs differs fundamentally de pending on which type of encoder is connected. Appropriate allocation diagrams can be found in the user documentation for the counter module.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
183
Page 184
Terminal CPX Accessories – Counter module, digital Ordering data Description
Part No.
Type
Counter module, digital 2 digital inputs, 2 digital outputs
576046
CPX-2ZE2DA
Cover for CPX-2ZE2DA (IP65, IP67) – 8 cable through-feeds M9 – 1 cable through-feed for multi-pin plug
538219
AK-8KL
Fittings kit
538220
VG-K-M9
8035733 8035734 8035735 8035736 8035737 8035738
P.BE-CPX-2ZE2DA-DE P.BE-CPX-2ZE2DA-EN P.BE-CPX-2ZE2DA-ES P.BE-CPX-2ZE2DA-FR P.BE-CPX-2ZE2DA-IT P.BE-CPX-2ZE2DA-ZH
Cover
Manual Manual counter module CPX-2ZE2DA
184
è Internet: www.festo.com/catalogue/...
German English Spanish French Italian Chinese
Subject to change – 2018/04
Page 185
-V- New Terminal CPX Technical data HART input/output module Function The HART input/output module allows the connection of up to 4 sensors or actuators. The corresponding communication channel is made available for sensors or actuators that communicate using the HART protocol. With the HART protocol, a conven tional analogue 4 … 20 mA current signal is modulated by a second frequency-modulated signal. Each of the 4 connections of the module can be configured as inputs or outputs.
Area of application Multi I/O module for 24 V DC supply voltage Supports connection blocks with M12 and terminal connection Module features can be parameterised The module receives the voltage supply for the electronics, outputs and the sensors from the interlinking block Module protection and diagnostics through integrated electronic fuse protection
General technical data Type code Protocol Number of selectable analogue inputs/outputs Sensor type Operating voltage Nominal value Permissible range Power failure buffering Intrinsic current consumption at nominal operating voltage Maximum short circuit current Maximum open circuit voltage Minimum available sensor voltage Fuse protection (short circuit) Reverse polarity protection Electrical isolation Channel – channel Channel – internal bus Signal range Data format Maximum load Maximum input resistance Maximum cable length Basic error limit at 25 °C Operating error limit related to the ambient temperature range Repetition accuracy LED indicators Group diagnostics Channel diagnostics Channel status Control components
2018/04 – Subject to change
CPX-4AE-4AA-H
[V DC] [V DC] [ms] [mA] [mA] [V]
[Ω] [Ω] [m] [%] [%]
HART 4 0 … 20 mA 4 … 20 mA 24 18 … 30 10 Typically 170 22 28.8 20.7 V DC at 20 mA Internal electronic fuse per channel For all electrical connections No Yes 0 … 20 mA 4 … 20 mA 15 bits + prefix Scalable to 15 bits 750 300 500 ±0.1 ±0.3 0.05% at 20 ºC 1 4 4 DIL switch
è Internet: www.festo.com/catalogue/...
4 … 20 mA with HART
4 … 20 mA with HART
185
Page 186
-V- New Terminal CPX Technical data – HART input/output module General technical data Wire break per channel Limit violation per channel Short circuit/overload per channel Parameterisation error Overflow/underflow Limit violation to NE43 per channel Data format Failsafe per channel Forcing per channel Limit monitoring per channel Idle mode per channel Measured value smoothing Signal range per channel Monitoring of overflow/underflow Monitoring to NE43, inputs Behaviour after short circuit/overload Monitoring wire break per channel Number of HART repetitions Hysteresis for limit values HART variables (4 pieces) Depending on connection block
Diagnostics
Parameterisation
Degree of protection to EN 60529 Technical data – Mechanical Type of mounting Product weight Grid dimension Dimensions (incl. interlinking block and connection block) WxLxH
[g] [mm] [mm]
On interlinking block 77.4 50 50 x 107 x 70
Materials Housing Note on materials
PA reinforced, PC RoHS-compliant
Operating and environmental conditions Ambient temperature Storage temperature Relative humidity Corrosion resistance class CRC1) CE marking (see declaration of conformity)3) 1)
2) 3)
[°C] [°C] [%]
–5 … +50 –20 … +70 95, non-condensing 1 (when installed) To EU EMC Directive2)
Corrosion resistance class CRC 1 to Festo standard FN 940070 Low corrosion stress. For dry indoor applications or transport and storage protection. Also applies to parts behind covers, in the non-visible interior area, and parts which are covered in the application (e.g. drive trunnions). For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com/sp è Certificates. If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary. Additional information www.festo.com/sp è Certificates.
