The text of a manual · part 12 of 31

X200 Series Inverter Instruction Manual, pages 111 to 120

Pages 111 to 120 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 111

3−28

Additional Analog Input Settings Input Range Settings – The parameters in the following table adjust the input characteristics of the analog current input. When using the inputs to command the inverter output frequency, these parameters adjust the starting and ending ranges for the current, as well as the output frequency range. Related characteristic diagrams are located in “Analog Input Settings” on page 3-13. Analog sampling setting is the value specified in A016.

Parameters

Parameters Configuring Drive

Func. Code A101

A102

A103

“A” Function Defaults Run Mode -FE -FU Name / Description Units Edit (EU) (USA) SRW Display [OI]-[L] input active range The output frequency U 0.0 0.0 Hz start frequency corresponding to the analog input range starting point, OI-EXS 0000.0Hz range is 0.0 to 400.0 Hz [OI]-[L] input active range The output frequency U 0.0 0.0 Hz end frequency corresponding to the current input range ending point, OI-EXE 0000.0Hz range is 0.0 to 400.0 Hz [OI]-[L] input active range start current

OI-EX%S A104

OI-EX%E A105

00000%

[OI]-[L] input active range end voltage

00000%

[OI]-[L] input start frequency enable

OI-LVL

0Hz

The starting point (offset) for the current input range, range is 0. to 100.% The ending point (offset) for the current input range, range is 0. to 100.% Two options; select codes: 00}Use offset (A101 value) 01}Use 0Hz

U

0.

0.

%

U

100.

100.

%

U

01

01

Refer to parameter A011 to A015 for analog voltage input.

NOTE: You cannot use voltage input and current input ([O] and [OI] input) at the same time on the X200 series inverter. Please do not connect the cable to [O] and [OI] terminals at the same time.

Page 112

3−29

Analog Input Calculate Function – The inverter can mathematically combine two input sources into one value. The Calculate function can either add, subtract, or multiply the two selected sources. This provides the flexibility needed by various applications. You can use the result for the output frequency setting (use A001=10) or for the PID Process Variable (PV) input (use A075=03).

Digital operator

A141

A143

Potentiometer A input select

[O] input [OI] input Network variable

A B

Digital operator

“CAL” (result)

x A+B x A-B x A*B

B input select

[O] input [OI] input Network variable

Func. Code A141

A142

A143

A142

“A” Function Name / Description SRW Display A input select for calculate Five options: function 00}Digital operator 01}Keypad potentiometer 02}[O] input 03}[OI] input CALC Slct1 POT 04}Network variable B input select for calculate Five options: function 00}Digital operator 01}Keypad potentiometer 02}[O] input 03}[OI] input CALC Slct2 OI 04}Network variable

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

Calculation symbol

CALC SMBL

Calculates a value based on the A input source (A141 selects) and B input source (A142 selects). Three options: 00}ADD (A input + B input) 01}SUB (A input - B input) 02}MUL (A input * B input)

U

01

01

U

02

02

U

00

00

NOTE: For A141 and A142, it is not possible to use [O] and [OI] together in calculation, because using both inputs at the same time on the X200 series inverter is not allowed.

Configuring Drive

Parameters Parameters

Potentiometer

Page 113

3−30

Add Frequency – The inverter can add or subtract on offset value to the output frequency setting which is specified by A001 (will work with any of the five possible sources). The ADD Frequency is a value you can store in parameter A145. the ADD Frequency is summed with or subtracted from the output frequency setting only when the [ADD] terminal is ON. Function A146 selects whether to add or subtract. By configuring an intelligent input as the [ADD] terminal, your application can selectively apply the fixed value in A145 to offset (positively or negatively) the inverter output frequency in real time. A001

Keypad potentiometer

Frequency source setting

Control terminal + Function F001 setting

Output frequency setting

+/-

Calculate function output Parameters

Parameters Configuring Drive

ModBus network input

Ȉ

A146 A145 ADD frequency

ADD direction select [ADD]

