Terminal CPX Technical data – Analogue module for thermocoupler Function The CPX-4AE-TC analogue input mod ule with four channels for temperature measurement enables up to four ther mocoupler sensors to be connected. The channels feature wire break and short circuit detection. If no cold junction compensation sensor is being used, an internal theoretical value of 25 °C can be used (accuracy is impaired).
Applications Supports connection blocks with M12 and terminal connection Temperature module features can be parameterised 2-wire connection 2-wire connection for a PT1000 sensor for cold junction compensation The temperature module is provided with voltage supply for the electronics and the sensors via the interlinking block Temperature module protection and diagnostics through integrated electronic fuse protection
General technical data Type No. of analogue inputs Fuse protection (short circuit) Nominal operating voltage Operating voltage range Sensor type (parameterisable for each channel by means of software)
Sensor connection technology Operating error limit relative to ambient temperature Basic error limit (at 25 °C) Repetition accuracy (at 25 °C) Max. line resistance per wire Max. residual current per module Max. permissible input voltage Internal cycle time (module)
2018/04 – Subject to change
CPX-4AE-TC Temperature input
[V DC] [V DC]
[%] [%] [%] [Ω] [mA] [V] [ms]
4 Internal electronic fuse for each channel 24 18 … 30 Type B +400 … +1,820 °C, 8 ìV/°C Type E –270 … +900 °C, 60 ìV/°C Type J –200 … +1,200 °C, 51 ìV/°C Type K –200 … +1,370 °C, 40 ìV/°C Type N –200 … +1,300 °C, 38 ìV/°C Type R 0 … +1,760 °C, 12 ìV/°C Type S 0 … +1,760 °C, 11 ìV/°C Type T –200 … +400 °C, 40 ìV/°C 2-wire technology Max. ±0.6 Max. ±0.4 ±0.05 10 30 ±30 250
è Internet: www.festo.com/catalogue/...
201
Page 202
Terminal CPX Technical data – Analogue module for thermocoupler General technical data Data format Cable length Electrical isolation
[m] Channel – channel Channel – internal bus Group diagnostics Channel diagnostics
LED displays Diagnostics
Parameterisation
Protection class to EN 60529 Temperature range
Operation Storage/transport
Materials Grid dimension Dimensions (incl. interlinking block and connection block) W x L x H Weight
[°C] [°C] [mm] [mm] [g]
15 bit + prefix, complement of two Binary notation in tenths of a degree Max. 50 (screened) No Yes 1 4 Parameterisation error Wire break per channel Limit value violation per channel Wire break monitoring per channel Unit of measurement Cold junction compensation Sensor type per channel Limit value monitoring per channel Measured value smoothing Depending on connection block –5 … +50 –20 … +70 Reinforced PA, PC 50 50 x 107 x 50 38
Connection and display components CPX-4AE-TC 1
1 Error LED (red, module error) 2 Channel-specific error LEDs (red)
1 Connection block/analogue module combinations Connection blocks Part No. CPX-AB-4-M12X2-5POL CPX-AB-4-M12X2-5POL-R CPX-AB-8-KL-4POL CPX-M-AB-4-M12x2-5POL
202
195704 541254 195708 549367
è Internet: www.festo.com/catalogue/...
Temperature module CPX-4AE-TC n n n n
Subject to change – 2018/04
Page 203
Terminal CPX Technical data – Analogue module for thermocoupler Pin allocation Connection block inputs
CPX-4AE-TC
CPX-AB-4-M12X2-5POL, CPX-AB-4-M12X2-5POL-R1) and CPX-M-AB-4-M12X2-5POL X1.1: Input I0+ X1.2: Input U0+ X1.3: Input I0– X1.4: Input U0– X1.5: FE2)
X3.1: X3.2: X3.3: X3.4: X3.5:
Input I2+ Input U2+ Input I2– Input U2– FE2)
X2.1: X2.2: X2.3: X2.4: X2.5:
Input I1+ Input U1+ Input I1– Input U1– FE2)
X4.1: X4.2: X4.3: X4.4: X4.5:
Input I3+ Input U3+ Input I3– Input U3– FE2)
X1.0: X1.1: X1.2: X1.3:
Input I0+ Input I0– Input U0– FE
X5.0: X5.1: X5.2: X5.3:
Input I2+ Input I2– Input U2– FE
X2.0: X2.1: X2.2: X2.3:
n.c. n.c. Input U0+ FE
X6.0: X6.1: X6.2: X6.3:
n.c. n.c. InputUI2+ FE
X3.0: X3.1: X3.2: X3.3:
Input I1+ Input I1– Input U1– FE
X7.0: X7.1: X7.2: X7.3:
Input I3+ Input I3– Input U3– FE
X4.0: X4.1: X4.2: X4.3:
n.c. n.c. Input U1+ FE
X8.0: X8.1: X8.2: X8.3:
n.c. n.c. Input U3+ FE
CPX-AB-8-KL-4POL
1) 2)
Speedcon quick lock, screening additionally on metal thread FE/screening additionally on metal thread
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
203
Page 204
Terminal CPX Accessories – Analogue module for thermocoupler Ordering data Designation
Part No.
