The text of a manual · part 8 of 31

X200 Series Inverter Instruction Manual, pages 71 to 80

Pages 71 to 80 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 71

2−24

Uncover the Inverter Vents Step 8: After mounting and wiring the inverter, remove any covers from the inverter housing. This includes material over the side ventilation ports.

Ventilation holes (top)

WARNING: Make sure the input power to the inverter is OFF. If the drive has been powered, leave it OFF for five minutes before continuing. and installation

Inverter Mountingand installation Inverter Mounting

8

Ventilation holes (both sides)

Powerup Test 9

Step 9: After wiring the inverter and motor, you’re ready to do a powerup test. The procedure that follows is designed for the first-time use of the drive. Please verify the following conditions before conducting the powerup test: x You have followed all the steps in this chapter up to this step. x The inverter is new, and is securely mounted to a non-flammable vertical surface. x The inverter is connected to a power source and a motor. x No additional wiring of the inverter connectors or terminals has been done. x The power supply is reliable, and the motor is a known working unit, and the motor nameplate ratings match the inverter ratings. x The motor is securely mounted, and is not connected to any load.

Goals for the Powerup Test If there are any exceptions to the above conditions at this step, please take a moment to take any measures necessary to reach this basic starting point. The specific goals of this powerup test are: 1. Verify that the wiring to the power supply and motor is correct. 2. Demonstrate that the inverter and motor are generally compatible. 3. Get an introduction to the use of the built-in operator keypad. The powerup test gives you an important starting to ensure a safe and successful application of the Hitachi inverter. We highly recommend performing this test before proceeding to the other chapters in this manual.

Page 72

2−25

Pre-test and Operational Precautions

CAUTION: The heat sink fins will have a high temperature. Be careful not to touch them. Otherwise, there is the danger of getting burned. CAUTION: The operation of the inverter can be easily changed from low speed to high speed. Be sure to check the capability and limitations of the motor and machine before operating the inverter. Otherwise, there is the danger of injury. CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage and/or injury. CAUTION: Check the following before and during the Powerup test. Otherwise, there is the danger of equipment damage. x Is the shorting bar between the [+1] and [+] terminals installed? DO NOT power or operate the inverter if the jumper is removed. x Is the direction of the motor rotation correct? x Did the inverter trip during acceleration or deceleration? x Were the rpm and frequency meter readings as expected? x Were there any abnormal motor vibration or noise?

Powering the Inverter If you have followed all the steps, cautions and warnings up to this point, you’re ready to apply power. After doing so, the following events should occur: x The POWER LED will illuminate. x The numeric (7-segment) LEDs will display a test pattern, then stop at 0.0. x The Hz LED will be ON. If the motor starts running unexpectedly or any other problem occurs, press the STOP key. Only if necessary should you remove power to the inverter as a remedy. NOTE: If the inverter has been previously powered and programmed, the LEDs (other than the POWER LED) may illuminate differently than as indicated above. If necessary, you can initialize all parameters to the factory default settings. See “Restoring Factory Default Settings” on page 6-8.

InverterInverter Mounting Mountingand and installation installation

The following instructions apply to the powerup test, or to any time the inverter is powered and operating. Please study the following instructions and messages before proceeding with the powerup test. 1. The power supply must have fusing suitable for the load. Check the fuse size chart presented in Step 5, if necessary. 2. Be sure you have access to a disconnect switch for the drive input power if necessary. However, do not turn OFF power during inverter operation unless it is an emergency. 3. Turn the keypad potentiometer to the minimum position (full counter-clockwise).

Page 73

2−26

Using the Front Panel Keypad Please take a moment to familiarize yourself with the keypad layout shown in the figure below. The display is used in programming the inverter’s parameters, as well as monitoring specific parameter values during operation.

