The text of a manual · part 9 of 31

X200 Series Inverter Instruction Manual, pages 81 to 90

Pages 81 to 90 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 81

2−34

Monitoring Parameters with the Display After using the keypad for parameter editing, it’s a good idea to switch the inverter from Program Mode to Monitor Mode. The PRG LED will be OFF, and the Hertz or Ampere LED indicates the display units.

and installation

Inverter Mountingand installation Inverter Mounting

RUN

STOP RESET

Hz

POWER

A

ALARM

RUN

PRG For the powerup test, monitor the motor speed indirectly by viewing the inverter’s output frequency. FUNC STR 2 1 The output frequency must not be confused with base frequency (50/60 Hz) of the motor, or the carrier frequency (switching frequency of the inverter, in the kHz range). The monitoring functions are in the “D” list, located near the top left of the “Keypad Navigation Map”on page 2-26.

Output frequency (speed) monitor – Resuming keypad operation from the previous table, follow the steps below. Or instead, you can simply power cycle the inverter, which automatically sets the display to D001 (output frequency value). Action (Starting point)

Display

Func./Parameter

H004

Motor poles parameter

Press the

FUNC key.

H- - -

“H” Group selected

Press the

1 key.

d001

Output frequency selected

Press the

FUNC key.

0.0

Output frequency displayed

When the inverter displays a monitor value, the PRG LED is OFF. This confirms the inverter is not in programming mode, even while you are selecting the particular monitoring parameter. The display shows the current speed (is zero at this point). The Hz LED will be ON, indicating the display units. For current, the Amperes LED will be ON.

Running the Motor If you have programmed all the parameters up to this point, you’re ready to run the motor! First, review this checklist: 1. 2. 3. 4. 5. 6. 7. 8.

Verify the power LED is ON. If not, check the power connections. Verify the Potentiometer Enable LED is ON. If it is OFF, check the A001 setting. Verify the Run Key Enable LED is ON. If it is OFF, check the A002 setting. Verify the PRG LED is OFF. If it is ON, review the instructions above. Make sure the motor is disconnected from any mechanical load. Turn the potentiometer to the minimum position (completely counter clock-wise). Now, press the RUN key on the keypad. The RUN LED will turn ON. Slowly increase the potentiometer setting in clockwise fashion. The motor should start turning. 9. Press the STOP key to stop the motor rotation.

Page 82

2−35

Powerup Test Observations and Summary 10

Step 10: Reading this section will help you make some useful observations when first running the motor. Error Codes – If the inverter displays an error code (format is “E xx”), see “Monitoring Trip Events, History, & Conditions” on page 6-5 to interpret and clear the error.

State of Inverter at Stop – If you adjust the motor’s speed to zero, the motor will slow to a near stop, and the inverter turns the outputs OFF. The high-performance X200 can rotate at a very slow speed with high torque output, but not zero (must use servo systems with position feedback for that feature). This characteristic means you must use a mechanical brake for some applications. Interpreting the Display – First, refer to the output frequency display readout. The maximum frequency setting (parameter A044) defaults to 50 Hz or 60 Hz (Europe and United States, respectively) for your application. Example: Suppose a 4-pole motor is rated for 60 Hz operation, so the inverter is configured to output 60 Hz at full scale. Use the following formula to calculate the rpm. Speed in RPM

Frequency u 60 Pairs of poles

Frequency u 120 # of poles

60 u120 1800 RPM 4

The theoretical speed for the motor is 1800 RPM (speed of torque vector rotation). However, the motor cannot generate torque unless its shaft turns at a slightly different speed. This difference is called slip. So it’s common to see a rated speed of approximately 1750 RPM on a 60 Hz, 4-pole motor. Using a tachometer to measure shaft speed, you can see the difference between the inverter output frequency and the actual motor speed. The slip increases slightly as the motor’s load increases. This is why the inverter output value is called “frequency”, since it is not exactly equal to motor speed. Run/Stop Versus Monitor/Program Modes – The Run LED on the inverter is ON in Run Mode, and OFF in Stop Mode. The Program LED is ON when the inverter is in Program Mode, and OFF for Monitor Mode. All four mode combinations are possible. The diagram to the right depicts the modes and the mode transitions via keypad.