Type
553594
CPX-4AE-TC
4x socket, M12, 5-pin
195704
CPX-AB-4-M12X2-5POL
4x socket, M12 with quick-lock technology, 5-pin
541254
CPX-AB-4-M12X2-5POL-R
Spring clip terminal, 32-pin
195708
CPX-AB-8-KL-4POL
4x socket, M12, 5-pin
549367
CPX-M-AB-4-M12X2-5POL
553596
CPX-W-PT1000
M12 plug, 5-pin
175487
SEA-M12-5GS-PG7
Cover for CPX-AB-8-KL-4POL (IP65, IP67) – 8 cable through-feeds M9 – 1 cable through-feed for multi-pin plug
538219
AK-8KL
Fittings kit
538220
VG-K-M9
Screening plate for M12 connections
526184
CPX-AB-S-4-M12
User manual
526415 526416 526417 526418 526419
P.BE-CPX-AX-DE P.BE-CPX-AX-EN P.BE-CPX-AX-ES P.BE-CPX-AX-FR P.BE-CPX-AX-IT
Input module, analogue 4 analogue temperature inputs, with 2-wire connection for a PT1000 sensor for cold junction compensation
Connection block Plastic
Metal
Cold junction compensation PT1000 temperature sensor for cold junction compensation
Plug
Cover
Screening plate
User manual
204
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 205
Terminal CPX Technical data – Analogue module for outputs Function Analogue modules control devices with a standard analogue interface such as proportional valves, etc. The analogue module supports vari ous connection concepts with different numbers of sockets or terminals as appropriate to the connection block selected.
Applications Analogue module for 0 … 10 V, 0 … 20 mA or 4 … 20 mA Supports connection blocks with M12, Sub-D and terminal connection Analogue module features can be parameterised Different data formats available Operation with and without galvanic isolation possible The analogue module receives the voltage supply for the electronics and the actuators from the interlinking block Analogue module protection and diagnostics through integrated electronic fuse protection
General technical data Type No. of analogue outputs Max. actuator supply per module Fuse protection Current consumption from 24 V sensor supply (at full load) Current consumption from 24 V actuator supply (at full load) Supply voltage of actuators Signal range (parameterisable for each channel by means of DIL switch or software) Resolution No. of units Absolute accuracy Linearity errors (no software scaling) Repetition accuracy (at 25 °C) Encoder selection Load resistance for ohmic load Load resistance for capacitive load Load resistance for inductive load Short circuit protection analogue output Short circuit current analogue output Open circuit voltage Destruction limit against externally applied voltage Actuator connection Cycle time (module)
2018/04 – Subject to change
CPX-2AA-U-I Voltage output
Current output
[%] [%] [%] [kΩ] [μF]
2 2.8 Internal electronic fuse for actuator supply Max. 150 4 … 10 24 ±25% 0 … 10 V DC 0 … 20 mA 4 … 20 mA 12 4,096 ±0.6 ±0.1 0.05 Min. 1 Max. 0.5 Max. 1 –
[mH]
–
Max. 1
Yes
–
[mA]
Approx. 20
–
[V DC] [V DC]
– 15
18
[ms]
2 wires 4
[A] [mA] [A] [V DC]
[bit]
è Internet: www.festo.com/catalogue/...