and installation

Inverter Mountingand installation Inverter Mounting

Display Units (Hertz / Amperes) LEDs Parameter Display Hz

POWER

A

ALARM

Run key Enable LED Run key

RUN

STOP RESET

Stop/Reset key

FUNC

1

RUN

2

Power LED Alarm LED Run/Stop LED Potentiometer Enable LED

PRG

Potentiometer STR

Program/Monitor LED

Function key Up/Down keys

Store key

Key and Indicator Legend x Run/Stop LED – ON when the inverter output is ON and the motor is developing torque (Run Mode), and OFF when the inverter output is OFF (Stop Mode). x Program/Monitor LED – This LED is ON when the inverter is ready for parameter editing (Program Mode). It is OFF when the parameter display is monitoring data (Monitor Mode). x Run Key Enable LED – is ON when the inverter is ready to respond to the Run key, OFF when the Run key is disabled. x Run Key – Press this key to run the motor (the Run Enable LED must be ON first). Parameter F004, Keypad Run Key Routing, determines whether the Run key generates a Run FWD or Run REV command. x Stop/Reset Key – Press this key to stop the motor when it is running (uses the programmed deceleration rate). This key will also reset an alarm that has tripped. x Potentiometer – Allows an operator to directly set the motor speed when the potentiometer is enabled for output frequency control. x Potentiometer Enable LED – ON when the potentiometer is enabled for value entry. x Parameter Display – A 4-digit, 7-segment display for parameters and function codes. x Display Units, Hertz/Amperes – One of these LEDs will be ON to indicate the units associated with the parameter display. x Power LED – This is ON when the power input to the inverter is ON. x Alarm LED – ON when an inverter trip is active (alarm relay contact will be closed). x Function Key – This key is used to navigate through the lists of parameters and functions for setting and monitoring parameter values. x Up/Down keys – Use these keys alternatively to move up or down the lists of parameter and functions shown in the display, and increment/decrement values. x Store key – When the unit is in Program Mode and you have edited a parameter value, press the Store key to write the new value to the EEPROM.

Page 74

2−27

Keys, Modes, and Parameters

Function Group “D” “F” “A” “B” “C” “H” “P” “E”

Hz

POWER

A

ALARM

RUN

STOP RESET

RUN

FUNC

1

2

Type (Category) of Function

Mode to Access

Monitoring functions Main profile parameters Standard functions Fine tuning functions Intelligent terminal functions Motor constant functions DeviceNet functions Error codes

Monitor Program Program Program Program Program Program

PRG STR

InverterInverter Mounting Mountingand and installation installation

The purpose of the keypad is to provide a way to change modes and parameters. The term function applies to both monitoring modes and parameters. These are all accessible through function codes that are primary 4-character codes. The various functions are separated into related groups identifiable by the left-most character, as the table shows.

PRG LED Indicator z z z z z z

For example, function “A004” is the base frequency setting for the motor, typically 50Hz or 60Hz. To edit the parameter, the inverter must be in Program Mode (PRG LED will be ON). You use the front panel keys to first select the function code “A004”. After displaying the value for “A004”, use the Up/Down keys ( 1 or 2 ) to edit it.

Hz

POWER

Hz

POWER

Hz

POWER

A

ALARM

A

ALARM

A

ALARM

FUNC

RUN FUNC

STOP RESET

RUN

1

2

FUNC

RUN

PRG STR

FUNC

STOP RESET

RUN

1

2

PRG STR

RUN

STOP RESET

RUN

FUNC

1

2

PRG STR

NOTE: The inverter 7-segment display shows lower case “b” and “d”, meaning the same as the upper case letters “B” and “D” used in this manual (for uniformity “A” to “F”). The inverter automatically switches into Monitor Mode when you access “D” Group functions. It switches into Program Mode when you access any other group, because they all have editable parameters. Error codes use the “E” Group, and appear automatically when a fault event occurs. “P” group appears when DeviceNet communication is available. Refer to “Monitoring Trip Events, History, & Conditions” on page 6-5 for error code details. TIP: Pressing

FUNC

MONITOR

“D” Group

PROGRAM “A” Group “B” Group “C” Group “F” Group “H” Group “P” Group key continuously for 3 seconds makes the display back to d001.

Page 75

2−28

Keypad Navigation Map and installation

Inverter Mountingand installation Inverter Mounting

The X200 Series inverter drives have many programmable functions and parameters. Chapter 3 will cover these in detail, but you need to access just a few items to perform the powerup test. The menu structure makes use of function codes and parameter codes to allow programming and monitoring with only a 4-digit display and a keys and LEDs. So, it is important to become familiar with the basic navigation map of parameters and functions in the diagram below. You may later use this map as a reference. Monitor Mode PRG LED=OFF

Program Mode PRG LED=ON

Display Data

Select parameter

Edit parameter

Power down Store as powerup default

1

FUNC

1

Select Function or Group 1

2

1

2

1

1

2

1

2 1

1

2

2

FUNC

1

2

1

2

1

2

1

2

Increment/ decrement value

2

Edit FUNC

1

2

1

2

1

2

1

2

FUNC

STR

2

2

Write data to EEPROM

Return to parameter list

The navigation map shows the relationship of all resources of the inverter in one view. 2 In general, use the FUNC key to move left and right, and the 1 (arrow) keys to move up and down.