Run

STOP RESET

Stop RUN

FUNC

Monitor

Program

NOTE: Some factory automation devices such as PLCs have alternative Run/Program modes; the device is in either one mode or the other. In the Hitachi inverter, however, Run Mode alternates with Stop Mode, and Program Mode alternates with Monitor Mode. This arrangement lets you program some value while the inverter is operating – providing flexibility for maintenance personnel.

InverterInverter Mounting Mountingand and installation installation

Acceleration and Deceleration – The X200 inverter has programmable acceleration and deceleration value. The test procedure left these at the default value, 10 seconds. You can observe this by setting the potentiometer at about half speed before running the motor. Then press RUN, and the motor will take 5 seconds to reach a steady speed. Press the STOP key to see a 5 second deceleration to a STOP.

Page 83

This page is a scan with no text; see it in the PDF.

Page 84

3−1

Configuring Drive Parameters page

-

Choosing a Programming Device................................................... 2

-

Using the Keypad Devices .............................................................. 3

-

“D” Group: Monitoring Functions .................................................. 6

-

“F” Group: Main Profile Parameters .............................................. 9

-

“A” Group: Standard Functions ................................................... 10

-

“B” Group: Fine Tuning Functions............................................... 32

-

“C” Group: Intelligent Terminal Functions .................................. 49

-

“H” Group: Motor Constants Functions ...................................... 65

Configuring Drive

Parameters Parameters

In This Chapter…

3

Page 85

3−2

Choosing a Programming Device Introduction

As the powerup test in Chapter 2 demonstrated, you do not have to program very many parameters to run the motor. In fact, most applications would benefit only from programming just a few, specific parameters. This chapter will explain the purpose of each set of parameters, and help you choose the ones that are important to your application. Parameters

Parameters Configuring Drive

Hitachi variable frequency drives (inverters) use the latest electronics technology for getting the right AC waveform to the motor at the right time. The benefits are many, including energy savings and higher machine output or productivity. The flexibility required to handle a broad range of applications has required ever more configurable options and parameters – inverter are now a complex industrial automation component. And this can make a product seem difficult to use, but the goal of this chapter is to make this easier for you.

If you are developing a new application for the inverter and a motor, finding the right parameters to change is mostly an exercise in optimization. Therefore, it is okay to begin running the motor with a loosely tuned system. By making specific, individual changes and observing their effects, you can achieve a finely tuned system.

Introduction of Inverter Programming The front panel keypad is the first and best way to get to know the inverter’s capabilities. Every function or programmable parameter is accessible from the keypad. The other devices simply imitate the keypad’s layout and inverter access, while adding another valuable aspect to the system. For example, the Digital Operator/Copy Unit can transfer one inverter’s parameter settings to another inverter, while still providing standard operator keypad control. In this way, you can use a variety of programming devices with basically the same keypad skills. The following table shows various programming options, the features unique to each device, and the cables required.

Device External inverter keypad Digital Operator/ Copy Unit

Part Number OPE-SRmini SRW-0EX

Parameter Access Monitor and Program Monitor and Program

Parameter setting storage EEPROM in inverter EEPROM in operator panel

Cables (choose one) Part number

Length

ICS-1 ICS-3 ICS-1 ICS-3

1 meter 3 meters 1 meter 3 meters

NOTE: When an external digital operator device such as an OPE-SRmini or SRW-0EX is connected to the inverter, the inverter’s keypad is automatically disabled (except for the Stop Key).

