The text of a manual · part 3 of 13

Micro 84 Programmable Controller User's Manual, pages 21 to 30

Pages 21 to 30 of 124

The original document is the PDF (6.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Gould Micro 84 Controller, Modicon Micro 84 Controller, AEG Micro 84 Controller and Schneider Micro 84 Controller

Page 21

DC Power

AC Power r

NO CONNECTION

VOLT sLcLT

CON:E%TlON GRND

GROUND

AC IN NEUT

-DC

IN

+DC

IN

Figure 3-7. Connection of External Power to MICRO 84 3.6.2 l/O Wiring The l/O module wiring information included in this paragraph is specifically for the B351,115 VAC Input module and the 8350,115 VAC Output Module. Wiring information, and other technical information, for these modules and all other MICRO 84 l/O Modules are contained in Appendix D. A discrete control device is assigned automatically to an internal memory address according to which screw terminal the device is connected. On both the input and the output modules, screw terminals 1 through 8 connect the MICRO 84 to specific user control devices. Input addresses range from 1001 through 1032 (1064 for the M84A-002) while output addresses range from 0001 through 0032 (0064 for the M84A-002). Refer to Figures 38 and 3-9 for the wiring scheme for input and output modules.

J r

OUTPUT

INPUT

1 i

AC Hot [I;

I;C Hot NEUTRAL

NEUTRAL

1

J

-

-11

I

Figure 3-9. Output Module Wiring

Figure 3-8. Input Module Wiring

3-7

Page 22

3.6.3 l/O Module Addressing The proper addressing of the l/O modules is accomplished automatically by the controller. The closer to the controller, the lower the l/O module’s address. This allows for the installation of additional l/O modules without disturbing the existing l/O module/addressing sequence. Refer to Figure 3-10. ‘ROCESSOR

ADDRESSES

IlJTPlJ’

1001

0001

I&

O&

INPUT

INPUT

0 1UTPUT OUTPUT

IO09

OF 0009 TO c PROCESSOR

ADDRESSES

NPUT

PROCESSOR

INPUT

TO 1016 INPUT

0008

0016

XJTPUT INPUT OUTPUT

_I-n-I

ADDRESSES

1001 TO 1008

PROCESSOR

INPUT

ADDRESSES

:I001 TO 1008

1009 TO 1016

O’ooo8

I&

0::

REGISTERREGISTER OUTPUT INPUT OUTPUT

0001 TO 0008

3001 AND 3002

Figure 3-10. I/O Addressing

3-8

_

4010 AND 4012

Page 23

SECTION 4 SYSTEM CHECKOUT 4.1

CONTROLLER OPERATION After securing the MICRO 84 controller using the two mounting screws and ensuring proper external AC power connections are made, AC power can be applied to the controller. When AC power is applied, the controller POWER light illuminates indicating the power supply is fully operational. The-RUN light does not illuminate unless the controller has been started and the terminator plug is in the right-hand connector. The controller is started initially using Supervisory Code 2 which is entered from the P370 Programming Panel. The controller is started also when using the program pack to load a program into the controller. If power is applied (power light on) and the controller is not running, the second push of the program pack pushbutton starts the controller. (See Section 8.) Also, if the controller was running when power was removed, it will be running when power is once again reapplied. Once started, the processor’s memory is fully operational. CAUTION During the power up sequence, AC output modules may cause the false triggering of certain loads for one-half cycle. The loads that are most susceptable are: Latching relays Fast-acting solenoids (Hydraulic/pneumatic valves) Latching circuits (Motor starter with seal contact) Special circuit designs have been incorporated into the AC output modules to minimize this false triggering. However, applications using fast reacting or latching devices that initiate mechanical action may be a hazard due to false triggering.

4.1 .l

Power-Up Sequence. During the power up sequence, the processor logic executes a program of diagnostic tests to ensure that all system hardware is functioning properly. If an error is detected during the power-up sequ.ence, the system halts. If the P370 Programmer is connected, an error code is displayed on the panel. If the programmer is not connected, no external indication of the error is available but the error code is stored in a location in the controller memory. When the P370 Programmer is reconnected to the controller, the error code that has been stored will be displayed on the panel. If all tests pass, the following sequence occurs: 1.

All coils are set OFF with the exception of latched coils and coils which were disabled when power was last removed. These coils retain their latched or disabled state.