205
Page 206
Terminal CPX Technical data – Analogue module for outputs General technical data Type
CPX-2AA-U-I Voltage output
Response time
For ohmic load For capacitive load For inductive load
[ms] [ms] [ms]
Data format
Cable length LED displays
[m] Group diagnostics Channel diagnostics
Diagnostics
Parameterisation
Protection class to EN 60529 Temperature range
Operation Storage/transport
Materials Grid dimension Dimensions (incl. interlinking block and connection block) W x L x H Weight
[°C] [°C] [mm] [mm] [g]
Current output
0.1 0.1 0.7 – – 0.5 15 bit + prefix, linear scaling 12 bit right-justified 12 bit left-justified, S7 compatible 12 bit left-justified, S5 compatible Max. 30 (screened) 1 Yes, by means of flashing frequency of group diagnostics Short circuit/overload, actuator supply Parameterisation error Value falling below nominal range/full-scale value Value exceeding nominal range/full-scale value Wire break Short circuit monitoring, actuator supply Short circuit monitoring, analogue output Behaviour after short circuit, actuator supply Data format Lower limit value/full-scale value Upper limit value/full-scale value Monitoring of value falling below nominal range/full-scale value Monitoring of value exceeding nominal range/full-scale value Wire break monitoring Signal range Depending on connection block –5 … +50 –20 … +70 Reinforced PA, PC 50 50 x 107 x 50 38
Connection and display components CPX-2AA-U-I 1
1 Error LED (red, module error)
Connection block/analogue module combinations Connection blocks Part No. CPX-AB-4-M12X2-5POL CPX-AB-4-M12X2-5POL-R CPX-AB-8-KL-4POL CPX-AB-1-SUB-BU-25POL CPX-M-AB-4-M12X2-5POL
206
195704 541254 195708 525676 549367
è Internet: www.festo.com/catalogue/...
Analogue module CPX-2AA-U-I n n n n n
Subject to change – 2018/04
Page 207
Terminal CPX Technical data – Analogue module for outputs Pin allocation Connection block outputs
CPX-2AA-U-I
CPX-AB-4-M12X2-5POL, CPX-AB-4-M12X2-5POL-R1) and CPX-M-AB-4-M12X2-5POL X1.1: 24 VOUT X1.2: Output U0+ X1.3: 0 VOUT X1.4: Output GND X1.5: FE2)
X3.1: X3.2: X3.3: X3.4: X3.5:
24 VOUT Output U1+ 0 VOUT Output GND FE2)
X2.1: X2.2: X2.3: X2.4: X2.5:
24 VOUT Output I0+ 0 VOUT Output GND FE2)
X4.1: X4.2: X4.3: X4.4: X4.5:
24 VOUT Output I1+ 0 VOUT Output GND FE2)
X1.0: X1.1: X1.2: X1.3:
24 VOUT 0 VOUT Output GND FE
X5.0: X5.1: X5.2: X5.3:
24 VOUT 0 VOUT Output GND FE
X2.0: X2.1: X2.2: X2.3:
n.c. n.c. Output U0+ FE
X6.0: X6.1: X6.2: X6.3:
n.c. n.c. Output U1+ FE
X3.0: X3.1: X3.2: X3.3:
24 VOUT 0 VOUT Output GDN FE
X7.0: X7.1: X7.2: X7.3:
24 VOUT 0 VOUT Output GND FE
X4.0: X4.1: X4.2: X4.3:
n.c. n.c. Output I0+ FE
X8.0: X8.1: X8.2: X8.3:
n.c. n.c. Output I1+ FE
1: 2: 3: 4: 5: 6: 7: 8: 9: 10: 11: 12: 13:
Output GND Output U0+ Output GND Output I0+ n.c. n.c. n.c. n.c. 24 VOUT 24 VOUT 0 VOUT 0 VOUT Screening3)
14: Output GND 15: Output U1+ 16: Output GND 17: Output I1+ 18: 24 VOUT 19: n.c. 20: 24 VOUT 21: n.c. 22: 0 VOUT 23: 0 VOUT 24: 0 VOUT 25: FE Housing: FE
CPX-AB-8-KL-4POL
CPX-AB-1-SUB-BU-25POL
1) 2) 3)
Speedcon quick lock, screening additionally on metal thread FE/screening additionally on metal thread Connect screening to functional earth FE
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
207
Page 208
Terminal CPX Accessories – Analogue module for outputs Ordering data Designation
Part No.