Safety data Shock resistance Vibration resistance
186
Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 187
-V- New Terminal CPX Technical data – HART input/output module Connection and display components CPX-4EA-4AA-H 3
1
2
1 Status LEDs: – Inputs (green) – Outputs (yellow) è Pin allocation for module 2 Error LEDs (red) Allocation to inputs/outputs è Pin allocation for module
Combinations of bus nodes/control blocks with HART input/output module Bus node/control block Part No. Protocol CPX-FB13 CPX-FB33 CPX-M-FB34 CPX-M-FB35
3 Error LED (red) (module error)
HART input/output module CPX-4EA-4AA-H n n n n
PROFIBUS PROFINET RT, M12 PROFINET RT, RJ45 PROFINET RT, SCRJ
195740 548755 548751 548749
-H- Note The HART input/output module CPX-4EA-4AA-H can only be connected as of software release 33 or 34 (in the case of CPX-FB13). Combinations of connection blocks with HART input/output module Connection blocks Part No. CPX-P-AB-4XM12-4POL CPX-P-AB-2XKL-8POL
2018/04 – Subject to change n n
565706 565704
Combinations of connection blocks with interlinking block Connection blocks Part No. CPX-P-AB-4XM12-4POL CPX-P-AB-2XKL-8POL
HART input/output module CPX-4EA-4AA-H
565706 565704
Plastic interlinking block CPX-GE… – n
è Internet: www.festo.com/catalogue/...
Metal interlinking block CPX-M-GE… n n
187
Page 188
-V- New Terminal CPX Technical data – HART input/output module Pin allocation Connection block inputs/outputs
CPX-4AE-4AA-H Inputs
Outputs
CPX-P-AB-4XM12-4POL X1.1: X1.2: X1.3: X1.4:
24 VSEN x 0V Input x 0V
X3.1: X3.2: X3.3: X3.4:
24 VSEN x+2 0V Input x+2 0V
X1.1: X1.2: X1.3: X1.4:
Output I0+ 0V – 0V
X3.1: X3.2: X3.3: X3.4:
Output I2+ 0V – 0V
X2.1: X2.2: X2.3: X2.4:
24 VSEN x+1 0V Input x+1 0V
X4.1: X4.2: X4.3: X4.4:
24 VSEN x+3 0V Input x+3 0V
X2.1: X2.2: X2.3: X2.4:
Output I1+ 0V – 0V
X4.1: X4.2: X4.3: X4.4:
Output I3+ 0V – 0V
X1.1: X1.2: X1.3: X1.4:
24 VSEN x 0V Input x 0V
X2.1: X2.2: X2.3: X2.4:
24 VSEN x+2 0V Input x+2 0V
X1.1: X1.2: X1.3: X1.4:
Output I0+ 0V – 0V
X2.1: X2.2: X2.3: X2.4:
Output I2+ 0V – 0V
X1.5: X1.6: X1.7: X1.8:
24 VSEN x+1 0V Input x+1 0V
X2.5: X2.6: X2.7: X2.8:
24 VSEN x+3 0V Input x+3 0V
X1.5: X1.6: X1.7: X1.8:
Output I1+ 0V – 0V
X2.5: X2.6: X2.7: X2.8:
Output I3+ 0V – 0V
CPX-P-AB-2XKL-8POL
-H- Note In the case of mixed operation of inputs and outputs in one module, the connections are first assigned input signals and then output signals, in ascending order.