4-1

Page 24

2.

All inputs are read including input registers.

3.

If the controller has been started, the RUN light on the controller is illuminated and the unit starts solving logic at network 1.

When power is applied to the mainframe, the power supply begins producing DC power. There is a slight delay between the time the DC voltages are within regulation and the processor begins operating. This delay allows sufficient power to be stored to ensure that proper powerdown procedures can be performed by the processor when external power is removed. Upon an indication of power failure, appropriate information is stored to permit an orderly start-up, the RUN light is extinguished, and all outputs turned OFF.

4.1.2

Power-Down Sequence When power is removed, the controller continues to operate using the power stored during the power-up sequence. If power is not restored within l/lOth of a second, the controller executes an orderly power-down sequence. The controller can operate for a longer time depending upon the devices (Programmer, l/O modules, etc.) that are connected to the mainframe at the time of power-down. Prior to actual loss of DC power, a warning signal is provided from the power supply to the processor. This warning signal causes the processor to stop solving logic wherever it is in the scanning process, and to begin the power-down sequence. The power-down sequence is performed to completion even if power is restored. The power-down sequence requires less than 1110th of a second.

During the power-down sequence, the controller calculates and stores a value for the contents of the random access memory. This value is used during power up to verify the content of memory. In addition, all outputs are turned OFF. The status of coils and the contents of registers are retained for use during the power-up. If it is necessary to remove power from the unit, remove power from the controller first. Removing power from the I/O first, or at the same time as the controller, can cause incorrect data to be stored during the power-down sequence (if the controller was running at the time power was removed).

4.2

P370 PROGRAMMER OPERATION Plugging the P370 Programmer into the mainframe supplies power to the programming panel and enables the processor to initiate a diagnostic test of the Programmer circuits. The COMM-OK status display should illuminate. During this sequence, scan time is increased significantly. All liquid crystal display segments turn on allowing the user to visually verify that all the segments are operating (turned on). Refer to Figure 4-1 for an illustration of the P370 displays.

4-2

Page 25

Figure 4-1. P370 Programmer

With All Display Segments

Lit

The display segments remain on for approximately 2.5 seconds and then turn off. After another 2.5 seconds, network 1 is displayed with the cursor at row 1, column 1. If the internal diagnostic tests detect an error between the controller and the programming panel, the error code will be displayed in the DATA area. Refer to Appendix A for an explanation of the error code. When not actively using the P370, it should be removed from the controller and stored in an appropriate environment.

4.3 J

SYSTEM

CHECKOUT AND MAINTENANCE The Disable function (see Section 6) can be used during the checkout maintenance of the control system.

and

In checking out a system, the disable function can be used to verify the proper wiring and operation of all discrete output coils. Each output is displayed on the P370 Programmer and then disabled. The coil can be cycled ON-OFF-ON-OFF, etc., and proper operation of the discrete device observed. It is recommended that the coil be enabled before the next output is tested to prevent unwanted functions from occurring in the control system. During control system maintenance, a particular “real-world” device can be removed from MICRO 84 control by disabling either all the inputs (discrete and register) or the logic coil associated with the device. The device can then be repaired or replaced without affecting MICRO 84 operation. When maintenance is complete, the device can be cycled by toggling it on and off from the P370 Programmer. After a successful checkout, the device can be put back on line by enabling the disabled logic element. The disabled state of a coil or discrete input is retained after the P370 Programming Panel is removed. This provides the ability to use this capability without leaving the programmer connected permanently.

J

4-3

Page 26

This page is a scan with no text; see it in the PDF.

Page 27

SECTION 5 THEORY OF OPERATION

The MICRO 84 system controls user equipment by means of a program stored in the user memory and by communication with the l/O section as illustrated in Figure 5-l.

3

INPUTS

OUTPUTS 3

Figure 5-7. System

5.1

Block Diagram

SCAN The MICRO 84 Programmable Controller solves each network (see Section 7) in their numeric sequence. A network is a group of logic elements that are connected together to perform a specific function (for example, a motor starter control circuit). Network 1 is the first network to be solved, followed by network 2, 3, etc., until all networks are solved. The controller then returns to solve network 1 again. The time it takes from the completion of solving any network on one scan until that network is again solved on the next scan is the “scan time” of the controller.