Intelligent input

“A” Function Func. Code A145

Name / SRW Display ADD frequency

ST-PNT A146

Description

0000.0Hz

ADD direction select

ADD DIR

PLUS

An offset value that is applied to the output frequency when the [ADD] terminal is ON. Range is 0.0 to 400.0 Hz Two options: 00}Plus (adds A145 value to the output frequency setting) 01}Minus (subtracts A145 value from the output frequency setting)

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

9

0.0

0.0

Hz

U

00

00

Page 114

3−31

Potentiometer Settings Input Range Settings – The parameters in the following table adjust the input characteristics of the integrated potentiometer. When using the potentiometer to command the inverter output frequency, these parameters adjust the starting and ending ranges for the potentiometer, as well as the output frequency range.

Func. Code A151

A152

A154

A155

Max frequency A152 A015=00

A015=01 A151 %

0

0% A153 Counterclockwise

A154

Input scale

100% Clockwise

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

0.0

0.0

Hz

U

0.0

0.0

Hz

U

0.

0.

%

U

100.

100.

%

U

01

01

Configuring Drive

Parameters Parameters

A153

“A” Function Name / Description SRW Display Pot. input active range start The output frequency frequency corresponding to the pot. range starting point, POT-EXS 0000.0Hz range is 0.0 to 400.0 Hz Pot. input active range end The output frequency frequency corresponding to the pot. range ending point, POT-EXE 0000.0Hz range is 0.0 to 400.0 Hz Pot. input active range start The starting point (offset) for the potentiometer range, POT-EX%S 00000% range is 0. to 100.% Pot. input active range end The ending point (offset) for the potentiometer range, POT-EX%E 00000% range is 0. to 100.% Pot. input start frequency Two options; select codes: enable 00}Use offset (A151 value) POT-LVL 0Hz 01}Use 0Hz

Page 115

3−32

“B” Group: Fine Tuning Functions The “B” Group of functions and parameters adjust some of the more subtle but useful aspects of motor control and system configuration.

Automatic Restart Mode The restart mode determines how the inverter will resume operation after a fault causes a trip event. The four options provide advantages for your applications. Frequency matching allows the inverter to read the motor speed by virtue of its residual magnetic flux and restart the output at the corresponding frequency. The inverter can attempt a restart a certain number of times depending on the particular trip event: x Over-current trip, restart up to 3 times

Parameters

Parameters Configuring Drive x Over-voltage trip, restart up to 3 times x Under-voltage trip, restarts up to 16 time When the inverter reaches the maximum number of restarts (3 or 16), you must power cycle the inverter to reset its operation. Other parameters specify the allowable under-voltage level and the delay time before restarting. The proper settings depend on the typical fault conditions for your application, the necessity of restarting the process in unattended situations, and whether restarting is always say. If the actual power failure time is shorter than the B002 set value, inverter resumes from the set frequency in B011.

Power failure < allowable power fail Time (B022), Inverter resumes Input power

The resumption mode is called “frequency pull-in” and the inverter performs reduced voltage start to avoid over-current trip.

Inverter output Freq. Pull-in restart level

B030

Motor current Motor rotation

Free-running Power fail

Allowable power fail time

B002

Retry wait time

B003

If the motor current exceeds the B030 set value during this period, the inverter decelerates according to the B029 set value and helps to reduce the motor current.

When the motor current is less than B030, the inverter increases motor speed toward the set speed. Freq. Pull-in restart The inverter continues this retry Deceleration constant process until the motor speed comes to the previous set speed. B029

Overload restriction (B021~B028) is not valid when frequency pull-in is activated. If the actual power failure time is longer than the B002 set value, the inverter does not resume and the motor will coast to stop.

Page 116

3−33

Func. Code B001

B002

B004

IPS TRIP B005

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

00

00

U

1.0

1.0 sec.

U

1.0

1.0 sec.

