Series One Programmable Controllers, Series One/One Plus User's Manual: Chapter 1 Series One/Series One Plus PC Introduction
Pages 21 to 30 of 300, from Series One Programmable Controllers, Series One/One Plus User's Manual
The original document is the PDF (40 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the GE Fanuc IC610CPU105A, GE Fanuc IC610CPU105C, Fanuc IC610CPU105A, GE IC610CPU105A, Fanuc IC610CPU105C and GE IC610CPU105C
Page 21
Chapter m 11
1
Series One/Series One Plus PC Introduction
? GEL90842
History of Programmable Controllers The factory with a future is here today, with machine and process controls provided by modem electronic devices. Today’s automated factory can provide improved system reliability, product quality, information flow, reduced costs, efficiency, and flexibility. One of the basic building blocks of such a factory is an electronic device called a Programmable Controller. This device was first introduced in 1970 and has been refined every 4-7 years as newer electronic components, such as microprocessors, are made available. Today’s Programmable Controllers are designed using the latest in microprocessor designs and electronic circuitry which provide reliable operation in industrial applications where many hazards such as electrical noise, high temperature, unreliable AC power, and mechanical shock exist. Here is where the Programmable Controller is in its element; it was designed for the industrial environment from its conception.
Advantages Over Other Control Devices Programmable Controllers, or PCs or PLCs as they are frequently referred to, offer many advantages over other control devices such as relays, electrical timers and counters, and drum type mechanical controllers. These advantages should be considered beyond just price when selecting any control device: Improved reliability Smaller space required l Easiertomaintain
0 Reusable 0 Reprogrammable if requhments change 0 More flexible-performs more fhctions
Series One Programmable Controllers A complete Series One PC contained in one S-slot rack can have over 1700 words of user logic, up to 64 timer/counters, and up to 64 I/O points in a panel surface area of only 54 square inches. That is less space than four 4pole relays might occupy. An available lo-slot rack can contain up to 120 I/O points. By adding additional racks (up to a total of three), the I/O can be expanded up to a total of 112 I/O points in a Series One PC or 168 points in a Series One Plus PC. Modules can be replaced individually without disturbing adjacent modules or their field wiring. The VO can be intermixed in many configurations, limited only by the module types available (either 4,8, or 16 circuits per module - see Chapter 6). Users need only purchase those modules required for their application; there is no fixed mix such as 12 in/8 out or 20 in/l2 out, The hand-held programmer can be fixed onto the CPU for quick reference, removed and carried in a pocket for future use, connected to the CPU via a 5 foot (1.5m) cable for flexible temporary use or mounted on the outside of a panel or console. It is a simple pushbutton and display unit designed for easy transportation and rugged use. Progr amming can also be done with the Portable Programmer or with a Workmaster Industrial computer using Logicmaster 1 application software for Series One or Logicmaster 1F application software for Series One Model E, Series One Plus and Series One Plus 3.7K. The Series One and Series One Plus PCs are designed control replacements. One Plus PCs.