Within each network, logic elements are solved from the left rail towards the right rail and on a column by column basis. The numeric contents of a register, once updated, can be used by all subsequent logic elements in a network (in the same or next column). All inputs and outputs are updated only at the end of each scan. Scan time varies depending upon the amount and type of logic entered. 5.2

INPUT/OUTPUT (l/O) MODULES The MICRO 84 input/output modules isolate the internal processor from the external user-supplied devices. This isolation prevents electrical noise from affecting processor operation. The processor responds to the condition of an external device (on, off, or numeric value). There are two major groupings of l/O modules: l

Discrete l/O l

Register l/O

5-l

Page 28

52.1

Discrete l/O Modules Each discrete l/O module can be connected to a maximum of 8 discrete devices. A discrete device is one that can be either ON or OFF. Reference Numbers

Processor

Input (Pushbutton switches, Limit switches, etc.)

1001-1032 1001-1064

(M84A-001) (M84A-002)

Output (Lights, motor starters, etc.)

0001-0032 0001-0064

(M84A-001) (M84A-002)

Type of Device

5.2.2

Register Modules Register modules provide the capability of handling numeric values (000-999) within the Micro 84 Programmable Controller. These values are represented either in binary coded decimal (BCD) or as an analog voltage or current. These numeric values can be either received from an external device or sent to an external device. The following list describes the type of register module and its associated reference numbers: Reference Numbers

Processor ~-

Input, (Thumbwheel, Panel meter, Temperature, Pressure, and Flow transducers, etc.)

3001-3004

Both

Output, (Digital

4010, 4012, 4014, 4016

M84A-001

4010, 4012, 4014, 4016, 4018, 4020, 4022, 4024

M84A-002

Type of Device display, Valves, positioning devices, etc.)

5-2

Page 29

SECTION 6 P370 PROGRAMMER The P370 Programmer (Figure 6-1) is the primary interface for the programming and monitoring of the MICRO 84 Programmable Controller. The programmer is a rugged, portable, hand-held unit that contains a function keyboard and a liquid crystal display (LCD). The LCD consists of a 4 (row) X 7 (column) node display and shows the power flow in a network in relay ladder diagram form. When a logic element is programmed into a specific row and column, that location is indicated by a node, or point of light, on the network display. The actual element is not shown. Specific information about an individual logic element (the logic element under the cursor) is displayed in the REFERENCE, DATA, STATUS, and Element Display areas of the LCD.

J

The programmer is connected to the MICRO 84 Programmable Controller, through a cable assembly. It provides a simple method of programming the user’s portion of the memory from a ladder diagram. The “language” used to program the controller utilizes familiar relay symbols; there is no requirement to learn a programming language. In addition, the LCD readout allows rapid and easy system checkout and maintenance. The front of the programmer’s panel is divided into an upper section and a lower section. The upper section consists of the liquid crystal display area and an Element Status light; the lower section consists of the function keyboard and keylock switch. 6.1

J

PROGRAMMER OPERATING MODES The P370 Programmer operational functions may be broken down into four distinct modes: l

EXAMINE Mode (including Hold State)

l

DATA ENTRY Mode l

SUPERVISORY Mode l

ERROR Mode

Each mode has specific effects on the display and keyboard operations.

6-l

Page 30

6.1.1

Examine Mode l l l

Normal monitoring of network power flow and status of any node within the network. Monitoring the value or status of any register or coil (using the REF key) that is not associated with the node located at the cursor position. In the HOLD state, the contents of the Data display are frozen, allowing examination of the reference value.

The programming panel enters the EXAMINE mode automatically after the power up diagnostics have successfully completed. The cursor is positioned at row 1, column 1 of network 1. 6.1.2

Enter Mode In the Enter mode, new information is entered into the programmer for subsequent entry into the controller. This can be new nodes, updating existing node information (reference, element type), register values, etc.

6.1.3

Supervisory Mode The Supervisory mode allows the user to enter and initiate the supervisory commands for the controller’s internal memory.

6.1.4

Error Mode In the event of a programmer or controller error condition (diagnostic error, communication error, or user error in entering data), the programmer automatically enters the error mode and displays the appropriate error code. Depending on the error code present, certain keys will be operational. The RESET key or the SHIFT/RESET keys are used to recover from an error condition (see Appendix A).

6.2

DISPLAY AREA The upper section of the programming panel is the LCD and consists of three display areas: l

Reference Data l

Node and Element l

Status

6-2