Page 11
SECTION 2 SYSTEM CONFIGURATION A typical programmable controller is divided into three components as shown in Figure 2-1. These components are the controller, the input/output modules, and a programming device. The programming device is the interface between the user and the programmable controller. The user program, located in the controller’s memory, is entered using the programming device. PROGRAMMABLE PROGRAMMING
CONTROLLER
CONTROLLER
INPUT /OUTPUT
DEVICE
MODULES
1
I
OPERATOR - i”
USER CONTROL DEVICES
INPUT
PROCESSOR
OUTPUT
ISER YIRING
Figure 2-1. Programmable Controller, System Basic Block Diagram 2.1
CONTROLLER The controller of the MICRO 84 system contains the processor, user memory, and the power supply.
2.1.1
Processor The processor, the “brain” of the system, is a microprocessor-based system designed to replace relays, counters, timers, and sequencers. The main purpose of the processor is to use the user program and continuously monitor the status of all input signals from the control devices and to change the output signal to a device, if required. The processor can also perform arithmetic computations (addition and subtraction).
2.1.2
User Memory A portion of the processor is designated for use by the user’s logic program. it is in this area that the relay ladder diagram logic is stored. Once the ladder diagram program is entered into memory, it remains there until deliberately changed by the user. The program is not altered by power failure or power off conditions. The P370 Programming Panel is attached, through a cable, to a connector on the controller housing. This allows entry of instructions and data and also permits previously entered information to be monitored and changed.
2.1.3
Power Supply The Micro 84 can include either an AC or DC power supply. The options are listed below by controller part number: M84A with AC Power Supply AS-M84A-001 or -002 M84A with DC Power Supply AS-M84A-101 or -102 The AC power supply operates on 115 VAC, or 220 VAC, 50160 Hz. The appropriate voltage is jumper selectable (see Section 3). The DC power supply operates on 24 VDC. No adjustment or maintenance of the power supply is required. A lamp indicates power-ready status. No external cooling is required; however, free air circulation must be provided. The power supply has sufficient capacity to operate the P370 Programming Panel, the input/output modules, and the processor. 2-l
Page 12
2.2
INPUT/OUTPUT (l/O) MODULES A MICRO 84 Programmable Controller can communicate with up to 112 input and output points. l/O modules are either input or output and are discrete, register or analog. Each module can be connected to eight l/O points. The controller can handle a maximum of fourteen l/O modules. (See the configuration rules listed below for basic and expanded systems.) The input modules contain the circuitry required to convert incoming voltages to signal levels compatible with the processor. The output modules contain the circuitry required to convert processor signal levels to levels compatible with the devices being controlled. All input and output module circuits are optically isolated from the internal controller circuitry and therefore can withstand severe voltage transients without damage to the controller.
2.2.1
Module Characteristics The simplicity of interlocking the I/O modules together represents a major savings in time for both the assembly and programming of the system when compared to competitive systems. A wide variety of l/O modules are offered. Each is designed to be an output driving or an input handling circuit. The controller and l/O units are designed to operate in an industrial environment; they operate in locations where electromagnetic noise, high temperature, humidity, corrosive elements, and mechanical shock are prevalent.
2.2.2
Module Addressing The terminal connections on the front of the l/O modules are associated with both an address in the processor (the reference number) and a specific piece of user equipment. To communicate, the processor selects the module address needed during operation. The proper addressing order is accomplished internally by the processor according to the module type and its physical location. The closer to the processor, the lower the module circuit address. This allows the installation of additional modules without repositioning the existing modules.
2.2.3 l/O Configuration Rules Before configuring the l/O module portion of your Micro 84 PC system, refer to the serial number of the PC. If the PC serial number ends with “A”, it is an expanded system. Follow the configuration rules in Section 2.2.3.2. If the PC serial number does not have an “A” suffix, it is a basic system. For basic systems, follow the configuration rules in Section 2.2.3.1. Contact your distributor or local sales office for information on upgrades.
2.2.3.1 l/O Configuration Rules - Basic System A Micro 84 Basic System has either 13 mixed l/O modules or 8 discrete l/O modules. The 13 mixed modules can be discrete, register, and analog modules, according to the following limitations.
a)
A maximum of four 8370 BCD Register Output or B374 4-20mA Analog Output Modules may be installed on one system.
b)
A maximum of one 8371 BCD Register Input, one B373 0-1OVDC Analog Input, or one B375 4-20mA Analog Input Module may be installed on .a system.
2-2
Page 13
cl J
2.2.3.2
A maximum of 4 discrete input and 4 discrete output modules may be installed in one system.
l/O Configuration Rules - Expanded System A Micro 84 Expanded System supports up to fourteen 300 Series l/O Modules, subject to the following configuration rules. a)
The maximum number of discrete inputs and outputs combined cannot exceed 112.
b)
A maximum of 14 discrete modules may be installed in one system. A maximum of eight discrete input or eight discrete output modules is allowed.
c)
A maximum of 2 analog or register input modules may be installed on one system.
d)
A maximum of 4 analog or register output modules may be installed on one system.
e)
Analog or register modules must be physically mounted to the right of all discrete modules (see Figure 2.2).