to be very cost effective relay or other sequential Despite the low cost, there is a lot of capability within the Series One and Series
Page 22
12I)
Series One/Series One Plus PC Introduction GEK-90842
The advantages l l l l l l l l l a 0 a l l 0 l 0 l l 0 0 l and features offered by the Series One and Series One Plus PCs include:
Small size - (64 I/O points in a 5-slot rack) Large Memory Capacity Timers/Counters Programming LanguageMaximum I/O Latching relays &bit Data Registers Flexible I/O Replaceable I/O Modules Portable ProgrammerPersonal Password Security
54 in2 panel space, 5 l/2 in. maximum depth, 250 i.19total volume Up to 1724 wonk of CMOS or PROM Up to 64 (4 digit, 9999 maximum preset) Boolean Based Relay Ladder Data Operations (Series One Plus Only) 112 (Series One) - 168 (Series One Plus) 28 total 64 (Series One Plus), 124 with TC refennces Anymixingroupsof4,8or16 Weight only 7 02s. Series One Plus and Series One Model E (Permits only Authorized Access To User’s Programs)
Internal and external indication of low battery Reliable operation without fan finm 0’ to 60’ C (convection cooling) Retentive counters Shift Registers (128) Built-in Sequencers Standard - Up to 64, each with up to 1000 steps Meets or exceeds NEMA ICS3-304 for noise rejection Self Diagnostics htemal Power for 24 V dc Inputs Inexpensive High Speed Counter Remote I/O - Saves instalktion and wiring cost a40793
Figure l-l. Series One/Series One Plus Programmable Controllers
Page 23
Series One/Series
One Plus PC Introduction m 13
GEK-90842
Series One Model E Programmable
Controller
The Series One Model E PC is an enhanced version of the Series One PC that offers more capability while retaining all of the features and functions of the Series One PC. The Model E requires an Ic610CPUI04 CPU module. The additional features of the Series One Model E are: Faster Scan Rate.Typical scan times are: 8 mSec for a OSK word program 12 mSec for a l.OK program 15 mSec for a 1.7K word program Password ProtectionAs with the Series One Plus PC, this is a valuable feature in that it permits only authorized access to user programs stored in the PC memory. A unique 4digit password is entered by the user and thereafter access to all functions (except monitor functions) is gained through a LOG ON sequence entered by the operator. After completion of required operations, a LOG OUT sequence returns the PC to password protection. Faster Data Communications.The Series One Model E PC requires the IC61OCCM.105 Data Communications Unit to communicate with external devices. Communications speed is noticeably faster when communicating with external devices, such as a host computer, than with a Series One PC using either the older version IC61OCCMlOO or the IC61OCCM105 Data Communications Unit. Program upload or download time, and access time to I/O, and timer/counter data is reduced during I communications sessions.
Series One Plus 3.7K The Series One Plus 3.7K PC is an enhancement of the Series One Plus PC which offers greater memory capability, while retaining all other features and functions of the Series One Plus PC. The Series One Plus 3.7K PC uses an IC61OCPU106 CPU module that provides 3700 words of CMOS RAM: or optional PROM memory (compared to 1700 words of memory available with a Series One Plus with an IC61OCPU105 CPU module). A typical scan time for a 3.7K word program is 36 milliseconds. This additional memory capability allows the Series One Plus 3.7K PC to moTe fully take advantage of programming with the data operations since those ladder logic programs that require numerous data operations also require more memory than do programs using the basic functions. The additional memory in a Series One Plus 3.7K PC provides the user with a great deal of capability in a small package. An additional feature of the Series One Plus 3.7K PC is that timers can be programmed to be .Ol second timers instead of .l second. This is done by setting output 770 (SET 770) to the ON condition. The timer preset range with a .Ol second duration selected is 0.01 to 99.99 seconds. When selecting timers to be .Ol in this manner, care must be exercised to prevent your program from resetting coil 770, since this would cause all timers programmed to then be .l second timers. Timer durations cannot be mixed, they can all only be .l second or .Ol second in the same program. Any Timer/Counter accumulate registers not being used for a Timer/Counter can be accessed and used as data registers as with the Series One Plus PC. Table l-1 provides a summary of general specifications for both PCs.
