Page 71
I/O MODULE
APPENDIX D DATA SHEETS
J
This appendix is included to provide a place in which module data sheets that are packed with each module. There are two types of modules that are available 84; discrete modules and register modules. DISCRETE to store the l/O for use with the MICRO
MODULES A discrete module is used to isolate, convert, and condition discrete signals that pass between the user’s device being controlled and the MICRO 84 Programmable Controller. A discrete signal is one that indicates the on or off condition of the device. A discrete input module converts the voltage level received from a control device (pushbutton, limit switch, etc.) to a voltage level that can be used within the programmable controller. Conversely, an output module converts the output voltage from the programmable controller to a voltage level that can be used to control a user device (motor-starter, solenoid valve, etc.).
REGISTER
J
MODULES A register module is used to isolate, convert, and condition binary-coded decimal (BCD) and analog (voltage or current) signals that pass between the user’s device being controlled and the MICRO 84 Programmable Controller. A BCD signal is a numeric value in the range of O-999. A register input module converts the input signals to numeric values usable by the programmable controller. A register output module converts the numeric output of the programmable controller to signals usable by the user’s device. Standard hardware to encode and decode BCD numbers is commonly available.
D-l
Page 72
Page 73
PI-6350-001 Rev. C
B350-001 I 115 VAC Output Module DATA SHEET I
The B350-001 Output
Module consists of eight independent and isolated
115 VAC output circuits.
FEATURES Eight independent Circuit isolation
Zero-cross of 1500 VAC switching
Field side status Transient
115 VAC outputs indicators protection
Surge withstand capability in compliance with IEEE 472-1974 and ANSI C37.90A Optional Fanning Strip permits module removal without disturbance to field wiring UL listed and CSA certified High 2 Amp current per output
Designed for harsh plant floor environments
GENERAL J
DESCRIPTION
The Gould B350-001, 115 VAC Output Module converts logic signals used within the Micro 84” Programmable Controller into 8 independent 115 VAC outputs. Each output is capable of driving relays, pilot lamps, motor starters, solenoids, or other loads up to 2.0 amperes. The module uses 8 triac switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads. Each output is electrically isolated from the controller by an optical coupler. This enables the module and controller to withstand the severe voltage transients prevalent in an industrial environment. The module employs a zero-cross switching technique. This feature minimizes switching noise, extends the life of the triacs, and improves system reliability. Both IEEE and ANSI standards for surge withstand capability (SWC) tests are fully satisfied.
Ir
The output circuits are divided into two groups of four outputs each. Each group is driven by a separate voltage source. A neon lamp connected to each circuit’s field side displays the ON/OFF status of the output. This lamp indicates the output’s true state. The module is housed in a light weight, durable LEXAN case. A structural “chimney” within the module provides flowthrough convection cooling and protection from moisture build-up. Self-contained mounting brackets eliminate the need for special I/O housings. A termination connector shipped with the Micro 84 mainframe is required when using the module at the extreme right bus location. The module is also compatible with the B351 Input Module without the use of additional components. User connections are made to a standard screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012) which allows quick module replacement without disturbing field wiring. Data bus connections are made with standard interface connectors. These connectors allow the B350 module to be placed in any location in the l/O structure without interference to other module operation.
iii
GOULD Electronics
Page 74
/ r______-_~
56
1
AC
HOT
AC
RETURN
OUTPUT NUMBER
ASSIGNMENT
0001
OUTPUT
I
LIZ
OUTPUT
2 o--+.r+
OUTPUT
3 o--b+
OUTPUT
4
@--2/--I
5
0004
OPTICAL COUPLER
.
TERMINAL NUMBERS ooo5
OUTPUT
0006
OUTFUT
6
0037
OUTPUT
7
0008
OUTFWT
6
Ok o-+--t
IeOK .
CJ
OUTPUT a+’
AC HOT GROUP A (OUTPUFS l-4)
a---@--’
Ii5VAC
AC HOT GROUP 6 LOUTFIJTS 5-6!
