Page 91

3−8

Local Monitoring During Network Operation

Parameters

Parameters Configuring Drive

The X200 inverter’s serial port may be connected to a network or to an external digital operator. During those times, the inverter keypad keys will not function (except for the Stop key). However, the inverter’s 4-digit display still provides the Monitor Mode function, displaying any of the parameters D001 to D007. Function B089, Monitor Display Select for Networked Inverter, determines the particular D00x parameter displayed. Refer to table below.

Option Code 01 02 03 04 05 06 07

B089 Monitor Display Select for Networked Inverter Monitor Monitor Function Name Code D001 Output frequency monitor D002 Output current monitor D003 Rotation direction monitor D004 Process variable (PV),PID feedback monitor D005 Intelligent input terminal status D006 Intelligent output terminal status D007 Scaled output frequency monitor

When monitoring the inverter during network operation, please note the following: x The inverter display will monitor D00x functions according to B089 setting when… ¾ The OPE/485 DIP switch is set to the “485” position, or ¾ A device is already connected to the inverter’s serial port at inverter powerup. x During network operation, the inverter keypad will also display error codes for inverter trip events. Use the Stop key or inverter Reset function to clear the error. Refer to “Error Codes” on page 6-5 to interpret the error codes. x The Stop key can be disabled, if you prefer, by using function B087.

Page 92

3−9

“F” Group: Main Profile Parameters The basic frequency (speed) profile is defined by parameters contained in the “F” Output frequency Group as shown to the right. The set F001 running frequency is in Hz, but acceleration and deceleration are specified in the time duration of the ramp (from zero to 0 maximum frequency, or from maximum frequency to zero). The motor direction parameter determines whether the keypad Run key produces a FWD or REV command. This parameter does not affect the intelligent terminal [FW] and [REV] functions, which you configure separately.

F002

F003 t

Func. Code F001

F002

“D” Function Name / Description SRW Display Output frequency setting Standard default target frequency that determines constant motor speed, range is VR 0000.0Hz 0.0 / start frequency to 400 Hz Acceleration (1) time setting Standard default acceleration, range is 0.01 to 3000 sec.

ACC 1 F202

010.00s

Cumulative power-on time monitor

DIG-RUN

10.0

10.0 sec.

Standard default acceleration, 2nd motor range is 0.01 to 3000 sec.

9

10.0

10.0 sec.

Standard default deceleration, range is 0.01 to 3000 sec.

9

10.0

10.0 sec.

Standard default deceleration, 2nd motor range is 0.01 to 3000 sec.

9

10.0

10.0 sec.

Two options; select codes: 00 }Forward 01 }Reverse

U

00

00

010.00s

Deceleration (1) time setting, 2nd motor

2DEC 1 F004

010.00s

Deceleration (1) time setting

DEC 1 F203

9

010.00s

Acceleration (1) time setting, 2nd motor

2ACC 1 F003

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 0.0 0.0 Hz 9

FWD

Configuring Drive

Parameters Parameters

Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main profile. Accel and decel values for an alternative profile are specified by using parameters Ax92 through Ax93. The motor direction selection (F004) determines the direction of rotation as commanded only from the keypad. This setting applies to any motor profile (1st or 2nd) in use at t particular time.

Page 93

3−10

“A” Group: Standard Functions The inverter provides flexibility in how you control Run/Stop operation and set the output frequency (motor speed). It has other control sources that can override the A001 / A002 settings. Parameter A001 sets the source selection for the inverter’s output frequency. Parameter A002 selects the Run command source (for FW or RV Run commands). The default settings use the input terminals for –FE (European) models, and the keypad for –FU (USA) models.

Func. Code A001

Parameters

Parameters Configuring Drive

A201

“A” Function Name / Description SRW Display Frequency source setting Five options; select codes: 00 }Keypad potentiometer F-COM VR 01 }Control terminal 02 }Function F001 setting Frequency source setting, 03 }ModBus network input 2nd motor 10 }Calculate function output

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 01 00

U

U

01

00

Run command source setting

U

01

02

U

01

02

2F-COM A002

OPE-Mode A202

VR

REM

Run command source setting, 2nd motor

OPE-Mode

Three options; select codes: 01 }Control terminal 02 }Run key on keypad, or digital operator 03 } ModBus network input

REM

Frequency Source Setting – For parameter A001, the following table provides a further description of each option, and a reference to other page(s) for more information. Code 00

01 02 03 10

Frequency Source Keypad potentiometer – The range of rotation of the knob matches the range defined by B082 (Start frequency adjustment) to A004 (Maximum frequency setting) Control terminal – The active analog input signal on analog terminals [O] or [OI] sets the output frequency Function F001 setting – The value in F001 is a constant, used for the output frequency ModBus network input – The network has a dedicated register for inverter output frequency Calculate function output – The Calculated function has user-selectable analog input sources (A and B). The output can be the sum, difference, or product (+, -, x) of the two outputs.

