Page 31

Chapter

2

Physical Equipment Configuration

21 m

.

.c

GEK-90842

Rack Description The Series One and Series One Plus PCs are provided as a family of racks into which modules can be inserted. Each rack contains a power supply to the right and space for up to either 5 or 10 modules (see figure 2-1). Racks are available in 6 versions, 5 or lo-slot that accept 115/230 V ac input power, 5 or lO-slot that accept 24 V dc, a UL listed 5-slot rack, IC61OCHSlll which accepts only a 115 V ac power source, and a low-cost 5-slot rack (IC6lOCHSlOl) that does not include an expansion part, 24 V dc tetials for external use, or a RUN relay. Each supplies internal power to the modules inserted into the rack. Mounting is provided by the brackets each with two keyholes at the rear of the rack. All racks are similar. The differences being the function of the rack as determined by the placement of modules by the user, the number of modules which may be inserted into a rack, and the input power required. Figure 2-2 illustrates typical modules for the Series One Family of PCs, illustrating in hardware, the block diagram concept of figure l-l. a40535

Figure 24. Typical Rack Module Location in Rack The CPU module is always placed adjacent to the power supply in the first ra& it contains the microprocessor and required memory storage. There is a connector on the CPU to which the programmer is attached when mounted on the rack. As an option, between the CPU and programmer a 5 foot (1.5m) cable can be installed for more flexible operation. The remaining slots can contain I/O modules in any mix of inputs versus outputs or voltage levels desired by the user for his particular application. Ail modules as well as the programmer are secured to the rack by two snap-locks which can be released by squeezing the module top and bottom toward the center (see Chapter 3 fo+ additional installation details).

Page 32

22m

Physical Equipment Configuration GE&90842 a40019

Figure 2-2. Typical Hardware Heat Dissipation The rack is designed to dissipate internal heat through convection cooling only and does not require a fan for forced air cooling. However, to ensure efficient operation, free air flow should not be inhibited at the top and bottom of the unit. A minimum of 3 inches (75mm) is recommended at the top and 4 inches (1OOmm) at the bottom with 6 inches (15Omm) between racks. Both sides should be free of obstacles to allow easy removal of the unit, approximately 3 inches (75 mm) from each side excluding the mounting brackets is recommended. Furthermore, the unit should be mounted horizontally as shown in figure 2-3 and not inverted nor rotated 90’. If not oriented as shown, derating of the maximum ambient temprature specification would need to be considered. Placements of other sources of large volumes of heat near the units should also be avoided, especially directly below the rack. For reliable operation, the air entering the bottom of the rack should not be at a higher temperature than 60°C (140”. Wiring to the

I/O modules and the power supplies should be placed so as to avoid blocking the air flow, yet provide a suitable service loop to allow easy removal of modules with wiring attached. Wires should be tied to maintain their order in the event they must be disconnected during module replacement. Adding Racks If more ?/O points a~ required than one rack can contain, additional racks can be installed similar to the first unit previously discussed (IC61OCHS101 cannot be used as an expansion rack). At the left of each rack are two connectors used to connect to additional I/O. An 18 inch (46Omm) cable is available to connect the rack containing the CPU module to the first I/O expansion rack. The ends of this cable are marked “CPU” and “EXP” (Expander). The CPU end is plugged into the bottom connector at the first rack and the EXP end similarly connected to the second rack using the top connector (see figure 2-S). If a third rack is used, another cable links the second rack to the third rack, the CPU end is inserted into the bottom conneztor on the second rack and the EXP end into the top connector on the last rack. Within these added racks, I/0 modules can be inserted in any order desired, up to five modules in a S-slot rack and up to 10 modules in a lo-slot rack. No additional CPU modules can be installed, nor are reckred. .\

Page 33

23-

Physical Equipment Configuration GE&90842 a4001 8

Figure 2-3. Typical (5 Slot) Rack lo-Slot Rack The 100slot rack provides in a single housing, as shown in figure 2-4, the same number of I/O module slots as two 5-slot racks. An added advantage of the lO-slot rack is easier and less expensive installation since fewer racks have to be mounted and wired. A system can be configured in many ways to contain Refer to Appendix B, which contains examples of valid I/O rack various quantities of I/O. configurations.

