The text of a manual · part 7 of 31

X200 Series Inverter Instruction Manual, pages 61 to 70

Pages 61 to 70 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 61

2−14

Dimensional drawings, continued… X200-004HFEF, -004HFU

Inverter Mountingand installation

Inverter Mounting and installation CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

Page 62

2−15

Dimensional drawings, continued…

Inverter Mountingand installation

Inverter Mounting and installation

X200-007HFEF, -007HFU

CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

Page 63

2−16

Dimensional drawings, continued… and installation

Inverter Mountingand installation Inverter Mounting

X200-015HFEF~040HFEF, -015HFU~040HFU

CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

Page 64

2−17

Dimensional drawings, continued… X200-055LFU, -075LFU, -055HFU, -075HFU, -055HFEF, -075HFEF

InverterInverter Mounting Mountingand and installation installation CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

Page 65

2−18

Prepare for Wiring 5

Step 5: It is very important to perform the wiring steps carefully and correctly. Before proceeding, please study the caution and warning message herebelow.

and installation

Inverter Mountingand installation Inverter Mounting

WARNING: “USE 60/75qC Cu wire only” or equivalent. For models X200-005S, -007S, -011S, -022S, 007N, -015N, 015L, -022L, -037L. WARNING: “USE 75qC Cu wire only” or equivalent. For models X200-002S, -004S, 002N, -004N, 002L, -004L, -007L, -022H, -030H, 037H and X200-040H. WARNING: “USE 60qC Cu wire only” or equivalent. For models X200-004H, -007H, and –015H. WARNING: “Open Type Equipment.”

WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes, 240V maximum.” For models with suffix S, N or L. WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes, 480V maximum.” For models with suffix H. HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric shock and/or fire. HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel. Otherwise, there is a danger of electric shock and/or fire. HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF. Otherwise, you may incur electric shock and/or fire. HIGH VOLTAGE: Do not connect wiring to an inverter or operate an inverter that is not mounted according to the instructions given in this manual. Otherwise, there is a danger of electric shock and/or injury to personnel.

Page 66

2−19

Determining Wire and Fuse Sizes The maximum motor currents in your application determines the recommended wore size. The following table gives the wire size in AWG. The “Power Lines” column applies to the inverter input power, output wires to the motor, the earth ground connection, and any other components shown in the “Basic System Description” on page 2-7. The “Signal Lines” column applies to any wire connecting to the two green connectors just inside the front cover panel. Wiring Inverter Model kW

HP

0.2 0.4 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 0.4 0.75 1.5 2.2 3.0 4.0 5.5 7.5

1/4 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 1/2 1 2 3 4 5 7 1/2 10

Power Lines X200-002SFEF/NFU X200-004SFEF/NFU X200-005SFEF X200-007SFEF/NFU X200-011SFEF X200-015SFEF/NFU X200-022SFEF/NFU X200-037LFU X200-055LFU X200-075LFU X200-004HFEF/HFU X200-007HFEF/HFU X200-015HFEF/HFU X200-022HFEF/HFU X200-030HFEF X200-040HFEF/HFU X200-055HFEF/HFU X200-075HFEF/HFU

Signal Lines

AWG14 / 2.1mm2

AWG10 / 5.3mm2 AWG12 / 3.3mm2 AWG10 / 5.3mm2 AWG8 / 8.4mm2 AWG16 / 1.3mm2

18 to 28 AWG / 0.14 to 0.75 mm2 shielded wire (see Note 4)

Applicable equipment Fuse (UL-rated, class J, 600V) 10A 10A 10A 15A 15A 20A 30A 30A 40A 50A 3A 6A 10A

AWG14 / 2.1mm2 (60qC only)

15A

AWG12 / 3.3mm2 (60qC only)

20A 25A

Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal connector sized for the wire gauge involved. Connector must be fixed by using the crimping tool specified by the connector manufacturer. Note 2: Be sure to consider the capacity of the circuit breaker to be used. Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m). Note 4: Use 18 AWG / 0.75mm2 wire for the alarm signal wire ([AL0], [AL1], [AL2] terminals).

InverterInverter Mounting Mountingand and installation installation

Motor Output

Page 67

2−20

Terminal Dimensions and Torque Specs The terminal screw dimensions for all X200 inverters are listed in table below. This information is useful in sizing spade lug or ring lug connectors for wire terminations.

and installation

Inverter Mountingand installation Inverter Mounting

WARNING: Fasten the screws with the specified fastening torque in the table below. Check for any loosening of screws. Otherwise, there is the danger of fire.