11(673
26.5 in. mm) 1 -
- r
-
-
J
-1
2
3.14 I
8
7
5 I
,
Discrete l/O Modules
9 1 10
11
I’)
IL 1 13 1 14
I
I
I
Discrete (Expanded System Only) Analog or Register l/O Modules
Figure 2-2. Expanded System Configuration Diagram Surge withstand specifications for a configuration with more than 8 modules of any type is 1000 VRMS. If a system has 8 or less modules which are mixed discrete and register, the surge withstand rating is 1500 VRMS. Systems having a configuration with 8 or less discrete modules have a surge withstand rating of 2500 VRMS (IEEE 472-1974, ANSI C37.90a). NOTE When recording and then reloading a program into the same controller, remove the P371 Program Pack and then reinsert it before loading the program. This procedure prevents the occurence of false error conditions.
2-3
Page 14
2.3
PROGRAMMING
DEVICES The principal peripheral devices which allow the user to interface with the MICRO 84 Programmable Controller are the P370 Programming Panel and the P371 MICRO 84 Program Pack.
2.3.1
P370 Programming Panel The P370 Programming Panel incorporates a function keypad and a liquid crystal display (LCD) in a rugged, compact case. This facilitates hand-held operation at the controller site. The programming panel connects to the MICRO 84 Controller and provides a simple method of programming the user memory from a ladder diagram. The “language” used to program the controller utilizes familiar relay symbols; there is no requirement to learn a programming language. In addition, the LCD readout allows rapid and easy system checkout and maintenance. See Section 6.
2.3.2
P371 Program Pack The program pack incorporates a memory identical to the user’s portion of the controller memory. Once a program is loaded into user memory, a copy of that program can be loaded into the program pack for storage. The program in user memory is left intact. Once the program pack is loaded with a program, that program can be reloaded into the same MICRO 84 or another one that is to perform the same functions. Loading a program into the program pack is controlled using the P370 Programming Panel. Loading a program into a MICRO 84 is controlled from the programming pack. See Section 8. NOTE When recording and then reloading a program into the same controller, remove the P371 Program Pack and then reinsert it before loading the program. This procedure prevents the occurence of false error conditions.
2-4
Page 15
SECTION 3 SYSTEM INSTALLATION
The MICRO 84 Programmable Controller mainframe is easily installed in a standard 8” deep NEMA rack. Figure 3-1 illustrates a typical system layout, providing mounting dimensions of all major components. Figure 3-2 provides mounting hole dimensions. For proper heat flow, all units should be mounted vertically. This allows natural air flow and removal of heat by way of the heavy duty housing fins. For Class I operating environments where air tight explosion-proof enclosures are employed, a minimum of six inches is necessary for heat dissipation between the top, bottom, sides, and front of the MICRO 84 and the enclosure.
MICRO-84
MAINFRAME i
7=’ PROGRAMMER
Figure 3-1. Typical System Installation
3-1
Page 16
NOTES:
MAINFRAME If |. MTG HOLES 10-32 UNF OUTLINE: OUTLINE (INSERT OR TAPPED) 2. SEE MODICON DRW. SK-M844-000 FOR SYSTEM CONFIGURATION
[ + + + + + + + + reo i i a a an i: aia aa
713.0) I | | | | | [O.150] 4 | i l e_ - - ee, 1__} CS P _t a 7 7 7 . + - + eat | . | $9.60 aeasrpe 4:28, 288.93 B x rm [2.000] fi.¢2s) (i\.375)
Figure 3-2. MICRO 84 Mounting Dimensions
3.1 SYSTEM REQUIREMENTS
Each MICRO 84 Programmable Controller requires an M84A mainframe unit (controller) containing the processor, user memory, and power supply, a combination of up to fourteen input and output modules for user equipment connections, and a P370 Programmer to allow communication between the user and the system. The MICRO 84 is available with one of two memory sizes. The memory size determines the number of networks that can be programmed into the controller (see Table 3-1).
Table 3-1. System Memory Sizes
MODEL 1/0 MODULES* NETWORKS M84A-001 (1K) 8 (basic system) 9 M84A-002 (2K) 14 (expanded system) 18 *Each module can be connected by a maximum of 8 input or output points.
3.2. SYSTEM SPECIFICATIONS Table 3-2 contains the specification for the various components of the MICRO 84 Programmable Controller system:
Page 17
Dimensions (WxHxD): Mainframe (w/Power Supply) Single l/O Module P370 Programming Panel Program Pack Weight: Mainframe (w/Power Supply) Single l/O Module, output Single l/O Module, input Programming Panel Program Pack
3.75 in. X 11.50 in. X 5.875 in. (95.25mm X 299.lOmm X 149.23mm) 1.625 in. X 11.50 in. X 5.875 in. (53.95mm X 292.lOmm X 149.23mm) 10.00 in. X 6.50 in. X 1.75 in. (254.00mm X 165.lOmm X 44.75mm) 2.88 in. X 1.50 in. X 5.00 in. (73.15mm X 38.lOmm X 127.00mm) 5 Ibs., 6 oz. (2.44 kg) 1 lb., 13 oz. (0.82 kg) 1 lb. (0.45 kg) 1 lb., 10 oz. (0.74 kg) 8 oz. (0.23 kg)
Power Requirements, AC: Voltage Range
115 or 220 VAC, f 15% 47 to 63 Hz, 50 watts max. NOTE: The 220 VAC option requires the removal of a jumper on the external power terminals.
