Page 101

3−18

DC Braking (DB) Settings Normal DC braking The DC braking feature can provide additional stopping torque when compared to a normal deceleration to a stop. DC braking is particularly useful at low speeds when normal deceleration torque is minimal.

+

Running

Free run

DC brake t

0 A053

-

A055

The braking power (A054) and duration (A055) can both be set. You can optionally specify a wait time before DC braking (A053), during which the motor will free run.

Parameters

Parameters Configuring Drive

When you set A051 to 01 (Enable during stop), and the RUN command (FW/RV signal) turns OFF, the inverter injects a DC voltage into the motor windings during deceleration below a frequency you can specify (A052).

DC Braking – Frequency Detection You can instead set DC braking to operate during RUN mode only, by setting A051 to 02 (Frequency detection). In this case DC braking operates when the output frequency comes down to the one you specified in A052 while the RUN command is still active. Refer to the graphs figures below. External DB and Internal DC braking are invalid during the frequency detection mode. FW

FW

ON

F-SET

F-SET

A052

A052

F-OUT

F-OUT

DB Ex.1) Step change in F-SET.

ON

DB

DB

DB

Ex.2) Analog change in F-SET.

Example 1, (above left) shows the performance with A051=02 with a step-changing frequency reference. In this case, when the reference goes to 0, the inverter immediately starts DC braking because the set point drops below the value specified in A052. DC braking continues until the set point exceeds A052. There will be no DC braking at next downward transition because the FW input is OFF. Example 2, (above right) shows a gradually changing frequency reference, for example by analog input. In this case, there will be a DC braking period at starting because the frequency set point is lower than the value specified in A052.

Page 102

3−19

CAUTION: Be careful to avoid specifying a braking time that is long enough to cause motor overheating. If you use DC braking, we recommend using a motor with a built-in thermistor, and wiring it to the inverter’s thermistor input (see “Thermistor Thermal Protection” on page 4-24). Also refer to the motor manufacturer’s specifications for duty-cycle recommendations during DC braking. “A” Function Func. Code A051

Name / SRW Display DC braking enable

Description

DCB Mode A052

DCB Wait A054

0000.5Hz

DC braking wait time

0000.0s

DC braking force for deceleration

DCB V A055

0.5

Hz

U

0.0

0.0 sec.

Level of DC braking force, settable from 0 to 100%

U

0.

0.

%

Sets the duration for DC braking, range is from 0.0 to 60.0 seconds

U

0.0

0.0 sec.

Two options; select codes: 00}Edge detection 01}Level detection

U

01

01

0000.0s

DC braking / edge or level detection for [DB] input

DCB KIND

0.5

00000%

DC braking time for deceleration

DCB T A056

U

LEVEL

Configuring Drive

Parameters Parameters

DCB F A053

OFF

DC braking frequency setting

Two options; select codes: 00}Disable 01}Enable during stop 02}Frequency detection The frequency at which DC braking begins, range is from the start frequency (B082) to 60Hz The delay from the end of controlled deceleration to start of DC braking (motor free runs until DC braking begins), range is 0.0 to 5.0 sec.

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 00 00

U

Page 103

3−20

Frequency-related Functions

Parameters

Parameters Configuring Drive

Frequency Limits – Upper and lower limits can be imposed on the inverter output frequency. These limits will apply regardless of the source of the speed reference. You can configure the lower frequency limit to be greater than zero as shown in the graph. The upper limit must not exceed the rating of the motor or capability of the machinery. The maximum frequency setting (A004/A204) takes precedence over frequency upper limit (A061/A261).

Func. Code A061

A261

A062

A262

Output frequency Upper A061 limit Settable range A062

Lower limit 0

Frequency command

“A” Function Name / Description SRW Display Frequency upper limit setting Sets a limit on output frequency less than the maximum frequency (A004). Range is from frequency lower limit (A062) to maximum frequency (A004). 0.0 setting is disabled Lim H 0000.0Hz >0.0 setting is enabled Frequency upper limit Sets a limit on output frequency setting, 2nd motor less than the maximum frequency (A204). Range is from frequency lower limit (A262) to maximum frequency (A204). 0.0 setting is disabled 2Lim H 0000.0Hz >0.0 setting is enabled Frequency lower limit setting Sets a limit on output frequency greater than zero. Range is start frequency (B082) to frequency upper limit (A061) 0.0 setting is disabled Lim L 0000.0Hz >0.0 setting is enabled

Defaults Run Mode -FE -FU Units Edit (EU) (USA) U 0.0 0.0 Hz

Frequency lower limit setting, 2nd motor

2Lim L

0000.0Hz

Sets a limit on output frequency greater than zero. Range is start frequency (B082) to frequency upper limit (A261) 0.0 setting is disabled >0.0 setting is enabled