U

00

00

U

00

00

OFF

Number of restarts on power failure / under-voltage trip events

IPS RETRY

Two option codes: 00}Restart 16 times 01}Always restart

16

Frequency Pull-in Restart Func. Code B011

B029

“B” Function Defaults Run Mode -FE -FU Name / Description Units Edit (EU) (USA) SRW Display Start freq to be used in case Three option codes: 00 00

U of frequency pull-in restart 00}freq at previous shutoff 01}start from max. Hz FSch Md CUTOFF 02}start from set frequency Deceleration rate of Sets the deceleration rate when U 0.5 0.5 sec. frequency pull-in restart frequency pull-in restart, range is setting 0.1 to 3000.0, resolution 0.1

FSch CNS B030

0000.5s

Current level of frequency pull-in restart setting

FSch LVL

002.60A

Sets the current level of frequency pull-in restart, range is 0.2*inverter rated current to 2.0*inverter rated current, resolution 0.1

U

Rated current

A

Configuring Drive

Parameters Parameters

B003

“B” Function Name / Description SRW Display Selection of automatic restart Select inverter restart method, mode Four option codes: 00}Alarm output after trip, no automatic restart 01}Restart at 0Hz 02}Resume operation after frequency pull-in 03}Resume previous freq. after freq. pull-in, then decelerate IPS POWR ALM to stop and display trip info Allowable under-voltage The amount of time a power power failure time input under-voltage can occur without tripping the power failure alarm. Range is 0.3 to 25 sec. If under-voltage exists longer than this time, the inverter trips, even if the restart mode is IPS Time 0001.0s selected. Retry wait time before motor Time delay after under-voltage restart condition goes away, before the inverter runs motor again. IPS Wait 0001.0s Range is 0.3 to 100 seconds. Instantaneous power failure / Two option codes: under-voltage trip alarm 00}Disable enable 01}Enable

Page 117

3−34

Electronic Thermal Overload Alarm Setting The thermal overload detection protects the inverter and motor from overheating due to an excessive load. It uses a current/inverse time curve to determine the trip point. First, use B013 to select the torque characteristic that matches your load. This allows the inverter to utilize the best thermal overload characteristic for your application.

Torque Constant torque B013 = 01 100% 80% 60%

0

Parameters

The torque developed in a motor is directly proportional to the current in the windings, which is also related to the heat generated (and temperature, over time).

Parameters Configuring Drive

Reduced torque1 B013 = 00

Reduced torque2 B013 = 02 Hz

5 20 60 120 Output frequency

Therefore, you must set the thermal overload threshold in terms of current (amperes) for parameter B012. The range is 20% to 120% of the rated current for each inverter model. If the current exceeds the level you specify, the inverter will trip and log an event (error E05) in the history table. The inverter turns the motor output OFF when tripped. Separate settings are available for the second motor (if applicable) as shown in the following table.

Func. Code B012

B212

“B” Function Name / Description SRW Display Level of electronic thermal Set a level between 20% and setting 100% for the rated inverter E-THM LVL 001.60A current.

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

Level of electronic thermal setting, 2nd motor

Set a level between 20% and 100% for the rated inverter current.

U

Select from three curves, option codes: 00}Reduced torque 1 01}Constant torque 02}Reduced torque 2 Select from three curves, option codes: 00}Reduced torque 1 01}Constant torque 02}Reduced torque 2

U

01

01

U

01

01

2ETHM LVL B013

E-THM CHAR B213

001.60A

Electronic thermal characteristic

CRT

Electronic thermal characteristic, 2nd motor

2ETHM CHAR

CRT

U

Rated current for each inverter model *1

A

A

WARNING: When parameter B012, level of electronic thermal setting, is set to motor FLA rating (Full Load Ampere nameplate rating), the inverter provides solid state motor overload protection at 115% of motor FLA or equivalent. If parameter B012 exceeds the motor FLA rating, the motor may overheat and be damaged. Parameter B012, level of electronic thermal setting, is a variable parameter.

Page 118

3−35

Overload Restriction If the inverter’s output current exceeds a preset current level you specify during acceleration or constant speed, the overload restriction feature automatically reduces the output frequency to restrict the overload. This feature does not generate an alarm or trip event. You can instruct the inverter to apply overload restriction only during constant speed, thus allowing higher currents for acceleration. Or, you may use the same threshold for both acceleration and constant speed.