Type
Output module, analogue 2 analogue current or voltage outputs
526170
CPX-2AA-U-I
195704 541254 195708 525676 549367
CPX-AB-4-M12X2-5POL CPX-AB-4-M12X2-5POL-R CPX-AB-8-KL-4POL CPX-AB-1-SUB-BU-25POL CPX-M-AB-4-M12X2-5POL
M12 plug, 5-pin
175487
SEA-M12-5GS-PG7
Sub-D plug, 25-pin
527522
SD-SUB-D-ST25
Modular system for connecting cables
–
NEBU-… è Internet: nebu
Cover for CPX-AB-8-KL-4POL (IP65, IP67) – 8 cable through-feeds M9 – 1 cable through-feed for multi-pin plug
538219
AK-8KL
Fittings kit
538220
VG-K-M9
Screening plate for M12 connections
526184
CPX-AB-S-4-M12
User manual
526415 526416 526417 526418 526419
P.BE-CPX-AX-DE P.BE-CPX-AX-EN P.BE-CPX-AX-ES P.BE-CPX-AX-FR P.BE-CPX-AX-IT
Connection block Plastic
4x socket, M12, 5-pin 4x socket, M12 with quick-lock technology, 5-pin Spring clip terminal, 32-pin 1x Sub-D socket, 25-pin 4x socket, M12, 5-pin
Metal Plug
Connecting cable
Cover
Screening plate
User manual
208
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 209
Terminal CPX Technical data – PROFIsafe shut-off module Function The PROFIsafe shut-off module inter rupts the contact rails of the interlink ing block for valves and outputs. The supply voltage for valves can be switched by the module within the CPX terminal and via a connection block to two consuming devices. Actuation takes place via the fieldbus node (PROFINET) of the CPX terminal.
Scope of application Output module for 24 V DC supply voltage Shut-off module for supply voltage for valves Can only be used with PROFINET or PROFIBUS bus node The shut-off module is supplied with voltage for the electronics and the outputs by the interlinking block The outputs are supplied from the power supply for valves (VValves)
General technical data Type
CPX-FVDA-P2
Number of outputs Note on outputs Max. power supply
Per module Per channel
Fuse protection (short circuit) Current consumption of module Operating voltage
Nominal value Permissible range
Voltage drop per channel Residual ripple Load capacity to FE Max. response time to shut-off command Electrical isolation Channel – channel Channel – internal bus Switching logic Outputs Safety integrity level Performance level Failure rate per hour (PFH) Certificate issuing authority LED displays Group diagnostics Channel diagnostics Channel status Failsafe protocol active Diagnostics
[A] [A] [mA] [mA] [V DC] [V DC] [V] [Vss] [nF] [ms]
Parameterisation Protection class to EN 60529 Materials Note on materials Grid dimension Dimensions (incl. interlinking block and connection block) W x L x H
2018/04 – Subject to change
[mm] [mm]
2 1 internal channel for shutting off the supply voltage for valves 2 external outputs 5 1.5 Internal electronic fuse for each channel Typ. 65 (power supply for valves) Typ. 25 (power supply for electronics) 24 20.4 … 28.8 0.6 2 within voltage range 400 23 No Yes, using an intermediate supply P-M switching Safe shut off, SIL 3 Safe shut off/category 3, performance level e 1.0x10-9 01/205/50294/13 1 3 3 1 Short circuit/overload per channel Undervoltage of valves Cross circuit Wire break per channel Wire break monitoring per channel Diagnostic behaviour Depending on connection block PA reinforced, PC RoHS-compliant 50 50 x 107 x 55
è Internet: www.festo.com/catalogue/...
209
Page 210
Terminal CPX Technical data – PROFIsafe shut-off module Operating and environmental conditions Ambient temperature Storage temperature CE mark (see declaration of conformity) Certification
[°C] [°C]
–5 … +50 –20 … +70 To EU Machinery Directive c UL us - Recognized (OL)
Connection and display components CPX-FVDA-P2 4
1
2
1 Status LEDs (yellow): 0: Supply voltage for valves 1: X1 2: X2
3
Combinations of bus nodes/control blocks and PROFIsafe shut-off module Bus node/control block Part No. CPX-FB13 CPX-FB33 CPX-M-FB34 CPX-M-FB35
2 Channel-specific error LEDs (red) 3 Failsafe protocol active (green) 4 Error LED (red, module error)
195740 548755 548751 548749
PROFIsafe shut-off module CPX-FVDA-P2 n n n n
-H- Note The PROFIsafe shut-off module CPX-FVDA-P2 can only be interfaced as of software release 21 or release 30 (CPX-FB13).
210
è Internet: www.festo.com/catalogue/...