U

0.0

0.0

Hz

U

0.0

0.0

Hz

U

0.0

0.0

Hz

Page 104

3−21

Jump Frequencies – Some motors or machines exhibit resonances at particular speed(s), which can be destructive for prolonged running at those speeds. The inverter has up to three jump frequencies as shown in the graph. The hysteresis around the jump frequencies causes the inverter output to skip around the sensitive frequency values. Output frequency A068 A067 A068 A066

A065

A066 A063

A064 A064

Frequency command

A064, Jump (hysteresis) frequency A066, width setting A068 JUMP W1 0000.5Hz

JUMP W2 JUMP W3

0000.5Hz 0000.5Hz

Defines the distance from the center frequency at which the jump around occurs Range is 0.0 to 10.0 Hz

U

0.5 0.5 0.5

0.5 0.5 0.5

Hz

Configuring Drive

Parameters Parameters

“A” Function Defaults Run Mode -FE -FU Func. Name / Description Units Edit (EU) (USA) Code SRW Display A063, Jump (center) frequency Up to 3 output frequencies can be U 0.0 0.0 Hz A065, setting defined for the output to jump 0.0 0.0 A067 JUMP F1 0000.0Hz past to avoid motor resonances 0.0 0.0 JUMP F2 0000.0Hz (center frequency) JUMP F3 0000.0Hz Range is 0.0 to 400.0 Hz

Page 105

3−22

PID Control When enabled, the built-in PID loop calculates an ideal inverter output value to cause a loop feedback process variable (PV) to move closer in value to the set point (SP). The frequency command serves as the SP. The PID loop algorithm will read the analog input for the process variable (you specify the current or voltage input) and calculate the output. x x x

A scaled factor in A075 lets you multiply the PV factor, converting it into engineering units for the process. Proportional, integral, and derivative gains are all adjustable. See “PID Loop Operation” on page 4-56 for more information.

Parameters

Parameters Configuring Drive

“A” Function Func. Code A071

Name / SRW Display PID enable

PID Mode A072

OFF

PID proportional gain

PID P A073

A075

001.00%

PV source setting

PID INP A077

OI

Reverse PID action

PID MINUS A078

OFF

PID output limit

PID Vari

9

1.0

1.0

Integral time constant has a range of 0.0 to 150 seconds

9

1.0

1.0 sec

Derivative time constant has a range of 0.0 to 100 seconds

9

0.00

0.00 sec

Process Variable (PV), scale factor (multiplier), range of 0.01 to 99.99 Selects source of Process Variable (PV), option codes: 00}[OI] terminal (current in) 01}[O] terminal (voltage in) 02}ModBus network 10}Calculate function output Two option codes: 00}PID input = SP-PV 01}PID input = -(SP-PV)

U

1.00

1.00

U

00

00

U

00

00

Sets the limit of PID output as percent of full scale, range is 0.0 to 100.0%

U

0.0

0.0

%

000.00s

PV scale conversion

PID Cnv A076

Proportional gain has a range of 0.2 to 5.0

0001.0s

PID derivative time constant

PID D

Enables PID function, two option codes: 00}PID Disable 01}PID Enable

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 00 00

U

0001.0

PID integral time constant

PID I A074

Description

0000.0%

NOTE: The setting A073 for the integrator is the integrator’s time constant Ti, not the gain. The integrator gain Ki = 1/Ti. When you set A073 = 0, the integrator is disabled.

Page 106

3−23

Automatic Voltage Regulation (AVR) Function The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a relatively constant amplitude during power input fluctuations. This can be useful if the installation is subject to input voltage fluctuations. However, the inverter cannot boost its motor output to a voltage higher than the power input voltage. If you enable this feature, be sure to select the proper voltage class setting for your motor. “A” Function Func. Code A081

Name / SRW Display AVR function select

ON

AVR voltage select

AVR AC

00230V

Automatic (output) voltage regulation, selects from three type of AVR functions, three option codes: 00}AVR enabled 01}AVR disabled 02}AVR enabled except during deceleration 200V class inverter settings: }}200/215/220/230/240 400V class inverter settings: }}380/400/415/440/460/480

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 00 00

U

U

230/ 400

230/ 460

V

Configuring Drive

Parameters Parameters

AVR Mode A082

Description

Page 107

3−24

Energy Savings Mode / Optional Accel/Decel Energy Saving Mode – This function allows the inverter to deliver the minimum power necessary to maintain speed at any given frequency. This works best when driving variable torque characteristic loads such as fans and pumps. Parameter A085=01 enables this function and A086 controls the degrees of its effect. A setting of 0.0 yields slow response but high accuracy, while a setting of 100 will yield a fast response with lower accuracy.

Func. Code A085

ECO Adj Parameters

Parameters Configuring Drive

A086

“A” Function Name / Description SRW Display Operation mode selection Three option codes: 00}Normal operation RUN MODE NOR 01}Energy-saver operation Energy saving mode tuning Range is 0.0 to 100 %.