Motor current

Restriction area

B022 t

0 Output frequency t

0 B022

“B” Function Func. Code B021

Name / SRW Display Overload restriction operation mode

Description

OL Mode B221

ON

Overload restriction operation mode, 2nd motor

2OL Mode B022

OL LVL B222

0001.0s

01

01

U

01

01

U

A

Sets the deceleration rate when inverter detects overload, range is 0.1 to 30.0, resolution 0.1

U

Rated current x 1.5 Rated current x 1.5 1.0 30.0 sec.

U

1.0

30.0 sec.

U

00

00

PARAM

Source of overload restriction selection, 2nd motor

2OL L_SLCT

U

00

00

U

A

0001.0s

Source of overload restriction selection

OL L_SLCT B228

U

Deceleration rate at overload restriction, 2nd motor

2OL Cnst B028

Select the operation mode during overload conditions, three options, option codes: 00}Disabled 01}Enabled for acceleration and constant speed 02}Enabled for constant speed only Sets the level for overload restriction, between 20% and 150% of the rated current of the inverter, setting resolution is 1% of rated current

002.40A

Deceleration rate at overload restriction

OL Cnst B223

002.40A

Overload restriction level setting, 2nd motor

2OL LVL B023

ON

Overload restriction level setting

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

PARAM

Two option codes: 00}set value of B022 01}[O] input Two option codes: 00}set value of B222 01}[O] input

Frequency Pull-in Restart See “Restart Mode Configuration” (B088) section on page 3-42.

Configuring Drive

Parameters Parameters

When the inverter detects an overload, it must decelerate the motor to reduce the current until it s less than the threshold. You can choose the rate of deceleration that the inverter uses to lower the output current.

Page 119

3−36

Software Lock Mode

Parameters

The table below lists all combinations of B031 option codes and the Run ON/OFF state of the [SFT] input. Each Check 9 or Ex U indicates Mode Edit whether the corresponding parameter(s) can be edited. The Standard Parameters column below shows access in permitted for U some lock modes. These refer to the parameter tables throughout 9 this chapter, each of which includes a column titled Run Mode Edit as shown to the right. The marks (Check 9 or Ex U) under the “Run Mode Edit” column title indicate whether access applies to each parameter as defined in the table below. In some lock modes, you can edit only F001 and the Multi-speed parameter group that includes A020, A220, A021–A035, and A038 (Jog). However, it does not include A019, Multi-speed operation selection. The editing access to B031 itself is unique, and is specified in the right-most two columns below. B031 Lock Mode

[SFT] Intelligent Input

Standard Parameters Stop

Run Run mode edit access

F001 and Multi-Speed Stop and Run

Stop

Run

9

9

U

B031

OFF

9

ON

U

U

U

9

U

OFF

9

Run mode edit access

9

9

U

00

01 ON

U

U

9

9

U

02

(ignored)

U

U

U

9

U

03

(ignored)

U

U

9

9

U

9

High level access

9

9

9

10

(ignored)

NOTE: Since the software lock function B031 is always accessible, this feature is not the same as password protection used in other industrial control devices.

Configuring Drive Parameters

Parameters Configuring Drive

The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B031 to select from various protection levels.

Page 120

3−37

“B” Function Name / Description SRW Display Software lock mode selection Prevents parameter changes, in four options, option codes: 00}all parameters except B031 are locked when [SFT] terminal is ON 01}all parameters except B031 and output frequency F001 are locked when [SFT] terminal is ON 02}all parameters except B031 are locked 03}all parameters except B031 and output frequency F001 are locked 10}High level access including B031

S-Lock

MD1

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

01

01

See appendix C for the accessible parameters in this mode.

NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the [SFT] function to one of the intelligent input terminals. See “Software Lock” on page 4-21.

Parameters

Configuring Drive Parameters

Func. Code B031