Rack Mount Brackets Rack mount brackets (IC610CHS191) are available to adapt the lo-slot racks for mounting in 19 inch racks. With the brackets assembled on either version of a lo-slot rack, the rack can be mounted on standard mounting rails in 19 inch cabinets and consoles. a40792

Figure 24. Typical (10 Slot) Rack

Page 34

24m

Physical Equipment Configuration GEK90842

83-pc-3Sm m-4-1 -3 1a

Figure 24. Expander Cable Installation

Programmer Tape Port The hand-held programmer, when installed on the CPU module, provides an auxiliary tape port for memory transfers to peripheral devices. Tape recordings of user programs can be made on virtually any audio cassette recorder and once made can be used to initialize any CPU to that program. Thus programs can be made once and transported to other CPUs without manually being reentered. Of course, once entered they can be edited if additional tailoring is required. In the unlikely event that a

CPU fails, a replacement can be installed and quickly reloaded to perform specifically the task its predecessor was accomplishing, if a tape record was made. The tame recorder functions are discussed in detail in Chapter 4, PC Operation. A

Programmer Mount Assembly A Programmer Mount Assembly (IC610PRG190) is available that can be used to mount and protect the hand-held programmer on the outside of a panel or console. A hand-held programmer, when mounted externally, can be used as an operator interface unit to change timer or counter presets, monitor timer or counter current values, monitor 16 consecutive I/O points, monitor the entire contents of the user program, and, with a Series One Plus PC, monitor register contents. The programmer mount assembly includes a mounting bezel, a clear plastic cover, and a cable fastener. In addition to the mounting assembly, a shielded, round CPU/Programmer cable (Catalog No. IC61OCBLl02), designed specifically for mounting the hand-held programmer away from the CPU rack must be ordezed separately for use when installing the hand-held programmer in this manner.

The Programmer Mount Assembly bezel installs on the outside of a panel or console with only four screws. The hand-held programmer snaps into the bezel using its two snap-locks. A clear plastic cover then fits over the bezel and programmer, thereby protecting it &om its industrial environment. The Programmer Mount Assembly can also be used as a table top stand for the hand-held programmer by

Page 35

250

Physical Equipment Configuration GEK90842 mounting four rubber feet, which are included with the assembly, on the reverse side of the bezel using the panel mounting holes. a401 48 l WHENUSEDASABENW-TYPE l WHENMOWTEDONARSEL

Figure 2-6. Programmer Mount Assembly Table 2-1 lists the Series One/Series One Plus PC catalog numbers and nomenclature for the various For detailed information on I/O module specifications modules, cables, peripherals, and accessories. and wiring diagrams, see Chapter 6.

Table 2-l. Series One/Series

I

One Plus Catalog Numbers

DESCRIPTION

CPU, Series One (700 wonls of CMOS Memory, standad) Version C is UL listed CPU, Series One Model E (Enhanced Version of CPUlOl) CPU, Series One Plus (700 words of CMOS Memory, std) CPU, Series One Plus 3.7K (3700 wads of CMOS Memory) I/O Expander Cable Programmer with Keylock Programmer w/Keybck (Required for Series One Plus) CPU to Programmer Cable, 5’ (1Sm)

CATALOG

NUMBER

1C61OCPu101 IC61OCPU104 IC61OCPU105 IC61OCPU106 IC61OCBLlOl IC61OPRG100 IC61OPRGlOS IC61OCBLlOO

Page 36

26(I

Physical Equipment Configuration GE&90842

Table 2-l. Series One/Series One Plus Catalog Numbers - Continued CATALOG

DESCRIPTION Rack, 115/230 V ac Power Source, 5-&t Rack, 115/230 V ac Power Source, S-slot (no expansion, 24 V dc Tee,

NUMBER

IC61OCHSllO or Run Relay)

Rack 115 V ac Power Source, 5-slot, UL listed

IC61OCHSlOl IC61OCHSlll

Rack w/24 V dc Power Source, S-slot

IC61OCHS114

Rack, 115/230 V ac Power Source, lO_slot

IC61OCHS130

Rack, w24 V dc Power Source, l&slot

IC61OCHS134

Kller Module 24 V dc Sink Input, 8 circuits

IC61OMDLlOO IC61OMDLlOl

14 V dc Input/Output, 4 Inputs/4Outputs

IC61OMDL103 IC61OMDL104

Z4 V dc Sink Input/Relay Output, 4 Inputs/4 Outputs humbwheel Interface Z4 V dc Sink Input, 16 Circuits w/LEDs L/OInterface Cable 10’ (3m) 24VdcSinkLoadI~put,16Circuits 14 V ac/dc SoInput, 8 Circuits 14 V ac/dc Source Input, 16 circuits 115 V ac Input, 8 Circuits 115 V ac Isolated Input, 4 Chuits 230 V ac Input, 8 circuits 115 V ac Input, 6 Circuits (UL listed)

IC61OMDL105 IC61OMDL106 IC61OCBL105 IC61OMDL107 IC61OMDLlll IC61OMDL112 IC61OMDL125 IC61OMDL126 IC61OMDL127

14VdcSinkOutput,8Circuits 24 V dc 2 Amp Sink Output, 4 Circuits 24 V dc 2 Amp Si&hurce Output, 4 Circuits