B--Q+
115vAC PCWERSJPRY
POWER SUPR’,
AC NEUTRAL
0, -
8350 115 VAC Output Module Terminal Numbering and Connections
6350 115 VAC Output Module Simplified Schematic
SPECIFICATIONS Circuit Characteristics
Load Ratings ON Current:
2.OA (max) per output (lO.OA max for 8 outputs)
Topology:
8 outputs 4 outputs
Surge Current:
50A (max) for 1 cycle
Isolation Voltage:
1500 VAC RMS for 60 sec.
Working
Voltage:
80 to 130V rms 47 to 63 Hz
Response
ON to OFF, 8.3 msec OFF to ON, 8.3 msec
Transient
Voltage:
200V rms (max) for 1 cycle 150V rms (max) for 10 seconds
Surge Withstand Capability:
ON Voltage OFF Current:
Drop:
1.2V at 2A (typical) 2mA (max)
Time:
per module per group
Per IEEE 472-1974 and ANSI C37.90A (2500V decaying in 6 microsec.)
Physical Characteristics Environment: Temperature Humidity Shock Vibration EMI RFI
0 to 60°C (ambient) 0 to 95% (non-condensing) 10 G for 11 msec. .625 G, 50-500 Hz Per MIL-STD 461 B Per FCC Class A
Dimensions:
1.62 in. (41.8 mm) X 6.00 in. (152.4 mm) X 11.00 in. (279.4 mm)
Weight:
2.0 Ibs. (.91 kg)
CAUTION During the power-up sequence, AC output modules may cause the false triggering of certain loads for onehalf cycle. The loads most susceptible are latching relays, fast-acting solenoids, and latching circuits. Special circuit designs have been incorporated to minimize this false triggering. However, applications using fast reacting or latching devices that initiate mechanical action may be a hazard.
1)1
GOULD
Page 75
PI-B351-001
B351-001
The Gould B351-001 input Module consists of eight independent
I
Rev. C
115 VAC Input Module DATA SHEET and isolated
115 VAC input circuits.
ix FEATURES Eight independent Circuit isolation
Field side status Transient
115 VAC inputs of 1500 VAC indicators protection
Surge withstand capability pliance with IEEE 472-1974 C37.90A in comand ANSI
Optional Fanning Strip permits module removal without disturbance to field wiring UL listed and CSA certified Designed for harsh plant floor environments
’
GENERAL
DESCRIPTION
The Gould B351-001, 115 VAC Input Module senses and converts switched input signals into logic voltage levels used by the Micro 84’” Controller. The module allows for up to eight independently sensed inputs. Inputs can be received from push buttons, limit and proximity switches, temperature and pressure switches, as well as other 115V sources. Eight independent threshold switches sense inputs from an external power source.
J
Each input is electrically isolated by an optical coupler. A neon lamp connected to the circuit’s field side displays the ON/OFF status of the input. The lamp indicates the input’s true state. Both IEEE and ANSI standards for surge withstand capability (SWC) tests are fully satisfied. The module is designed to withstand the severe voltage transients prevalent in industrial environments.
The B351 Input Module is housed in a light weight, durable LEXAN case. A structural “chimney” within the module provides flowthrough convection cooling and protection from moisture build-up. Self-contained mounting brackets eliminate the need for special I/O housings. A termination connector shipped with the Micro 84 mainframe is required when using the module at the extreme right bus location. User connections are made to a standard screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012) allowing quick module replacement without disturbing field wiring. Data bus connections are made with standard interface connectors. These connectors allow the B351 Input Module to be placed in any location in the l/O structure without interference to other module operation.
ii+
GOULD Electronics
Page 76
TERMINAL NUMBERS
7.5K
SBS (THRESWXD
SWITCH 1
ASSIGNMENT
INPUT
I
001
INPUT
2
002
INPUT
3
OD3
INPUT
4
004
INPUT
5
005
INPUT
6
006
INPUT
7
007
INPUT
6
006
Al
WTICAL
COUPLER
75K iZ”lRAL
INPUT NUMBER
NOT CONNECTED Fli!ziT NOTCONNECTED NEUTRAL
B351 115 VAC Input Module Terminal Numbering and Connections
8351 115 VAC Input Module Simplified Schematic
SPECIFICATIONS Circuit Characteristics
Electrical Characteristics ON Level:
OFF Level:
80 to 130V rms
Topology:
8 inputs per module
(less than 1000 ohms source impedance)
Isolation Voltage:
1500V rms for 60 sec.