Page 24
(I) 14
Series One/Series One Plus PC Introduction I
GEK-90842
Table M. Series One Family General Specifications Operating Temperature Storage Temperature Humidity (non-condensing) AC Power Required: 1C610CHS101/110/130 Rack vohage FFequency
Maximum Load output
CwTeen~
Maximum Individual
DC Power Required IC61OCHS114/l34 Rack Voltage
Ripple output current
Maximum Individual
Maximum, Total (All Voltages) Typical Battery life * (loaded) shelf We * (no load)
0’ to 60°C (32” to 14OOF) -loo to 7ooc (14O to +lSs”F) 5 to 95% llSV/230 v ac 15% 47-63 Hz 30 VA (CHSlOl/llO) 36.7 VA (CHS130) 1.4 A at 5 V dc, (0.4 A, CHSlOl) 0.8 A at 9 V dc, CHSllO (1.7 A, CHS130), (0.6 A, CHSlOl) 0.5 A at 24 V dc, (0.2 A, CHSlOl)
20.5 - 30 V dc (100% of capacity used) 18 - 30 V dc (90% of capacity used) 10% of Input Voltage 1.4 A at 5 V dc 0.8 A at 9 V dc, CHS114 (1.7 & cHS134) 0.4 A at 24 V dc, -114 (0.5 A, CHS134) 22 A, CHS114 (2.3 A, CHS134) 2-5 years 8-10 years
*Depends upon operating temperature Memory Size and Type (16-bit words)
700 words (CMOS) or 1724 words (CMOS or EPROM) 3700 words (Series One Plus 3.7K (CMOS or EPROM)
Typical Scan Time per K of Memory) (Only memory programmed is scanned)
20 m&c (O.SK)
Series One
Overhead time must be added to the
40 m&c (l.OK) 65 msec (1X)
logic solution for total real scIu1, time overhead is typically 4 to 5 m&c. series one Plus aadModelE one Plus 3.7K
Maximum I/O Intemal coils special Fbuaction coils
Retintive Coils (Latches) Timer/Counters Shift Register Stages seqrrepcers
Data Rm
(Series One Pius and
Series one Pius 3.7K)
8 mSec (0.5K) 12 mSec (l.OK) 15 mSec (1.7K) 36 m&c (3.7K)
112 (s&es one) 168 (Series One Plus) 144
4 28 64 (Wigit) 128 64atlooOstepseach ’ 64 (&bit), up to 124 with mused T/C references
Page 25
l-5
Series One/Series One Plus PC Introduction GEK-90842
Programmable Controller Concepts When using a new product for the first time, there are always new concepts and terms to become familiar with. Although PC’s are relatively easy to install, program, and apply, there are some simple principles to follow. Figure 1-2 illustrates a general block diagram of a Programmable Controller. Specific hardware components to illustrate this diagram will be described in Chapter 2.
1 c INPUT/ OUTPUT
I
0
II I 1
I
I
I
CENTRAL PROCESSOR UNIT
PROGRAMMER
1 I
I
1
USER SUPPLIED FIELD DEVICES
L ---B-B---
I I 1 I
J
Figure l-2. Basic PC Block Diagram Programming the Series One and Series One Plus PCs The programmin g devices are used to enter the specific logic the user desires the PC to follow.
This logic, to be described in detail in Chapter 5 is what makes the user’s PC a unique unit, different from all others unless the identical logic is entered into another unit. Recording and reloading logic from one PC to another or to itself is also a standard feature with the programmers.
Hand-Held Programmer The programmer can display any previously entered logic, allow the user to edit it (make changes, add or delete portions of the logic), or display the current value of any internal timer or counter. It is a very valuable and powerful piece of peripheral equipment, for entry of logic, control system checkout, and troubleshooting. It can be permanently comected to the CPU or removed without disturbing the operation of the CPU. If removed, one programmer can service several CPUs. The exact quantity of CPUs is dependent upon the expected rate of usage but typically is between 5 and 20 CPUs.
Portable Programmer The portable programmer uses a liquid crystal display (LCD) screen to allow ladder logic programming for both the Series One and Series One Plus PCs. New programs can be created, previously entered ladder logic displayed and existing logic edited. An on-line monitor function is available when the Portable Programmer is used with the Series One Plus. Programs can be transferred to the PCs or stored
Page 26
16m
Series One/Series One Plus PC Introduction GEK-90842 on cassette tape. The program can be printed using a standard parallel or Centronics compatible printer through the printer port located on the rear of the Portable Programmer. For detailed information refer to GEK-90846, which is the Portable Programmer User’s Manual.
Logicmaster 1 Family Application Software Another option available for programmin g the Series One Family of PCs is the Workmaster industrial computer with Logicmaster 1 Family application software. This software allows you to write, edit, display, and print programs in ladder diagram format. You can view up to 7 lines of your ladder diagram program on one screen. Programs can be annotated by assigning names and nicknames to program elements, assigning labels to coils and adding explanations of program rungs or segments. Many programs can be stored on a single 3 inch diskette and each program can be assigned a unique name. For detailed information on using the Workmaster industrial computer with Logicmaster 1 application software refer to GFK-0075, which is the Logicmaster 1 Family Programming and Documentation Software User’s Manual.