Page 86

3−3

Using the Keypad Devices The X200 Series inverter front keypad contains all the elements for both monitoring and programming parameters. The keypad is layout is pictured below. All other programming devices for the inverter have a similar key arrangement and function. Display Units (Hertz / Amperes) LEDs Parameter Display Hz

POWER

A

ALARM

Run key Enable LED Run key

RUN

STOP RESET

Stop/Reset key

FUNC

1

RUN

2

Power LED Alarm LED Run/Stop LED Potentiometer Enable LED

PRG

Potentiometer STR

Program/Monitor LED

Up/Down keys

Store key

Key and Indicator Legend x Run/Stop LED – ON when the inverter output is ON and the motor is developing torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode). x Program/Monitor LED – This LED is ON when the inverter is ready for parameter editing (Program Mode). It is OFF when the parameter display is monitoring data (Monitor Mode). x Run Key Enable LED – is ON when the inverter is ready to respond to the Run key, OFF when the Run key is disabled. x Run Key – Press this key to run the motor (the Run Enable LED must be ON first). Parameter F004, Keypad Run Key Routing, determines whether the Run key generates a Run FWD or Run REV command. x Stop/Reset Key – Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm that has tripped. x Potentiometer – Allows an operator to directly set the motor speed when the potentiometer is enabled for output frequency control. x Potentiometer Enable LED – ON when the potentiometer is enabled for value entry. x Parameter Display – A 4-digit, 7-segment display for parameters and function codes. x Display Units, Hertz/Amperes – One of these LEDs will be ON to indicate the units associated with the parameter display. x Power LED – This is ON when the power input to the inverter is ON. x Alarm LED – ON when an inverter trip is active (alarm relay contact will be closed). x Function Key – This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values. x Up/Down keys – Use these keys alternatively to move up or down the lists of parameter and functions shown in the display, and increment/decrement values. x Store key – When the unit is in Program Mode and you have edited a parameter value, press the Store key to write the new value to the EEPROM.

Configuring Drive

Parameters Parameters

Function key

Page 87

3−4

Keypad Navigation Map You can use the inverter’s front panel keypad to navigate to any parameter or function. The diagram below shows the basic navigation map to access these items. Monitor Mode PRG LED=OFF

Programming Mode PRG LED=OFF

Display Data

Select parameter

Edit parameter

Power down Store as powerup default

1

FUNC

1

Parameters

Parameters Configuring Drive

Select Function or Group 1

2

1

2

1

1

2

1

2 1

1

2

2

FUNC

1

2

1

2

1

2

1

2

Increment/ decrement value

2

Edit FUNC

1

2

1

2

1

2

1

2

FUNC

STR

2

2

Write data to EEPROM

Return to parameter list

NOTE: The inverter 7-segment display shows lower case “b” and “d”, meaning the same as the upper case letters “B” and “D” used in this manual (for uniformity “A” to “F”). NOTE: The Store Key saves the edited parameter (shown in the display) to the inverter’s EEPROM. Upload or download of parameters to/from external devices is accomplished through a different command – do not confuse Store with Download or Upload.

Page 88

3−5

Operational Modes The RUN and PRG LEDs tell just part of the story; Run Mode and Program Modes are independent modes, not opposite modes. In the state diagram to the right, Run alternates with Stop, and Program Mode alternates with Monitor Mode. This is a very important ability, for it shows that a technician can approach a running machine and change some parameters without shutting down the machine.

STOP RESET

Stop RUN

FUNC

Monitor

Run

Program

STOP RESET

Stop RUN STOP RESET

Fault

Trip

Fault

Run Mode Edit The inverter can be in Run Mode (inverter output is controlling motor) and still allow you to edit certain parameters. This is useful in applications that must run continuously, you need some inverter parameter adjustment. The parameter tables in this chapter have a column titled “Run Mode Edit”. An Ex mark U means the parameter cannot be edited; a Check mark 9 means the parameter can be edited. The Software Lock Setting (parameter B031) determines when the Run Mode access permission is in effect and access permission in other conditions, as well. It is the responsibility of the user to choose a useful and safe software lock setting for the inverter operating conditions and personnel. Please refer to “Software Lock Mode” on page 3-36 for more information.

Run Mode Edit

U 9

Control Algorithms The motor control program in the X200 inverter has two sinusoidal PWM switching algorithms. The intent is that you select the best algorithm for the motor and load characteristics of your application. Both algorithms generate the frequency output in a unique way. Once configured, the algorithm is the basis for other parameter settings as well (see “Torque Control Algorithms” on page 3-16). Therefore, choose the best algorithm early in your application design process.