Refer to page(s)… 2-24

4-53, 3-13, 3-28, 3-49 3-9 B-19 3-29

Page 94

3−11

Run Command Source Setting – For parameter A002, the following table provides a further description of each option, and a reference to other page(s) for more information. Code 01 02 03

Run Command Source Control terminal – The [FW] or [RV] input terminals control Run/Stop operation Keypad Run key – The Run and Stop keys provide control ModBus network input – The network has a dedicated coil for Run/Stop command and a coil for FW/RV

Refer to page(s)… 4-11 2-24 B-19

A001/A002 Override Sources – The inverter allows some sources to override the setting for output frequency and Run command in A001 and A002. This provides flexibility for applications that occasionally need to use a different source, leaving the standard settings in A001/A002.

Priority 1 2 3 4 5

A001 Frequency Source Setting Method [CF1] to [CF4] Multi-speed terminals [OPE] Operator Control intelligent input [F-TM] intelligent input [AT] terminal A001 Frequency source setting

Refer to page… 4-12 4-29 4-31 4-22 3-10

The inverter also has other control sources that can temporarily override the parameter A002 setting, forcing a different Run command source. The following table lists all Run command setting methods and their relative priority (“1” is the highest priority). Priority 1 2 3

A002 Run Command Setting Method [OPE] Operator Control intelligent input [F-TM] intelligent input A002 Run command source setting

Refer to page… 4-29 4-31 3-10

Configuring Drive

Parameters Parameters

The inverter has other control sources that can temporarily override the parameter A001 setting, forcing a different output frequency source. The following table lists all frequency source setting methods and their relative priority (“1” is the highest priority).

Page 95

3−12

Basic Parameter Settings

Parameters

Parameters Configuring Drive

These settings affect the most fundamental behavior of the inverter – the outputs to the motor. The frequency of the inverter’s AC output determines the motor speed. You may select from three different sources for the reference speed. During application development you may prefer using the potentiometer, but you may switch to an external source (control terminal setting) in the finished application, for example. The base frequency and maximum frequency settings interact according to the graph below (left). The inverter output operation follows the constant V/f curve until it reaches the full-scale output voltage at the base frequency. This initial straight line is the constant-torque part of the operating characteristic. The horizontal line over to the maximum frequency serves to let the motor run faster, but at a reduced torque. This is the constant-power operating range. If you want the motor to output constant torque over its entire operating range (limited to the motor nameplate voltage and frequency rating), then set the base frequency and maximum frequency equal as shown (below right). A003 V 100%

A003

A004

Base Frequency

Maximum Frequency f

0

A004

V 100% f

0

Base Frequency = Maximum Frequency

NOTE: The “2nd motor” settings in the table in this chapter store an alternate set of parameters for a second motor. The inverter can use the 1st set or 2nd set of parameters to generate the output frequency to the motor. See “Configuring the Inverter for Multiple Motors” on page 4-58.

Func. Code A003

“A” Function Name / Description SRW Display Base frequency setting Settable from 30 Hz to the maximum frequency(A004)

Defaults Run Mode -FE -FU Units Edit (EU) (USA) U 50.0 60.0 Hz

Base frequency setting, 2nd motor

Settable from 30 Hz to the 2nd maximum frequency(A204)

U

50.0

60.0

Hz

Settable from the base frequency to 400 Hz

U

50.0

60.0

Hz

Settable from the 2nd base frequency to 400 Hz

U

50.0

60.0

Hz

F-BASE A203

2F-BASE A004

00060Hz

Maximum frequency setting

F-MAX A204

00060Hz

00060Hz

Maximum frequency setting, 2nd motor

2F-MAX

00060Hz

Page 96

3−13

Analog Input Settings The inverter has the capability to accept an external analog input that can command the output frequency to the motor. Voltage input (0-10 V) and current input (4-20mA) are available on separate terminals ([O] and [OI] respectively). Terminal [L] serves as signal ground for the two analog inputs. The analog input settings adjust the curve characteristics between the analog input and the frequency output. Please note that you cannot use the [O] and [OI] input at the same time.

Adjusting [OI-L] characteristics – In the graph to the right, A103 and A104 select the active portion of the input current range. Parameters A101 and A102 select the start and end frequency of the converted output frequency range, respectively. Together, these four parameters define the major line segment as shown. When the line does not begin at the origin (A101 and A103 > 0), then A105 defines whether the inverter outputs 0Hz or the A101-specified frequency when the analog input value is less than the A103 setting. When the input voltage is greater than the A104 ending value, the inverter outputs the ending frequency specified by A102.