Page 76

2−29

Selecting Functions and Editing Parameters To prepare to run the motor in the powerup test, this section will show how to configure the necessary parameters: 1. Select the keypad potentiometer as the source of motor speed command (A001). 2. Select the keypad as the source of the RUN command (A002).

4. Set the motor current for proper thermal protection (B012). 5. Set the inverter’s Automatic Voltage Regulation for the motor (A082). 6. Set the number of poles for the motor (H004). The following series of programming tables are designed for successive use. Each table uses the previous table’s final state as the starting point. Therefore, start with the first and continue programming until the last one. If you get lost or concerned that some of the other parameters setting may be incorrect, refer to “Restoring Factory Default Settings” on page 6-8. Prepare to Edit Parameters – This sequence begins with powering ON the inverter, then it shows how to navigate to the “A” Group parameters for subsequent settings. You can also refer to the “Keypad Navigation Map” on page 2-26 for orientation throughout the steps. Action

Display

Turn ON the inverter.

0.0

Func./Parameter Inverter output frequency Displayed (0Hz in Stop Mode)

Press the

FUNC key.

d001

“D” Group selected

Press the

2 key four times.

A- - -

“A” Group selected

Select the Potentiometer for Speed Command – The inverter output frequency can be set from several sources, including an analog input, memory setting, or the network, for example. The powerup test uses the keypad potentiometer as the speed control source for your convenience. In the figure to the right, notice the Potentiometer Enable LED, just above the knob. It the LED is ON, the potentiometer is already selected as the source, and you may skip this step. Note that the default setting depends on the country.

Potentiometer Enable LED

Hz

POWER

A

ALARM

RUN

STOP RESET

RUN

FUNC

1

2

PRG STR

InverterInverter Mounting Mountingand and installation installation

3. Set the inverters maximum output frequency to the motor (A003).

Page 77

2−30

If the Potentiometer Enable LED is OFF, follow these steps below. Action and installation

Inverter Mountingand installation Inverter Mounting

(Starting point)

Display

Func./Parameter

A- - -

“A” Group selected

A001

Speed command source setting

Press the

FUNC

Press the

FUNC key again.

01

00 = Keypad potentiometer 01 = Control terminals 02 = Function F001 setting 03 = ModBus network 04 = Calculate function output

Press the

2 key.

00

00 = Potentiometer (selected)

Press the

STR key.

A001

Store parameter, returns to “A” Group list key.

Select the Keypad for RUN Command – To RUN command causes the inverter to accelerate the motor to the selected speed. The Run command can arrive from various sources, including the control terminals, the Run key on the keypad or the network. In the figure to the right, notice the Run Key Enable LED, just above the Run key. If the LED is ON, the Run key is already selected as the source, and you may skip this step. Note that the default setting depends on the country.

Run Key Enable LED

Hz

POWER

A

ALARM

RUN

STOP RESET

RUN

FUNC

1

2

PRG STR

If the Potentiometer Enable LED is OFF, follow these steps below (the table resumes action from the end of the previous table). Action (Starting point)

Display

Func./Parameter

A001

Speed command source setting

A002

Run command source setting

Press the

1 key once.

Press the

FUNC key.

01

01 = Control terminals 02 = Run key on keypad 03 = ModBus network

Press the

1 key.

02

02 = Run key on keypad (selected)

Press the

STR key.

A002

Store parameter, returns to “A” Group list

NOTE: After completing the steps above, the Run Key Enable LED will be ON. This does not mean the motor is trying to run; it means that the RUN key is now enabled. DO NOT press the RUN key at this time – complete the parameter setup first.

Page 78

2−31

Set the Motor Base Frequency – The motor is designed to operate at a specific AC frequency. Most commercial motors are designed for 50/60 Hz operation. First, check the motor specifications. Then follow the steps below to verify the setting or correct it for your motor. DO NOT set it greater than 50/60 Hz unless the motor manufacturer specifically approves operation at the higher frequency. Action

Press the

Press the

1

FUNC key once.

key.