Series One Plus Program Protection The Series One Plus and Series One Model E PCs allow the user to enter a unique password with the hand-held programmer or the LCD Portable Programmer, which prevents unauthorized users or inadvertent program access. When a password is entered, all programmer functions are disabled except the I/O, T/C accumulated value and register monitor functions. In order to have access to all programmer functions when a password has been entered, a log on sequence must be entered. i
Function of the Central Processing Unit The next element of the PC is the Central Processor Unit (CPU). The CPU is the “brain” behind all logical decision making. It reads in the status of the control system, makes decisions based upon the logic it has been provided, and then provides decisions to the actuating portion of the control system. The CPU also performs self checking of its internal operation to ensure reliable operation. If an error is detected, it will shut itself down. The logic entered by the programmer is actually stored in the CPU along with storage for the operation of timers and counters.
Memory Word Length The memory provided for this storage diction is normally measured in K words, where K is an abbreviation for kilo or 1024. Typically, one word is required storage for each function such as a relay contact, timer preset or timer storage. These words can be of various lengths such as 16 bits, 8 bits, or even 4 bits, wherein a bit is the most elementary measurement and can have only two states (on or off). The word length is much like a ruler used to measure wire, sheet steel, or fabric. It can be a yard long (16 bits) or a foot (8 bits) or an inch (4 bits). Numerical values are for illustrative purposes only and do not represent exact ratios. Thus when quoting memory in K words (lK, UC, 4K, etc.) always check to verify the word length. The Series One and Series One Plus PCs use the most common measurement, 16 bits per word.
Page 27
Series One/Series One Plus PC Introduction
17-
GEK-90842
Types of Memory for Program Storage There are several types of memory used in PCs to store both logic and data. ‘Ike two used in the Series One and Series One Plus PCs are CMOS and PROM. CMOS or CMOS RAM, which is an acronym for Complimentary Metal-oxide Semiconductor, Random Access Memory, provides a fast, low cost, low power memory that can be both examined (read) and also changed (written) easily. However, it is volatile, which means that it can lose its content if power is removed. To avoid reloading memory (and losing counts and system status) every time power is turned off, the CMOS memory is usually provided (as it is in Series One and Series One Plus) with a back-up battery to maintain its content (not system operation) when power fails. Due to the low power drain of CMOS technology, a single new lithium battery can maintain memory without application of power for up to 2 to 5 years. The battery is not used when the power is applied and the system is operating normally. Its storage or shelf life is many years, typically 8 to 20 years. The second memory is PROM(Programmable Read only Memory) that again is fast, relatively low cost, and retentive upon loss of power. However, this memory cannot be easily changed. It can be examined (read) at anytime, but to change (write) it requires some special action on the part of the user. In this system, the PROM must be cleared of all previous contents (new PROM, or erased with an intense ultraviolet light) and then placed into a special loader. A previous logic program developed in CMOS is then written into the PROM. Finally, the PROM is removed from the loader and placed into the CPU.
Function of the Input/Output Circuitry The final element of the PC is the Input/output section. Electrical noise such as spikes on the power lines, inductive “kick-back” from loads, or interference picked up from field wiring is very prevalent in industrial applications. Since the CPU operates at relatively low voltage levels (typically 5 volts), this noise would have serious impact on its operation if allowed to reach the internal circuits of the CPU. The I/O section, both inputs and outputs, protects the CPU from electrical noise entering via the I/O modules or wiring. The I/O section is where status signals are filtered to remove noise, voltage levels are validated, and where decisions made by the CPU are put into operation. Inputs provide their status to a storage area within the CPU and outputs are driven from similar stored status in the CPU. In general, the I/O section is modular in design and can accommodate a variety of signals. A complete discussion of the types and capacities available for both the Series One and Series One Plus PCs is provided in Chapter 6. The specific type of module (e.g. 115 V ac or 24 V dc) is usually determined by the field device the user selects. Decisions such as number of 115 V ac solenoids, 24 V dc solenoids, motor starters, limit switches (their voltages), control panel lamps (what voltage), pushbuttons, and external relays have a major impact on the configuration of any PC. These parameters should be established as early as possible in the overall design of the control system. Of course, being a flexible device, the PC configuration either on paper or in hardware, can be changed if rtQuireirements change. Typically, the user provides the field devices, wires them to the I/O section, and provides the power source to operate them. UL Listed Products Several Series One family products are available that have been tested and approved by the Underwriters Laboratory (UL). These UL listed products should be used in installations where UL listed products are required. The UL listed products include the Series One CPU (IC61OCPU101, revision C), 5-slot
Page 28
18-
Series One/Series One Plus PC Iutroduction GE&90842 rack (IC610CHSlll), 115 V ac Input module (IC61OMDL135), Relay Output module (IC61OMDLl81), and a 115 V ac Output module (IC61OMDLl85). Specifications and wiring information for the UL listed modules can be found in chapter 6 of this manual. When installing a system requiring UL approval, do not mix non UL listed products with the UL listed products.