Max frequency A012 A015=00

A015=01 A011 0

% 0% 0V

A013

A014

Input scale

100% 10V

Max frequency A102 A105=00

A105=01 A101 0

% 0% 0

A103

A104

Input scale

100% 20mA

Adjusting keypad potentiometer characteristics – Refer to parameters A151~A155.

Configuring Drive

Parameters Parameters

Adjusting [O-L] characteristics – In the graph to the right, A013 and A014 select the active portion of the input voltage range. Parameters A011 and A012 select the start and end frequency of the converted output frequency range, respectively. Together, these four parameters define the major line segment as shown. When the line does not begin at the origin (A011 and A013 > 0), then A015 defines whether the inverter outputs 0Hz or the A011-specified frequency when the analog input value is less than the A013 setting. When the input voltage is greater than the A014 ending value, the inverter outputs the ending frequency specified by A012.

Page 97

3−14

“A” Function Func. Code A005

Name / SRW Display [AT] selection

AT-Slct

A012

0.0

0.0

Hz

U

0.0

0.0

Hz

U

0.

0.

%

The ending point (offset) for the active analog input range, range is 0. to 100.

U

100.

100.

%

U

01

01

0Hz

Two options; select codes: 00}Use offset (A011 value) 01}Use 0Hz

External frequency filter time constant

Range n = 1 to 17, where n = number of samples for avg.

U

8.

8.

Samples

0000.0Hz

O-L input active range start voltage

00000%

O-L input active range end voltage

00000%

O-L input start frequency enable

O-LVL A016

0000.0Hz

O-L input active range end frequency

O-EX%E A015

O/VR

U

O-EX%S A014

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 02 02

U

The output frequency corresponding to the analog input range starting point, range is 0.0 to 400.0 The output frequency corresponding to the analog input range ending point, range is 0.0 to 400.0 The starting point (offset) for the active analog input range, range is 0. to 100.

O-EXE A013

Five options; select codes: 02...Select between [O] and keypad potentiometer at [AT] 03...Select between [OI] and integrated POT at [AT] 04...Only [O] input active 05...Only [OI] input active

O-L input active range start frequency

O-EXS Parameters

Parameters Configuring Drive

A011

Description

F-SAMP

00008

A016: External Frequency Filter Time Constant – This filter smoothes the analog input signal for the inverter’s output frequency reference. A016 set the filter range from n=1 to 16. This is a simple moving average calculation, where n (number of samples used) can be selected.

Page 98

3−15

Multi-speed and Jog Frequency Setting The X200 inverter has the capability to store and output up to 16 preset frequencies to the motor (A020 to A035). As in traditional motion terminology, we call this multi-speed profile capability. These preset frequencies are selected by means of digital inputs to the inverter. The inverter applies the current acceleration or deceleration setting to change from the current output frequency to the new one. The first multi-speed setting is duplicated for the second motor settings (the remaining 15 multi-speeds apply only to the first motor). The jog speed setting is used whenever the Jog command is active. The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The acceleration to the jog frequency is instantaneous, but you can choose from three modes for the best method for stopping the jog operation.

A220

A021 to A035

A038

A039

“A” Function Name / Description SRW Display Multi-speed frequency setting Defines the first speed of a multispeed profile, range is 0.0 / start frequency to 400Hz SPD 00s 0000.0Hz A020 = Speed 0 (1st motor) Multi-speed frequency Defines the first speed of a multisetting, 2nd motor speed profile or a 2nd motor, range is 0.0 / start frequency to 400Hz 2SPD00s 0000.0Hz A220 = Speed 0 (2nd motor) Multi-speed frequency Defines 15 more speeds, settings range is 0.0 / start frequency to (for both motors) 400 Hz. A021=Speed 1 ~ A035=Speed15 SPD 01s 000.0Hz A021 SPD 02s 000.0Hz A022 SPD 03s 000.0Hz A023 SPD 04s 000.0Hz A024 SPD 05s 000.0Hz A025 SPD 06s 000.0Hz A026 SPD 07s 000.0Hz A027 SPD 08s 000.0Hz SPD 09s 000.0Hz A028 SPD 10s 000.0Hz A029 SPD 11s 000.0Hz A030 SPD 12s 000.0Hz A031 SPD 13s 000.0Hz A032 SPD 14s 000.0Hz A033 SPD 15s 000.0Hz A034 A035 Jog frequency setting Defines limited speed for jog, range is 0.00 / start frequency to Jog-F 001.00Hz 9.99 Hz Jog stop mode Define how end of jog stops the motor; three options: 00}Free-run stop 01}Controlled deceleration Jog-Mode FRS 02}DC braking to stop