IC61OMDL135 IC6lOMDL151 IC61OMDL153 IC61OMDL154

24VdcSourceOutput,8C!ircuits 24VdcSinkOutput,16CircuitswjLEDs 24 V dc Sink Output, 16 Cixuits 24 V dc Source Output, 16 Cinxxits 115/230 V ac Output, 8 Circuits 115/230 V ac Isolated Output, 4 Circuits

IC61OMDL155 IC61OMDL156 IC61OMDL157 IC61OMDL158 IC61OMDL175 IC61OMDL176

Relay Output, 8 Chuits Relay Output, 5 Circuits (‘UL listed) Relay Output, 16 Circuits 115 V ac Output, 6 Circuits (UL listed) Hi@ Speed Counter I/O Interthe Cable (High Speed Counter)

IC61OMDL180 IC6lOMDLl85 IC61OMDL182 IC61OMDL181 IC61OMDLllO IC61OCBL107

Fast Response &/O I/O Simulator, 8 Inputs printer Interface Unit PROM Writer Unit Accessory Kit Lithium Battery

IC61OMDLl15 IC61OMDL124 IC61OPER151 IC6lOPER154 IC61OACC120 IC61OACCl50

PROM Memory (4 Chips), Series One, Series One Junior CMOS Memory (4 Chips), Series One PROM Memory (4 Chips), Sties One Plus CMOS Memory (4 Chips), Series One Plus Rack Mount Brackets Programmer Mount Assembly

IC61OACC151 IC61OACC152 IC61OACC155 IC61OACC156 IC61OCHS191 IC61OPRG190

Page 37

27I

Physical Equipment Configuration GEK-90842

Table 2-l. Series One/Series One Plus Catalog Numbers - Continued

I

DESCRIPTION

CATALOG

Remote CPU/Programmer Cable Data Communications Unit I/o Link Local I/O Link Remote

NUiiiiii~

IC61OCBL102 1C61OCCM105 IC61OCCMllO IC61OCCMlll

Hardware Requirements The Series One and Series One Plus PCs are an excellent relay and timer/counter replacer or substitute for other sequential type control devices, such as drum or stepping switch based systems. However, one question always arises - how much hardware do I need to buy ? The answer varies extensively based upon different applications and their attendant complexities. Areas of concern include amount of memory, mix of inputs versus outputs, voltages of I/O, and physical size of the Series One or Series One Plus PC system. The following steps are guides to estimate the requirements of the Series One or Series One Plus PC system. With a little experience, estimating required components will become second nature. If you require assistance, please contact your local GE Fanuc Automation distributor who handles the Series One Family of PCs. NOTE CPU Module IC61OCPUlOlA is different from 1OlB and 1OlC in that 1OlA has a 3 digit preset for Timers and Counters, while the updated modules, 1OlB and 1OlC have a 4 digit preset. The 1OlA method of monitoring the accumulated value of Timers and Counters is also different. With the 1OlA module, each individual Timer or Counter must be accessed by using the sequence SHF, 6X, MON for each Timer/Counter to be monitored. With the 1OlB or the 1OlC CPU module, the keys NXT or PRV will move the monitor display to the next or previous Timer or Counter.

System Estimating The Series One and Series One Plus PCs are provided with 700 words of CMOS memory as a standard feature. Expansion to 1724 words is possible by adding a CMOS memory chip. If the unit is to be PROM based, the program can be up to 1724 words. The Series One Plus 3.7K PC provides the user with 3700 words of CMOS memory as a standard feature. For average complexity relay replacement, 700 words should be adequate for up to 64 I/O, and the 1724 should be adequate for up to 168 I/O. If the logic is conside& more complex than that used as examples in this manual, a representative sample (10 to 15%) of the logic should be programmed. From the amount of memory (on paper) the sample requires, the total memory requirements can be estimated. If in doubt, obtain the optional memory with your unit to ensure simple system design. The key to many of the answers (cost, physical size, memory requirements, etc.) is the I/O structure. If a design exists such as shown in figure 2-7, assume that all the relays and timers are enclosed within a box; these are the elements to be replaced. This figure is for illustrative purposes only; no indication is given that it performs any real functions. Passing through this box are wires tirn switches, auxiliary contacts, overload relays, etc.; these are inputs to the control system. There are wires connecting to loads or actuating devices such as solenoid valves, motor starters, indicator lights, etc.; these are outputs

Page 38

280

Physical Equipment Configuration GEK-90842 from the control system. The power lines (e.g., 115 V ac and 24 V dc) are not considered important to estimating the number of I/O modules required. Use the following steps to estimate rack and module quirements;

I/O, but are figure 2-7 is used as an example:

1 . Add total number of inputs and outputs separating them by type and voltage. (5) 24 V dc inputs plus (3) 115 V ac and (1) 24 V dc output).