Power Requirements, DC: Voltage Range Polarity Reversal
Current Draw Fuse Environmental Requirements: Ambient (Room) Temperature, mainframe Ambient (Room) Temperature programming panel Relative Humidity Shock Vibration EMI (electromagnetic Interference) Ml (magnetic interference) RFI (radio frequency interference) SWC (surge withstand capability
24 VDC, + 20%, - 15% (20.4 to 28.8 VDC) Polarity reversal to the external power terminals will blow the power supply fuse. No damage will occur to the power supply, controller, or I/O modules. 3A max. .5A operating 5A
O” to 60°C o” to 4o”c 0% to 95% (non-condensing) 10 G for 11 msec. .625 G, 50 to 500 Hz MIL-STD 461 6 HELM HOLTZ Co.1 FCC Class A IEEE 472-1974 & ANSI C37.90A
Table 3-2. MICRO 84 Specifications 3.3
CONTROLLER The MICRO 84 controller (Model M84A) is contained within a rugged metal housing that is designed to screw mount into a standard 8” deep NEMA rack. The controller can also be screw mounted onto a wood mounting panel.
J
Located on the housing front is a five screw terminal strip and two indicating lights. The terminal strip is used to co.nnect external AC power to the MICRO 84 system. The upper indicating light, (POWER), is illuminated when external AC power is applied to the power supply. The lower indicating light, (RUN), is on when the processor is solving the logic networks. Refer to Figure 3-3.
3-3
Page 18
Figure 3-3. MICRO
84 Controller
Located on the bottom of the controller are two female sockets that are used in connecting peripheral (user interface) devices to the controller. The socket closest to the front of the controller is for the P370 Programmer and the other is for the P371 Program Pack (see Figure 3-4).
PROGRAM PACK / CONNECTOR
/
Figure 3-4. Bottom
3-4 of MICRO
P370 PROGRAMMER CONNECTOR 84 Controller
Page 19
A female socket is located on the right side of the controller housing. This socket is the link between the controller unit and the input/output and register modules. A terminator plug, supplied with the controller, must be inserted into the rightmost I/O module during system operation. Programs can be generated in the MICRO-84 without any I/O modules as long as the terminator plug is inserted into this socket. 3.4
INPUT/OUTPUT MODULES The B300 Series modules are contained in rugged plastic housings that can be screw mounted into a standard 8” deep NEMA rack. Located on the housing front are circuit indicating lights that turn on to indicate when a particular circuit is active. Screw terminals connect the MICRO 84 to the user’s equipment. An interconnecting socket is located on each side of the l/O housing. The left side socket allows communication between the l/O module and the controller and the right side socket allows communication between additional I/O modules and the controller. The last I/O module must have the terminator cap, shipped with the controller, inserted in the right side socket. All user control devices that provide input to the MICRO 84 are connected to the screw terminals located on the input modules. All user devices that are controlled by the MICRO 84 are connected to the screw terminals located on the output modules. Refer to Figure 3-5.
J
Figure 3-5. Typical Discrete
3-5 -
I/O Module
Page 20
3.5
COMPONENT MOUNTING The MICRO 84 controller (M84A) unit is secured to the mounting surface using two screws, one top and one bottom. See Figure 3-l. After securing the controller unit, the first input/output module is plugged into the controller using the connector located on the right side of the controller unit. Use the tabs (mating protrusions) on the left side of the module to assure proper alignment of the module with the controller. Each module has upper and lower sliding interlocks. Both should be pulled out before installing and pushed in after the module is properly mated to the adjacent module. Once positioned and secured to the controller, the module can then be fastened to the mounting surface using two mounting screws. Position l/O mounting screws at the rightmost side of the slotted holes so that the modules can slide to the right for easy removal. Refer to Figure 3-8. Additional modules can then be added and fastened in the same way. Care should be exercised not to overtighten the screws used to mount the I/O modules.
UPPER
SLIDE
--MATING
LOCK
(LOCKED
POSITION)-,
POINTS
-ELECTRICAL
-MATING
3.6
POINTS
-
SYSTEM WIRING After properly mounting the MICRO 84 Controller and l/O modules, the external AC power and l/O wiring connections can be made. It is recommended that separate sources of power be used for the controller and l/O modules.
3.6.1
Power Connection The Micro 84 system can operate on AC or DC power. Always check to see which type of power supply is being used before wiring the controller. On AC power supplies, the presence or absence of a jumper between the upper two terminals determines the voltage. Remove the jumper for 220 VAC operation. Refer to Figure 3-7 for the proper wiring connection. On DC power supplies, the top two terminals are not connected. The middle terminal is the ground connection. The bottom two terminals are used to connect the negative (-) and positive (+) DC inputs. Refer to Figure 3-7 for the proper wiring connection.