0 to 45V rms (less than 1000 ohms source impedance) 0 to 130V rms (greater than 80K ohms source impedance)
Response
Time:
ON to OFF, 30 ms (max) OFF to ON, 10 ms (max)
Visual Indicators:
One neon lamp per input ON when input is ON
Surge Withstand Capability:
Per IEEE 472-1974 and ANSI C37.90A (2500V decaying in 6 microsec.)
Input Wetting Current:
5mA (typical) @I 80V rms input
Source
1000 ohm (max)
Physical Characteristics
45 to 80V rms
Environment:
Resistance:
Threshold
Voltage:
Max Input Voltage:
130V rms continuous
Frequency:
47 to 63 Hz
Temperature Humidity Shock Vibration EMI RFI
0 to 60°C (ambient) 0 to 95% (non-condensing) 10 G for 11 msec. .625 G, 50-500 Hz Per MIL-STD 461B Per FCC Class A
Dimensions:
1.62 in. (41.8 mm) X 6.00 in. (152.4 mm) X 11.00 in. (279.4 mm)
Weight:
2.0 Ibs. (.91 kg)
NOTES The B351-001 Input Module of additional components.
is compatible with the B350-001 Output
Module
-i without the use
GOULD Electronics
Page 77
PI-8352-001
Rev C
6352-001 I 24 VDC Output Module (True Low) DATA SHEET tin The Gould B352-001, 24 VDC Output output circuits.
Module
(True Low) consists of eight independent and isolated
FEATURES l
Eight independent l
Circuit l
Field side status l
Transient l l of 1500 VDC indicators protection
Surge withstand capability in compliance with IEEE 472-1974 and ANSI C37.90A Optional Fanning Strip permits module removal without disturbance to field wiring l
UL listed and CSA certified l
High 2 amp current l
’ isolation
24 VDC outputs per output
Designed for harsh plant floor environments
GENERAL
DESCRIPTION
The B352-001, 24 VDC Output Module converts logic signals used within the Micro 84’” Programmable Controller into 8 independent 24 VDC outputs. Logic format for the module is “true low”. Each output is capable of driving relays, pilot lamps, motor starters, solenoids, and other loads up to 2.0 amperes. The module uses 8 transistor switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads. Each output is electrically isolated from the controller by an optical coupler. This enables the module and controller to withstand the severe voltage transients prevalent in an industrial environment. Both iEEE and ANSI standards for surge withstand capability (SWC) tests are fully satisfied. J
The output circuits are divided into two groups of four outputs each. Each group is driven by a separate voltage source. An
LED indicator connected to each circuit’s field side displays the ON/OFF status of the output. The LED indicates the output’s true state. The module is housed in a light weight, durable LEXAN@ case. A structural “chimney” within the module provides flowthrough convection cooling and protection from moisture build-up. Self-contained mounting brackets eliminate the need for special l/O housings. A termination connector is shipped with the Micro 84 mainframe to be used when the module is attached at the extreme right bus location. User connections are made to a standard screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012) which allows quick module replacement without disturbing field wiring. Data bus connections are made with standard interface connectors. These connectors allow the B352 Output Module to be placed in any location in the I/O structure without interference to other module operation. ->
GOULD Electronics
Page 78
TYPICAL OUTPUT NUMBER
0001
0002 0003 0004 0005 0006 0007 0006 “DC HOT VOtiAGE SOURCE
B352-001 Output Module Terminal Numbering and Connections
B352-001 Output Module Simplified Schematic
SPECIFICATIONS Circuit Characteristics
Load Ratings ON Current:
2.OA (max) continuous per output (lO.OA max per module)
Surge Current:
5A (max) for 10 msec
Working
Voltage:
18 to 30 VDC
Transient
Voltage:
50 VDC for 10 ms
ON Voltage OFF Current:
Drop:
1.2V at 2A 1mA (max)
Topology:
8 outputs
Isolation Voltage:
1500 VDC (peak) for 10 sec.
Response
ON to OFF, 1 msec OFF to ON, 1 msec
Time:
per module
Visual Indicators:
One LED per input ON when input is ON (low)
Surge Withstand Capability:
Per IEEE 472-1974 and ANSI C37.90A (2500V decaying in 6 microsec.)