188
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 189
-V- New Terminal CPX Accessories – HART input/output module Ordering data Designation
Part No.
Type code
HART input/output module 4 analogue inputs/outputs
8059847
CPX-4AE-4AA-H
4x socket, M12, 4-pin
565706
CPX-P-AB-4XM12-4POL
2x plug, 8-pin
565704
CPX-P-AB-2XKL-8POL
Connection block Plastic
Connectors 8-pin socket
Plug M12x1, 4-pin, straight, A-coded
Spring-loaded terminal
Connection cross-section 0.2 … 2.5 mm2
565712
NECU-L3G8-C1
Screw terminal
Connection cross-section 0.2 … 2.5 mm2
565710
NECU-L3G8-C2
Insulation displacement connector Screw terminal
Connection cross-section 0.25 … 0.5 mm2
525928
SEA-GS-HAR-4POL
Connection cross-section 0.14 … 0.5 mm2 Connection cross-section 0.75 mm2 Permissible cable diameter 4 … 6 mm Connection cross-section 0.75 mm2 Permissible cable diameter 6 … 8 mm
192008 18666
SEA-4GS-7-2,5 SEA-GS-7
18778
SEA-GS-9
165592
ISK-M12
565713
CPX-P-KDS-AB-2XKL
Cover Cover cap for sealing unused ports M12x1 (10 pieces)
Coding element Ensures that a coded socket NECU-L3G8 can only be inserted in the matching coded connection block CPX-P-AB-2XKL (96 pieces of each)
2018/04 – Subject to change
For NECU-L3G8
è Internet: www.festo.com/catalogue/...
189
Page 190
Terminal CPX Technical data – Analogue module for inputs Function Analogue modules control devices with a standardised analogue inter face such as sensors for pressure, temperature, flow rate, filling level, etc. The analogue module supports vari ous connection concepts with different numbers of sockets or terminals as appropriate to the connection block selected.
Application Analogue module for 0 … 10 V, 0 … 20 mA or 4 … 20 mA Supports connection blocks with Sub-D, terminal connection and M12 connection Analogue module features can be parameterised Different data formats available Operation with and without galvanic isolation possible The analogue module receives the voltage supply for the electronics and the sensors from the interlinking block Analogue module protection and diagnostics through integrated electronic fuse protection
General technical data Type
CPX-2AE-U-I CPX-4AE-U-I Voltage input Current input Voltage input
No. of analogue inputs Max. power supply per module Fuse protection Current consumption from 24 V sensor supply (quiescent current) Current consumption from 24 V sensor supply (at full load) Nominal operating voltage, load voltage Nominal operating voltage Operating voltage range Signal range (parameterisable for each channel by means of DIL switch or software)
[A] [mA] [A] [V DC] [V DC] [V DC]
Operational error limit Basic error limit (at 25 °C) Repetition accuracy (at 25 °C) Input resistance Max. permissible input voltage Max. permissible input current
[%] [%] [%]
Conversion time per channel Cycle time (module) Data format
[ μs] [ms]
Cable length
190
[V DC] [mA]
[m]
è Internet: www.festo.com/catalogue/...
2 0.7 Internal electronic fuse Typically 50 Max. 0.7 24 ±2% 24 18 … 30 0 … 10 V 0 … 20 mA 4 … 20 mA
Current input
4
CPX-4AE-I Current input 4
1…5V 0 … 10 V –5 … +5 V –10 … +10 V ±0.3 ±0.2 0.1 100 kΩ –30 … +30 –
0 … 20 mA 0 … 20 mA 4 … 20 mA 4 … 20 mA –20 … +20 mA
Typically 150 4 12 bit + prefix
0.5 15 bit + prefix
Scalable to 15 bit
Scalable to 15 bit
10 12 bit + prefix Scalable to 15 bit
±0.5 ±0.3 0.15 100 kΩ 30 –
– – 0.15 100 Ω – 40
±0.3 ±0.2 0.1 100 Ω – Internally limited to 60
±0.6 ±0.5 0.15 100 Ω – 40
Max. 30 (shielded)
Subject to change – 2018/04