Terminal CPX Technical data – PROFIsafe shut-off module Combinations of connection blocks and PROFIsafe shut-off module Connection blocks Part No. CPX-M-AB-4-M12X2-5POL CPX-AB-8-KL-4POL

Pin allocation Connection block outputs

PROFIsafe shut-off module CPX-FVDA-P2 n n

549367 195708

CPX-FVDA-P2

CPX-M-AB-4-M12X2-5POL X1.1: X1.2: X1.3: X1.4: X1.5:

0 VOUT 1 (cannot be shut off) 24 VOUT 1 (cannot be shut off) 0 VOUT 1 (can be shut off via fieldbus) 24 VOUT 1 (can be shut off via fieldbus) FE (earth)

X3.1: X3.2: X3.3: X3.4: X3.5:

n.c. n.c. n.c. n.c. FE (earth)

X2.1: X2.2: X2.3: X2.4: X2.5:

0 VOUT 2 (cannot be shut off) 24 VOUT 2 (cannot be shut off) 0 VOUT 2 (can be shut off via fieldbus) 24 VOUT 2 (can be shut off via fieldbus) FE (earth)

X4.1: X4.2: X4.3: X4.4: X4.5:

n.c. n.c. n.c. n.c. FE (earth)

X1.0: X1.1: X1.2: X1.3:

0 VOUT 1 (cannot be shut off) 0 VOUT 1 (can be shut off via fieldbus) 24 VOUT 1 (can be shut off via fieldbus) FE (earth)

X5.0: X5.1: X5.2: X5.3:

n.c. n.c. n.c. n.c.

X2.0: X2.1: X2.2: X2.3:

n.c. n.c. 24 VOUT 1 (cannot be shut off) FE (earth)

X6.0: X6.1: X6.2: X6.3:

n.c. n.c. n.c. n.c.

X3.0: X3.1: X3.2: X3.3:

0 VOUT 2 (cannot be shut off) 0 VOUT 2 (can be shut off via fieldbus) 24 VOUT 2 (can be shut off via fieldbus) FE (earth)

X7.0: X7.1: X7.2: X7.3:

n.c. n.c. n.c. n.c.

X4.0: X4.1: X4.2: X4.3:

n.c. n.c. 24 VOUT 2 (cannot be shut off) FE (earth)

X8.0: X8.1: X8.2: X8.3:

n.c. n.c. n.c. n.c.

CPX-AB-8-KL-4POL

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

211

Page 212

Terminal CPX Technical data – PROFIsafe shut-off module Combinations of interlinking blocks and PROFIsafe shut-off module Interlinking blocks Part No. CPX-GE-EV-S CPX-GE-EV-S-7/8-4POL CPX-GE-EV-S-7/8-5POL CPX-M-GE-EV-S-7/8-CIP-4P CPX-M-GE-EV-S-7/8-5POL CPX-M-GE-EV-S-PP-5POL CPX-GE-EV CPX-M-GE-EV CPX-M-GE-EV-FVO CPX-GE-EV-Z CPX-GE-EV-Z-7/8-4POL CPX-GE-EV-Z-7/8-5POL CPX-M-GE-EV-Z-7/8-5POL CPX-M-GE-EV-Z-PP-5POL CPX-GE-EV-V CPX-GE-EV-V-7/8-4POL

PROFIsafe shut-off module CPX-FVDA-P2 – – – – – – – – n – – – – – – –

195746 541248 541244 568956 550208 563057 195742 550206 567806 195744 541250 541246 550210 563058 533577 541252

General technical data Type

CPX-M-GE-EV-FVO

Nominal operating voltage Acceptable current load (per contact/contact rail) Protection class to EN 60529 Ambient temperature Material declaration Note on materials Type of mounting Grid dimension Dimensions W x L x H Product weight

[V DC] [A] [°C]

[mm] [mm] [g]

Pin allocation Circuitry

212

è Internet: www.festo.com/catalogue/...

24 16 Depending on connection block –5 … +50 RoHS-compliant Die-cast aluminium Angled fitting 50 50 x 107 x 35 170

Pin

Allocation

–

–

–

–

–

–

–

–

Subject to change – 2018/04

Page 213

Terminal CPX Accessories – PROFIsafe shut-off module Ordering data Description

Part No.