Inverter Control Algorithms Variable freq. control, constant torque

Variable freq. control, reduced torque

Output

Configuring Drive

Parameters Parameters

The occurrence of a fault during operation will cause the inverter to enter Trip Mode as shown. An event such as an output overload will cause the inverter to exit the Run Mode and turn OFF its output to the motor. In the Trip Mode, any request to run the motor is ignored. You must clear the error by pressing the Stop/Reset switch. See “Monitoring Trip Events, History, & Conditions” on page 6-5.

Run

Page 89

3−6

“D” Group: Monitoring Functions You can access important parameter values with the “D” Group monitoring functions, whether the inverter is in Run Mode or Stop Mode. After selecting the function code number for the parameter you want to monitor, press the Function key once to show the value on the display. In functions D005 and D006, the intelligent terminals use individual segments of the display to show ON/OFF status. If the inverter display is set to monitor a parameter and powerdown occurs, the inverter stores the present monitor function setting. For your convenience, the display automatically returns to the previously monitored parameter upon the next powerup.

Parameters

Parameters Configuring Drive

Func. Code D001

D002

D003

D004

D005

“D” Function Run Mode Units Name / Description Edit SRW Display Output frequency monitor Real time display of output Hz frequency to motor from FM 000.00Hz 0.0 to 400.0Hz Output current monitor Filtered display of output current to A motor (100 ms internal filter time constant), range is Iout 0000.0A 0 to 999.9 ampere Rotation direction monitor Three different indications:

“F” }Forward “o” }Stop Dir STOP “r” }Reverse Process variable (PV), Displays the scaled PID process % times

PID feedback monitor variable (feedback) value (A075 is constant scale factor), 0.00 to 99.99, 100.0 to 999.9 1000. to 9999., 1000 to 999, FB 00000.00% and 10000 to 99900 Intelligent input Displays the state of the intelligent terminal status input terminals: ON OFF 5 4

IN-TM D006

LHLHL

Intelligent output terminal status

3

2 1

Terminal numbers

Displays the state of the intelligent output terminals: ON OFF AL

OUT-TM

L H

11

Terminal numbers

Page 90

3−7

Func. Code D007

D013

“D” Function Run Units Mode Name / Description Edit SRW Display Scaled output frequency Displays the output frequency Hz times monitor scaled by the constant in B086. constant Decimal point indicates range: XX.XX 0.00 to 99.99 XXX.X 100.0 to 999.9 XXXX. 1000. to 9999. XXXX 1000 to 9999 F-Cnv 00000.00 (x10=10000 to 99999) Output voltage monitor Voltage of output to motor, V

Range is 0.0 to 600.0V

Vout D016

00000V

RUN D017

0000000hr

Cumulative power-on time monitor

RUN D018

Cooling monitor

0000000hr Fin

TH-Fin temperature

Displays total time the inverter has been in RUN mode in hours. Range is 0 to 9999 / 1000 to 9999 / ª100 to ª999 (10,000 to 99,900) Displays total time the inverter has been powered up in hours. Range is 0 to 9999 / 1000 to 9999 / ª100 to ª999 (10,000 to 99,900) Temperature of the cooling fin. (0.0~200)

hours hours qC

0000.0 C

Trip Event and History Monitoring The trip event and history monitoring feature lets you cycle through related information using the keypad. See “Monitoring Trip Events, History, & Conditions” on page 6-5 for more details. “D” Function Func. Code D080

Name / SRW Display Trip counter

ERR CNT D081

D102

######## ########

DC bus voltage monitor

Vpn D104

########

Trip monitor 3

ERR3

0000.0Vdc

Electronic thermal monitor

E-THM

Run Mode Edit

Units events

00000

Trip monitor 2

ERR2 D083

Number of trip events, Range is 0. to 9999

Trip monitor 1

ERR1 D082

Description

0000.0%

Displays trip event information: x Error code x Output frequency at trip point x Motor current at trip point x DC bus voltage at trip point x Cumulative inverter operation time at trip point x Cumulative power-ON time at trip point

Voltage of inverter internal DC bus, Range is 0.0 to 999.9 Accumulated value of electronic thermal detection, range is from 0.0 to 100.0

V

%

Configuring Drive

Parameters Parameters

Cumulative operation RUN time monitor