(e.g. (4) 115 V ac and

2 . Divide each separate category by 8 (assume 8 circuit modules), (e.g. (1) 115 V ac and (1) 24 V dc input modules and (1) 115 V ac and (1) 24 V dc output modules). See Chapter 6 for I/O that uses 4 or 16 circuits per module. 3 . Add total I/O modules (e.g. 4 I/O modules). One 5-slot rack is required for l-4 I/O modules, two 5-slot racks for 5-9, and three 5-slot racks for 10-14. 4 . If lo-slot racks are used one lo-slot rack is required for 1-9 I/O modules, lo-slot and a 5-slot rack will contain 1-14 I/O modules. 5.

wo lo-slot racks or a

Each additional rack also requires an I/O expander cable. Empty slots should be covered by blank filler plates.

6 . Estimate memory requirements Total I/O Points l-64 65-168 as follows:

Estimated Memory Basic Unit with 700 words Add 1K Memory Chip

7 . The following optional hardware is available and should be considered Had-Held Programmer Portable Programmer Extender Cable Programmer Mount Assembly when configuring a system:

PROM Writer Unit Printer Interface Unit Thumbwheel Illunit Timer/Counter Setpoint Unit (Series One Plus)

If the system has not yet been designed, the same basic technique can be used. Inputs are signals the PC will require to perform its assigned functions. Any device or person regardless of intelligence can not respond to events it does not know occurred. Plan to provide the PC all the information you would require to perform the same function. Make a list of those inputs, including source and voltage level (if currently defined). Outputs, on the other hand, are devices the PC will use to perform its fimctions. Again, even if the PC knows it must do something, if it is not given control over these actuating devices, it can not maintain proper control. Make a list of these devices including their voltage levels and current/power requirements. Use the above steps with the list of l/O devices. In any case, when

Page 39

290

Physical Equipment Configuration GEL90842 estimating system requirements, review the following define their impact on your control needs:

standard features as discussed in later chapters to

Up to 64 Timers and Counters (4 digits each) 128 Stage Shift Register Up to 64 Sequencers Each With Up to 1000 Steps 28 Latched Relays Data Operations (Series One Plus and Series One 3.7K) 64 Sixteen Bit Data Registers (Series One Plus and Series One 3.7K) - Up to 124 Data Registers are possible when unused T/C references are used as Data Registers.

a421 53

Figure 2-7. Example of Relay Control

Peripheral Devices Supporting Series One Family of PCs Several peripheral units are available to support a Series One or Series One Plus Programmable Controller. A basic description of these units is provided in the following paragraphs. For a more detailed description of the use and operation of these units, refer to Chapter 4, Operation, in this manual.

Page 40

2-10

Physical Equipment Configuration GEK-90842

Data Communications Unit The Data Communications Unit (DCU), 1C610CCM100/105, provides the ability for external devices to communicate with the Series One, Series One Model E, Series One Plus or Series One Plus 3.7K PC. Series One Model E, Series One Plus and Series One Plus 3.7K PCs require the CCM105 DCU. These devices function as a host to the Series One or One Plus PC and can be other programmable controllers, computers, or other smart devices. User programs and I/O information in the Series One or One Plus PC can be uploaded and downloaded to or from any master device that supports the Series Six CCM2 (Communications Control Module, Version 2) master/slave protocol as defined in GEK-25364, which is the Series Six Data Communications Manual. The Series One or Series One Plus can only function as a slave device during a communications session. a40537

Figure 2-8. Data Communications Unit

Page 41

241

Physical Equipment Configuration GE&90842

Printer Interface Unit The Printer Interface Unit, IC61OPER151, is a compact, easy to use device that attaches to the Series One, One E, One Plus or One Plus 3.7K PC in the same manner as the programmer. This peripheral interfaces to many readily available personal computer printers and provides a means of obtaining a hard-copy printout of the user program in either boolean or ladder diagram format. Version B works with Series One, One E and One Plus PCs. A higher revision will be available that will also work with the Plus 3.7K PC. a40538

Figure 2-9. Printer Interface Unit

Page 42

2-12

Physical Equipment Configuration GEK-90842

PROM Writer Unit Also available is a PROM Writer unit, IC61OPER154, which allows the user program in CMOS memory to be transferred to PROM memory, thereby providing a convenient method of non-volatile (permanent) storage for those programs. The PROM Writer unit is a compact, easy to use unit which attaches directly to the PC in the same manner as the programmer. In addition to providing a means of non-volatile storage, an added advantage of PROM memory is that several PROMS can be programmed, each containing a different program, for use as required. Version B of this unit replaces version A and can be used with a Series One Plus PC as well as Series One and Series One Junior PCs. Version B will not work with the Series One Plus 3.7K PC. A revisedversion will be available that can be used for all Series One Family PCs.

a40539

Figure 2-10. Prom Writer Unit PROGRAMMABLE CONTROLLER series One/OneE series OIX!Plus/3.7K

PROM 2732A-2

27256-25