Connector

Power Terminals (Top side) Power Terminals (Bottom side) Control Signal Alarm Signal

Number of Screw Terminals

Models 002S~004S, 002N~004N Screw Diameter

Width (mm)

Models 007S~022S, 007N~022N,037L, 004H~040H Screw Width Diameter (mm)

Models 055~075L/H Screw Diameter

Width (mm)

5

M3.5

7.1

M4

9.2

M5

12

8(dual in row) 7 15 3

M3.5

M2 M3

7.1

M4 M2 M3

9.2

M5 M2 M3

12

When connecting wiring, use the tightening torque listed in the following table to safely attach wiring to the connectors. Screw Tightening Torque M2 0.2Nxm (max. 0.25 Nxm) M3 0.5Nxm (max. 0.6 Nxm)

Screw Tightening Torque M3.5 0.8Nxm (max. 0.9 Nxm) M4 1.2Nxm (max. 1.3 Nxm)

Screw Tightening Torque M5 2.0Nxm (max. 2.2 Nxm)

Wire the Inverter Input to a Supply 6

Step 6: In this step, you will connect wiring to the input of the inverter. First, you must determine whether the inverter model you have required three-phase power only, or single-phase power only. All models have the same power connection terminals [R/L1], [S/L2], and [T/L3]. So you must refer to the specifications label (on the side of the inverter) for the acceptable power source types! For inverters that can accept singlephase power and are connected that way, terminal [S/L2] will remain unconnected. The wiring example to the right shows an X200 inverter wired for 3-phase input. Note the use of ring lug connectors for a secure connection.

Input wiring for single-phase input (-SFEF and -NFU models)

Input wiring for 3-phase input (models -NFU, -LFU, -HFEF, -HFU)

CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

Page 68

2−21

Please use the terminal arrangement below corresponding to your inverter model. Inverter models X200-002SFEF~004SFEF, X200-002NFU~004NFU

L1

/

N

L1

SFEF

/

Jumper NFU,LFU

L1

L2 L3/N

InverterInverter Mounting Mountingand and installation installation

SFEF

X200-005SFEF~022SFEF, X200-007NFU~022NFU,037LFU X200-004HFEF~040HFEF X200-004HFU~040HFU X200-055LFU~075LFU X200-055HFU~075HFU X200-055HFEF~075HFEF N Jumper NFU, LFU

L1

L2 L3/N

Jumper

Jumper HFEF, HFU

R/L1 S/L2 T/L3 Jumper

Jumper + +1 U/T1 V/T2 W/T3

Jumper

U/T1 V/T2 W/T3

-

+

+1

CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

NOTE: An inverter powered by a portable power generator may receive a distorted power waveform, overheating the generator. In general, the generator capacity should be five times that of the inverter (kVA).

Page 69

2−22 and installation

Inverter Mountingand installation Inverter Mounting

CAUTION: Be sure that the input voltage matches the inverter specifications: x Single-phase 200 to 240 V 50/60 Hz (0.2kW~2.2kW) for SFEF models x Single/Three-phase 200 to 240 V 50/60 Hz (0.2kW~2.2kW) for NFU models x Three-phase 200 to 240 V 50/60 Hz (3.7kW~7.5kW) for LFU models x Three-phase 380 to 480 V 50/60Hz (0.4kW~7.5kW) for HFEF and HFU models CAUTION: Be sure not to power a three-phase-only inverter with single phase power. Otherwise, there is the possibility of damage to the inverter and the danger of fire. CAUTION: Be sure not to connect an AC power supply to the output terminals. Otherwise, there is the possibility of damage to the inverter and the danger of injury and/or fire.

X200 Inverter

Power Input Output to Motor

CAUTION: Remarks for using ground fault interrupter breakers in the main power supply: Adjustable frequency inverter with integrated CE-filters and shielded (screened) motor cables have a higher leakage current toward earth GND. Especially at the moment of switching ON this can cause an inadvertent trip of ground fault interrupters. Because of the rectifier on the input side of the inverter there is the possibility to stall the switch-off function through small amounts of DC current. Please observe the following: x Use only short time-invariant and pulse current-sensitive ground fault interrupters with higher trigger current. x Other components should be secured with separate ground fault interrupters. x Ground fault interrupters in the power input wiring of an inverter are not an absolute protection against electric shock. CAUTION: Be sure to install a fuse in each phase of the main power supply to the inverter. Otherwise, there is the danger of fire. CAUTION: For motor leads, ground fault interrupter breakers and electromagnetic contactors, be sure to size these components properly (each must have the capacity for rated current and voltage). Otherwise, there is the danger of fire.

Page 70

2−23

Wire the Inverter Output to Motor 7

Step 7: The process of motor selection is beyond the scope of this manual. However, it must be an AC induction motor with three phases. It should also come with a chassis ground lug. If the motor does not have three power input leads, stop the installation and verify the motor type. Other guidelines for wiring the motor include: Use an inverter-grade motor for maximum motor life (1600V insulation).

x

For standard motors, use the AC reactor accessory if the wiring between the inverter and motor exceeds 10 meters in length.

Simply connect the mot or to the terminals [U/T1], [V/T2], and [W/T3] as shown to the right. This is a good time to connect the chassis ground lug on the drive as well. The motor chassis ground must also connect to the same point. Use a star ground (singlepoint) arrangement, and never daisy-chain the grounds (point-to-point). x

Check the mechanical integrity of each wire crimp and terminal connection.

x

Replace the housing partition that covers access to the power connections.

CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable

Logic Control Wiring After completing the initial installation and powerup test in this chapter, you may need to wire the logic signal connector for your application. For new inverter users/applications, we highly recommend that you first complete the powerup test in this chapter without adding any logic control wiring. Then you will be ready to set the required parameters for logic control as covered in Chapter 4, Operations and Monitoring.

InverterInverter Mounting Mountingand and installation installation x