Type

4x socket, M12, 5-pin

549367

CPX-M-AB-4-M12X2-5POL

Spring-loaded terminal, 32-pin

195708

CPX-AB-8-KL-4POL

Electronics module (can only be used with PROFINET, PROFIBUS CPX-M-GE-EV-FVO)

1971599

CPX-FVDA-P2

Metal interlinking block (only for CPX-FVDA-P2)

567806

CPX-M-GE-EV-FVO

Modular system for sensor/actuator distributor

–

NEDY-… è Internet: nedy

Plug M12, 4-pin

2x socket M12, 5-pin

8005310

NEDY-L2R1-V1-M12G5-N-M12G4

Plug

M12, PG7 M12, PG7, 4-pin for cable 2.5 mm M12, PG9 M12 for 2 cables M12 for 2 cables, 5-pin M12, 5-pin

18666 192008 18778 18779 192010 175487

SEA-GS-7 SEA-4GS-7-2,5 SEA-GS-9 SEA-GS-11-DUO SEA-5GS-11-DUO SEA-M12-5GS-PG7

–

NEBU-… è Internet: nebu

8022606 8022607 8022608 8022609 8022610 8022611

P.BE-CPX-FVDA-P2-DE P.BE-CPX-FVDA-P2-EN P.BE-CPX-FVDA-P2-ES P.BE-CPX-FVDA-P2-FR P.BE-CPX-FVDA-P2-IT P.BE-CPX-FVDA-P2-ZH

PROFIsafe shut-off module Metal connection block Plastic connection block

Distributor

Plug

Connecting cable Modular system for connecting cables

Manual Manual for PROFIsafe shut-off module

2018/04 – Subject to change

German English Spanish French Italian Chinese

è Internet: www.festo.com/catalogue/...

213

Page 214

Terminal CPX Technical data – End plate with system power supply Function End plates form the outer edge of the CPX terminal. The earth connection and mounting holes for wall or H-rail mounting are located on the left end plate. The end plate with system power supply has contact rails from which the other CPX components on the interlinking modules are supplied with power.

Application 24 V DC supply voltage for the electronics of the CPX terminal 24 V DC supply voltage for inputs 24 V DC supply voltage for valves 24 V DC supply voltage for outputs

General technical data Electrical connection Type of mounting Power supply Maximum power supply Product weight

[A] [g]

Plug, 7-pin Tie rod System power supply 12 145

Materials Housing Note on materials

Die-cast aluminium, painted RoHS-compliant

Operating and environmental conditions Approval certificate cULus Recognized (OL)

Pin allocation Circuitry

Pin

Allocation

1

0 V power supply for valves

2

24 V DC load voltage supply for valves

3

0 V power supply for outputs

4

24 V DC load voltage supply for outputs

5

0 V power supply for electronics and sensors

6

24 V DC power supply for electronics and sensors

7

FE

Plug, 7-pin

214

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 215

Terminal CPX Accessories – End plate with system power supply Ordering data End plate with system power supply End plate for CPX terminal in plastic design

Part No.

Type

576315

CPX-EPL-EV-S

576319

NECU-L3G7-C1

Terminal strip Plug, 7-pin, straight

2018/04 – Subject to change

Spring-loaded terminal

è Internet: www.festo.com/catalogue/...

215

Page 216

Terminal CPX Technical data – End plate with extension Function End plates form the outer edge of the CPX terminal. The earth connection and mounting holes for wall or H-rail mounting are located on the left end plates. The end plates with extension enable the CPX terminal to be separated into two interconnected terminals. Control is provided via a common bus node or control block.

Application Separation of long CPX terminals into two shorter units Adaptation for installation in a control cabinet

General technical data Type

CPX-EP…

CPX-M-EP…

Type of mounting Maximum power supply

Tie rod 6

Angled fitting 6

Materials Type

CPX-EP…

CPX-M-EP…

Housing Note on materials

Die-cast aluminium, painted RoHS-compliant

Die-cast aluminium RoHS-compliant

[A]

Operating and environmental conditions Approval certificate

216 cULus Recognized (OL)

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 217

Terminal CPX Technical data – End plate with extension Pin allocation – End plate with extension Circuitry

Pin

Right-hand end plate (first row)

Allocation

Pin

Round plug, 8-pin M12

Circuitry Left-hand end plate (second row)

1

0 V DC supply voltage for electronics and sensors

1

2

0 V DC load voltage supply for valves

2

3

24 V DC load voltage supply for valves

3

4

24 V DC supply voltage for electronics and sensors

4

5

Bus signal

5

6

Bus signal

6

7

Bus signal

7

8

Bus signal

8

Housing

FE

Housing

Ordering data

End plate with extension For CPX terminal in plastic design For CPX terminal in metal design

First row, right-hand end plate Second row, left-hand end plate First row, right-hand end plate Second row, left-hand end plate

Weight [g]

Part No.