Communicating With Other Devices An available Data Communications Unit (DCU) allows the Series One and Series One Plus to communicate with external devices. The Series One PC uses the IC61OCCMlOO DCU, while the Series One Model E, Series One Plus and Series One Plus 3.7K PCs use the IC61OCCM.105 DCU. These devices can be other programmable controllers, computers, or other smart devices. User programs and I/O information in a Series One or Series One Plus PC can be uploaded and downloaded to or from any master device that supports the Series Six CCM2 protocol as defined in the Series Six Data Communications Manual, GEK-25364. For detailed information on how to use a DCU in a Series One or Series One Plus PC system, refer to the Series One Data Communications Manual, GEK-90477.
Remote I/O for Series One and Series One Plus Another option available for a Series One or Series One Plus PC system is Remote I/O. By using Remote I/O, I/O modules can be located in a rack convenient to the input sensors or the&output devices being controlled by the PC at a distance of up to .6 miles (1 km) from the PC. This is accomplished by installing a Link Local module in the CPU rack, a Link Remote module in the distant I/O rack and connecting them through a single twisted-pair cable. For detailed information on using Remote I/O in a Series One or Series One Plus PC system, refer to the Series One Remote I/O Manual, GEK-90507.
PC Terminology To summarize the preceding discussion of Programmable Controller concepts, table 1-2 provides a definition of terms discussed above that you should be familiar with, relating to PCs. A more complete list of terms is provided in a glossary at the end of this manual.
Table l-2. Common PC Terminology TERM PC
Programmer Logic
CPU Memory
DEFINTTION Programma&kController or Rogrammable Logic Controller. An indudal control device using microprocessor technology to perform logic decision maEng with r&y ladder diagram based programming* *A device for entry, examdtion and alteration of the PC’s memory including logic and storage ~RXS. A fixed set of respond (outputs) to various external conditions (inputs). All possible situations for both syncbr~nous and non-synchronous activity must be sped% by the user. Also r&d to as the pTo8T8m* Central Processor Unit - the physical unit in which the PC’s intelligence ~lesides. Decision making is performMi heI& A physical place to stow information such as programs and/or data.
Page 29
Series One/Series One Plus PC Introduction
\
19m
GEE90842
Table l-2. Common PC Terminology - Continued TERM
K word CMOS PROM I/O Noise Inau@ outputs Modules Field
Devices
DEFINITION An abbreviation for kilo or exactly 1024 in the world of computers. Usually r&ted to 1024 words of memory. A measurement of memory usually 16, 8, or 4 bits long. A read/write memory that requires a battery to retain content upon loss of power. A read only memory that requires a special method of loading, but is inherently retentive upon power loss. Input/Output - that portion of the PC to which field devices are connected. Isolates the CPU from electrical noise. Undesirable electrical disturbances to normal signals genefly of high frequency content. A signal, typically ON or OFF, that provides information to the PC. A signal typically ON or OFF, that originates h-am the PC with user supplied power that controls earnal devices based upon commands from the CPU. A replaceable electronic subassembly usually plugged in and secured in place but easily removable in case of fault or system redesign User supplied &vices typically providing information to the PC (Inputs: pushbutton, limit switches, day contacts etc.) or performing PC tasks (Outputs: motor starters, solenoids, indicator lights, etc.).