Display

Func./Parameter

A002

Run command source setting

A003

Base frequency setting

60.0

Default value for the base frequency. US = 60 Hz, Europe = 50 Hz

InverterInverter Mounting Mountingand and installation installation

(Starting point)

or 50.0

Press the

1 or

Press the

STR key.

2 key as needed.

60.0 A003

Set to your motor specs (your display may be different) Store parameter, returns to “A” Group list

CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage. Set the AVR Voltage Setting – The inverter has an Automatic Voltage Regulation (AVR) function. It adjusts the output voltage to match the motor’s nameplate voltage rating. The AVR smoothes out fluctuation in the input power source, but note that it does not boost the voltage in the event of a brown-out. Use the AVR setting (A082) that most closely matches the one for your motor. x

200V class: 200 / 215 / 220 / 230 / 240 VAC x

400V class: 380 / 400 / 415 / 440 / 460 / 480 VAC

TIP: If you need to scroll through a function or parameter list, press and hold the 2 key to auto-increment through the list. To set the motor voltage, follow the steps on the following page.

1 or

Page 79

2−32

Action (Starting point)

and installation

Inverter Mountingand installation Inverter Mounting

Press the

1 key and hold until Æ

Press the

FUNC key.

Press the

1 or

Press the

STR key.

Display

Func./Parameter

A003

Base frequency setting

A082

AVR voltage select

230

Default value for AVR voltage: 200V class = 230VAC 400V class = 400VAC (HFE) = 460VAC (HFU)

or 400

2 key as needed.

215 A082

Set to your motor specs (your display may be different) Store parameter, returns to “A” Group list

Set the Motor Current – The inverter has thermal overload protection that is designed to protect the inverter and motor from overheating due to an excessive load. The inverter’s uses the motor’s current rating to calculate the time-based heating effect. This protection depends on using correct current rating for your motor. The level of electronic thermal setting, parameter B012, is adjustable from 20% to 120% of the inverter’s rated current. A proper configuration will also help prevent unnecessary inverter trip events. Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps below to configure the inverter’s overload protection setting. Action (Starting point)

Display

Func./Parameter

A082

AVR voltage select

Press the

FUNC key.

A- - -

“A” Group selected

Press the

1 key.

b- - -

“B” Group selected

Press the

FUNC key.

b001

First “B” Group parameter selected

Press the

1 key and hold until Æ b012

Level of electronic thermal setting

Press the

FUNC key.

1.60

Press the

1 or

Press the

STR key.

2 key as needed.

1.80 b012

Default value will be 100% of inverter rated current Set to your motor specs (your display may be different) Store parameter, returns to “B” Group list

Page 80

2−33

Set the Number of Motor Poles – The motor’s internal winding arrangement determines its number of magnetic poles. The specification label on the motor usually indicates the number of poles. For proper operation, verify the parameter setting matches the motor poles. Many industrial motors have four poles, corresponding to the default setting in the inverter (H004). Follow the steps in the table below to verify the motor poles setting and change if necessary (the table resumes action from the end of the previous table.) Display

Func./Parameter b012

Level of electronic thermal setting

Press the

FUNC key.

b- - -

“B” Group selected

Press the

1 key two times.

H- - -

“H” Group selected

Press the

FUNC key.

H003

First “H” Group parameter

Press the

1 key once

H004

Motor poles parameter

Press the

FUNC key.

Press the

1 or

Press the

STR key.

2

4 key as needed.

4 H004

2 = 2 poles 4 = 4 poles (default) 6 = 6 poles 8 = 8 poles Set to your motor specs (your display may be different) Store parameter, returns to “H” Group list

This step concludes the parameter setups for the inverter. You are almost ready to run the motor for the first time! TIP: If you became lost during any of these steps, first observe the state of the PRG LED. Then study the “Keypad Navigation Map on page 2-26 to determine the current state of the keypad controls and display. As long as you do not press the STR key, no parameter will be changed by keypad entry errors. Note that power cycling the inverter causes it to power up Monitor Mode, displaying the value for D001 (output frequency). The next section will show you how to monitor a particular parameter from the display. Then you will be ready to run the motor.

InverterInverter Mounting Mountingand and installation installation

Action (Starting point)