Type

190 175 190 175

576313 576314 576316 576317

CPX-EPR-EV-X CPX-EPL-EV-X CPX-M-EPR-EV-X CPX-M-EPL-EV-X

47 69 113 154 200 280

564189 564190 564191 564192 576015 576636

NEBC-F12G8-KH-0.25-N-S-F12G8 NEBC-F12G8-KH-0.5-N-S-F12G8 NEBC-F12G8-KH-1-N-S-F12G8 NEBC-F12G8-KH-1.5-N-S-F12G8 NEBC-F12G8-KH-2-N-S-F12G8 NEBC-F12G8-KH-3-N-S-F12G8

Connecting cable 8-pin

2018/04 – Subject to change

0.25 m 0.5 m 1m 1.5 m 2m 3m

è Internet: www.festo.com/catalogue/...

217

Page 218

Terminal CPX Technical data – Interlinking block with system supply Function Interlinking blocks ensure the electri­ cal supply of all other CPX modules. They have contact rails, from which the other CPX components on the in­ terlinking modules are supplied with current. Internal division of the power supply makes it possible to switch off specific areas of the sensors and actuators individually.

Applications 24 V DC supply voltage for electronics of the CPX terminal 24 V DC supply voltage for inputs 24 V DC supply voltage for valves 24 V DC supply voltage for outputs

General technical data Nominal operating voltage Protection class to EN 60529 Ambient temperature Note on materials Grid dimension Dimensions W x L x H

[V DC] [°C] [mm] [mm]

Technical data – Plastic interlinking blocks Type

24 Depending on connection block –5 … +50 RoHS-compliant 50 50 x 107 x 35

CPX-GE-EV-S -VL

Electrical connection Current supply

Sensors and electronics Valves and outputs

Materials Product weight

[A] [A] [g]

Technical data – Metal interlinking blocks Type Electrical connection Current supply Materials Product weight

Sensors and electronics Valves and outputs

[A] [A] [g]

M18 M18 Max. 16 Max. 8 Max. 16 Max. 8 PA, reinforced 125

-7/8-4POL

-7/8-5POL

-7/8-5POL-VL

7/8", 4-pin Max. 10 Max. 10

7/8", 5-pin Max. 8 Max. 8

7/8", 5-pin Max. 8 Max. 8

CPX-M-GE-EV-S -7/8-CIP-4P

-7/8-5POL

-7/8-5POL-VL

-PP-5POL

7/8", 4-pin

7/8", 5-pin

7/8", 5-pin Max. 8 Max. 8

AIDA push-pull, 5-pin Max. 16 Max. 16

187

279

Max. 10 Max. 8 Max. 10 Max. 8 Die-cast aluminium 187 187

-H- Note Note the following points about the interlinking block CPX-M-GE-EV-S-7/8-CIP-4P: Must be mounted as the first module to the right of the left-hand end plate

218

è Internet: www.festo.com/catalogue/...

Only permitted as an interlinking block to a bus node The functional earth (FE) must be connected via the left-hand end plate

Subject to change – 2018/04

Page 219

Terminal CPX Technical data – Interlinking block with system supply Pin allocation – Plastic interlinking blocks Circuitry

Pin

Allocation

1

24 V DC supply voltage for electronics and sensors

2

24 V DC load voltage supply for valves and outputs

3

0V

4

FE

A

24 V DC supply voltage for electronics and sensors

B

24 V DC load voltage supply for valves and outputs

C

FE

D

0V

1 2 3 4 5

0 V valves and outputs 0 V electronics and sensors FE 24 V DC supply voltage for electronics and sensors 24 V DC load voltage supply for valves and outputs

Round connector, 4-pin M18

7/8”

Round connector, 5-pin 7/8”

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

219

Page 220

Terminal CPX Technical data – Interlinking block with system supply Pin allocation – Metal interlinking blocks Circuitry

Pin

Allocation

1 2 3 4 5

0 V valves and outputs 0 V electronics and sensors FE 24 V DC supply voltage for electronics and sensors 24 V DC load voltage supply for valves and outputs

A B C D

24 V DC supply voltage for electronics and sensors 24 V DC load voltage supply for valves and outputs 0 V DC supply voltage for electronics and sensors 0 V DC load voltage supply for valves and outputs

Round connector, 5-pin 7/8"

Round connector, 4-pin 7/8"

-H- Note The functional earth (FE) must be connected via the left-hand end plate