Physical
Characteristics
Environment: Temperature Humidity Shock Vibration EMI RFI
0 to 60°C (ambient) 0 to 95% (non-condensing) 10 G for 11 msec. .625 G, 50500 Hz Per MIL-STD 461B Per FCC Class A
Dimensions:
1.62 in. (41.8 mm) X 6.00 in. (152.4 mm) X 11.00 in. (279.4 mm)
Weight:
2.0 Ibs. (.91 kg)
NOTES The B352-001 Output Module of additional components.
is compatible with the B353-001 Input Module without the use m> GOULD Electronics
Page 79
PI-B353-001
Rev C
6353-001 I 24 VDC Input Module (True Low) DATA SHEET J
The Gould B353-001, 24 VDC input Module (True Low) consists circuits.
of eight independent and isolated input
FEATURES Eight independent Circuit isolation
Field side status Transient
24 VDC inputs of 1500 VDC indicators protection
Surge withstand capability in compliance with IEEE 472-1974 and ANSI C37.90A Optional Fanning Strip permits module removal without disturbance to field wiring UL listed and CSA certified Designed for harsh plant floor environments
J
GENERAL
DESCRIPTION
The Gould B353-001, 24 VDC Input Module senses and converts switched input signals into logic voltage levels used by the Micro 84’” Controller. The logic format for the module is “true low”. Inputs can be received from push buttons, limit and proximity switches, temperature and pressure switches, as well as other 24V sources. Eight independent threshold switches sense inputs from an external power source. Each input is electrically isolated by an optical coupler. An LED indicator connected to the circuit’s field side displays the true ON/OFF status of the input. Both IEEE and ANSI standards for surge withstand capability (SWC) tests are fully satisfied. This enables the module and controller to withstand severe voltage transients prevalent in industrial environments. J
The module is housed in a light weight, durable LEXAN@ case. A structural “chimney” within the module provides flowthrough convection cooling and protection from moisture build-up. Self-contained mounting brackets eliminate the need for special I/O housings. A termination connector is shipped with the Micro 84 mainframe to be used when the module is attached at the extreme right bus location. User connections are made to a standard screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012) allowing quick module replacement without disturbing field wiring. Data bus connections are made with standard interface connectors. These connectors allow the B353 Input Module to be placed in any location in the l/O structure without interference to other module operation.
-i.
GOULD Electronics
Page 80
TYPICAL INPUT NUMBER
1001
1002 1003 1004 1005 1006 1007 1006 YOLTACE
SOURCE
NOT CONNECTED DC RETURN (INPUTS I-81 u
B353-001 Input Module Simplified Schematic
Terminal
B353-001 Input Module Numbering and Connections
SPECIFICATIONS Electrical
Characteristics Less than 30% of V source
Circuit
Topology:
8 inputs per module,
OFF Level:
Greater than 70% of V source
Isolation Voltage:
1500 VDC for 10 sec.
Response
Source
1000 ohm (max) at 10 VDC
ON to OFF, 12 ms (max) OFF to ON, 12 ms (max)
ON Level:
Resistance:
Threshold
Voltage:
Max Input Voltage:
30-70%
Characteristics
Time:
Visual Indicators:
of V source
50 VDC, 10 ms
External Supply:
One LED indicator per input ON when input is ON (low)
Power 24 VDC at 100 mA (max)
Surge Withstand Capability: Physical true low
Per IEEE 472-1974 and ANSI C37.90A (2500V decaying in 6 microsec.)
Characteristics
Environment: Temperature Humidity Shock Vibration EMI RFI
0 to 60°C (ambient) 0 to 95% (non-condensing) 10 G for 11 msec. .625 G, 50-500 Hz Per MIL-STD 461 B Per FCC Class A
Dimensions:
1.62 in. (41.8 mm) X 6.00 in. (152.4 mm) X 11.00 in. (279.4 mm)
Weight:
2.0 Ibs. (.91 kg)
NOTES The B353-001 Input Module of additional components.
is compatible with the 8352-001
Output
Module without the use
=i!+ GOULD