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 00 00

U

U

50.0

50.0

%

0050.0%

The acceleration time is controlled so that the output current below the level set by the Overload Restriction Function if enabled (Parameters b021, b022, and b023). If Overload Restriction is not enabled, then the current limit used is 150% of the inverter’s rated output current. The deceleration time is controlled so that the output current is maintained below 150% of the inverter’s rated current, and the DC bus voltage is maintained below the OV Trip level (400V or 800V). NOTE: If the load exceeds the rating of the inverter, the acceleration time may be increased. NOTE: If using a motor with a capacity that is one size smaller than the inverter rating, enable the Overload Restriction function (b021) and set the Overload Restriction Level (b022) to 1.5 times the motor nameplate current. NOTE: Be aware that the acceleration and deceleration times will vary, depending on the actual load conditions during each individual operation of the inverter.

Page 108

3−25

Second Acceleration and Deceleration Functions The X200 inverter features two-stage acceleration and deceleration ramps. This gives flexibility in the profile shape. You can specify the frequency transition point, the point at which the standard acceleration (F002) or deceleration (F003) changes to the second acceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] to trigger this transition. These profile options are also available for the second motor settings. Select a transition method via A094 as depicted below. Be careful not to confuse the second acceleration/deceleration settings with settings for the second motor! A094 = 00 Output frequency

Transition via 2CH input

A094 = 01 Output frequency

Accel 2

A292

A093

A293

A094

Frequency transition point t

0

1 t

0

“A” Function Name / Description SRW Display Acceleration (2) time setting Duration of 2nd segment of acceleration, range is: ACC 2 0015.00s 0.01 to 3000 sec. Acceleration (2) time setting, Duration of 2nd segment of 2nd motor acceleration, 2nd motor, range is: 2ACC2 0015.00s 0.01 to 3000 sec. Deceleration (2) time setting Duration of 2nd segment of deceleration, range is: DEC 2 0015.00s 0.01 to 3000 sec. Deceleration (2) time setting, Duration of 2nd segment of 2nd motor deceleration, 2nd motor, range is: 2DEC2 0015.00s 0.01 to 3000 sec.

Defaults Run Mode -FE -FU Units Edit (EU) (USA) 9 15.00 15.00 sec

Select method to switch to Acc2/Dec2 profile

ACC CHG A294

Accel 1

TM

Select method to switch to Acc2/Dec2 profile, 2nd motor

2ACCCHG

TM

Two options for switching from 1st to 2nd accel/decel: 00}2CH input from terminal 01}Transition frequency Two options for switching from 1st to 2nd accel/decel: 00}2CH input from terminal 01}Transition frequency (2nd motor)

9

15.00 15.00 sec

9

15.00 15.00 sec

9

15.00 15.00 sec

U

00

00

U

00

00

Configuring Drive

Parameters Parameters t

0

Func. Code A092

Accel 2

A095

Accel 1

2CH input

Transition via freq. level

Page 109

3−26

Func. Code A095

A295

A096

Parameters

Parameters Configuring Drive

A296

“A” Function Name / Description SRW Display Acc1 to Acc2 frequency Output frequency at which transition point Accel1 switches to Accel2, range ACC CHfr 0000.0Hz is 0.0 to 400.0 Hz Acc1 to Acc2 frequency Output frequency at which transition point, 2nd motor Accel1 switches to Accel2, 2nd 2ACCCHfr 0000.0Hz motor, range is 0.0 to 400.0 Hz Dec1 to Dec2 frequency Output frequency at which transition point Decel1 switches to Decel2, range DEC CHfr 0000.0Hz is 0.0 to 400.0 Hz Dec1 to Dec2 frequency Output frequency at which transition point, 2nd motor Decel1 switches to Decel2, 2nd 2DECCHfr 0000.0Hz motor, range is 0.0 to 400.0 Hz

Defaults Run Mode -FE -FU Units Edit (EU) (USA) U 0.0 0.0 Hz

U

0.0

0.0

Hz

U

0.0

0.0

Hz

U

0.0

0.0

Hz

NOTE: For A095 and A096 (and for 2nd motor settings), if you set a very rapid Acc1 or Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or Dec2 before reaching the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in order to achieve the second ramp to the target frequency.

Page 110

3−27

Accel/Decel Standard acceleration and deceleration is linear. The inverter CPU can also calculate an S-curve acceleration or deceleration curve as shown. This profile is useful for favoring the load characteristics in particular applications. Curve settings for acceleration and deceleration are independently selected. To enable the S-curve, use function A097 (acceleration) and A098 (deceleration).

A098

Target freq.

Accel. curve selection S-curve A097 = 01 Linear A097 = 00 t

0 Acceleration period

“A” Function Name / Description SRW Display Acceleration curve selection Set the characteristic curve of Acc1 and Acc2, two options: 00}linear ACC LINE L 01}S-curve Deceleration curve selection Set the characteristic curve of Dec1 and Dec2, two options: 00}linear DEC LINE L 01}S-curve

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

00

00

U

00

00

Configuring Drive

Parameters Parameters

Func. Code A097

Output frequency