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 0.0 0.0 Hz 9

9

0.0

0.0

Hz

9

See next row

See next row

Hz

9

0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.00

0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.00

Hz

U

00

00

Configuring Drive

Parameters Parameters

Func. Code A020

Page 99

3−16

Torque Control Algorithms

Inverter Torque Control Algorithms

The inverter generates the motor output according Variable freq. control, 00 to the V/f algorithm selected. Parameter A044 constant torque selects the inverter algorithm for generating the Variable freq. control, 01 frequency output, as shown in the diagram to the reduced torque right (A244 for 2nd motor). The factory default is Variable freq. control, 06 00 (constant torque).

A044 Output reduced torque1

Review the following description to help you choose the best torque control algorithm for your application.

Parameters

Parameters Configuring Drive

The built-in V/f curves are oriented toward developing constant torque or variable torque characteristics (see graphs below). You can select either constant torque or reduced torque V/f control. Constant and Variable (Reduced) Torque – The graph at right shows the constant torque characteristic from 0Hz to the base frequency A003. The voltage remains constant for output frequencies higher than the base frequency. The graph below (left) shows the general variable (reduced) torque curve. The range from 0Hz to the base frequency is the variable characteristic. V

A044 = 01

Variable torque

V

A044 = 00

Hz 0 Base freq. V

100%

Constant torque

100%

A044 = 06

Max. freq.

Variable torque

100%

Hz 0

Hz 0

Base freq.

Max. freq.

10% Base freq.

Base freq.

Max. freq.

The graph above (right) shows the variable (reduced) torque curve, which has a constant torque characteristic from 0Hz to 10% of the base frequency. This helps to achieve higher torque at low speed with reduced torque curve at higher speeds. Manual Torque Boost – The Constant V and Variable Torque algorithms A042 = 5 (%) 100% feature an adjustable torque boost curve. When the motor load has a lot of inertia or starting friction, you may A 5% voltage need to increase the low frequency boost starting torque characteristics by (100%=A082) Hz 0 boosting the voltage above the normal 1.8Hz 30Hz fbase = 60Hz V/f ratio (shown at right). The function attempts to compensate for voltage A043 = 3 (%) drop in the motor primary winding in the low speed range. The boost is applied from zero to the base frequency. You set the breakpoint of the boost (point A on the graph) by using parameters A042 and A043. The manual boost is calculated as an addition to the standard V/f curve.

Page 100

3−17

Be aware that running the motor at a low speed for a long time can cause motor overheating. This is particularly true when manual torque boost is ON, or if the motor relies on a built-in fan for cooling.

Voltage gain – Using parameter A045 you can modify the voltage gain of the inverter (see graph at right). This is specified as a percentage of the full scale output voltage. The gain can be set from 20% to 100%. It should be adjusted in accordance with the motor specifications.

A045=100

V 100% 80%

The following table shows the methods of torque control selection.

A045=80

0 fbase

Name / SRW Display Torque boost select

Description

V-Bst Slct A241

MN

Torque boost select, 2nd motor

2VBst Slct A042

A242

00100%

V/f gain setting, 2nd motor

2V-Gain

%

Can boost starting torque between 0 and 20% above normal V/f curve, range is 0.0 to 20.0%

9

1.8

1.8

%

9

0.0

0.0

%

Sets the frequency of the V/f breakpoint A in graph (top of previous page) for torque boost, range is 0.0 to 50.0%

9

10.0

10.0

%

9

0.0

0.0

%

Two available V/f curves; 00}Constant torque 01}Reduced torque 06}Reduced torque1

U

00

00

U

00

00

Sets voltage gain of the inverter, range is 20. to 100.%

9

100.

100.

%

9

100.

100.

%

C-TRQ

V/f gain setting

V-Gain A245

C-TRQ

V/f characteristic curve, 2nd motor

2CTRL A045

00

0000.0%

V/f characteristic curve

CTRL A244

0003.0%

Manual torque boost frequency adjustment, 2nd motor

2MBst F A044

00

0005.0%

Manual torque boost frequency adjustment

M-Bst F A243

0005.0%

Manual torque boost value, 2nd motor

2VBst V A043

U

MN

Manual torque boost value

V-Bst V

Two options: 00}Manual torque boost 01}Automatic torque boost

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 00 00 % U

00100%

Parameters

“A” Function Func. Code A041 fmax