The text of a manual · part 13 of 31
X200 Series Inverter Instruction Manual, pages 121 to 130
Pages 121 to 130 of 305
The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi X200 Series
Page 121
3−38
Controlled Stop Operation at Power Loss Controlled stop operation at power loss helps avoid tripping or free-running (coasting) of the motor when power is lost while in run mode. The inverter controls the internal DC bus voltage while decelerating the motor, and brings the motor to a controlled stop.
Power
OFF c d e f
DC bus voltage b052 b051
Parameters
Output frequency b054 b053 b053 b053
Should power be lost while the inverter is in run mode, this function will have the following effect: c When the internal DC bus voltage of the inverter comes down to the set level of B051, the inverter decreases the output frequency by the amount set in B054. (During this interval the DC bus voltage rises due to regeneration, so does not reach the UV level.) d The inverter then continues deceleration according to the value set in B053. If the DC bus voltage rises up to the set value of B052, the inverter stops deceleration to avoid OV tripping. e During this interval, the DC bus voltage decreases again due to lack of input power. f When the DC bus voltage comes down to the set value of B051, the inverter starts deceleration according to the set value of B053 again. This process will be repeated as needed until the motor is brought to a stop. NOTE: If the DC bus voltage comes down to the UV level during this operation, the inverter trips with under-voltage and motor will free-run (coast) to a stop. NOTE: If the set value of B052<B051, then the inverter internally swaps the B052 and B051 values. However the displayed values are not changed. NOTE: This function cannot be interrupted until it is completed. So if the power is restored during this operation, wait until the operation is done (motor stops) and then give the run command.
Configuring Drive Parameters
Under-voltage level
Page 122
3−39
Func. Code B050
B051
“B” Function Defaults Run Mode -FE -FU Name / Description Units Edit (EU) (USA) SRW Display Selection of controlled stop Two option codes: 00 00
U operation 00}Disabled 01}Enabled (stop) IPS MODE OFF 02}Enabled (restart) Controlled stop operation Setting of DC bus voltage to start V U 0.0 0.0 start voltage setting controlled stop operation. Range is 0.0 to 1000.0
IPS V B052
IPS OV
0.0
0.0
V
Range is 0.01 to 3000
U
1.0
1.0 sec
Setting of the first quick drop in frequency. Range is 0.0 to 10.0
U
0.0
0.0
Hz
0001.0s
Frequency drop for quick deceleration setting
IPS F
U
0000.0V
Deceleration time of controlled stop operation setting
IPS DEC B054
Setting the OV-LAD stop level of controlled stop operation. Range is 0.0 to 1000.0
0000.0Hz
Parameters
Configuring Drive Parameters
B053
0000.0V
OV-LAD Stop level of controlled stop operation setting
Page 123
3−40
Miscellaneous Settings The miscellaneous settings include scaling factors, initialization modes, and others. This section covers some of the most important settings you may need to configure. B080: [AM] analog signal gain –This parameter allows you to scale the analog output [AM] relative to the monitored variable. Use together with C086 (AM offset adjustment) to get required performance.
B083: Carrier frequency adjustment – The internal switching frequency of the inverter circuitry (also called the chopper frequency). It is called the carrier frequency because the lower AC power frequency of the inverter “rides” the carrier. The faint, high-pitched sound you hear when the inverter is in Run Mode is characteristic of switching power supplies in general. The carrier frequency is adjustable from 2.0kHz to 12kHz. The audible sound decreases at the higher frequencies, but RFI noise and leakage current may be increased. Refer to the specification derating curves in Chapter 1 to determine the maximum allowable carrier frequency setting for your particular inverter and environmental conditions.
NOTE: The carrier frequency setting must stay within specified limits for invertermotor applications that must comply with particular regulatory agencies. For example, a European CE-approved application requires the inverter carrier to be 5kHz or less.
B084, B085: Initialization codes – These functions allow you to restore the factory default settings. Please refer to “Restoring Factory Default Settings” on page 6-8. B086: Frequency display scaling – You can convert the output frequency monitor on D001 to a scaled number (engineering units) monitored at function D007. for example, the motor may run a conveyor that is monitored in feet per minute. Use this formula: Scaled output frequency (D007) = Output frequency (D001) x Factor (B086)
Configuring Drive Parameters
Parameters
B082: Start frequency adjustment – When the inverter starts to run, the output frequency does not ramp from 0Hz. Instead, it steps directly to the start frequency (B082), and the ramp proceeds upward from there.
Page 124
3−41
Func. Code B080
B082
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
9
100.
100.
Start frequency adjustment
Sets the starting frequency for the inverter output, range is 0.5 to 9.9 Hz
U
0.5
0.5
Hz
Sets the PWM carrier (internal switching frequency), range is 2.0 to 12.0 kHz
U
3.0
3.0 kHz
Select the type of initialization to occur, three option codes: 00}Trip history clear 01}Parameter initialization 02} Trip history clear and parameter initialization
U
00
00
Select default parameter values for country on initialization, three option codes: 00}Japan 01}Europe 02}US
U
01
02
Specify a constant to scale the displayed frequency for D007 monitor, range is 0.1 to 99.9
9
1.0
1.0
Select whether the STOP key on the keypad is enabled, two option codes: 00}Enabled 01}Disabled
U
00
00 fmin B083
0000.5Hz
Carrier frequency setting
Carrier
Configuring Drive Parameters
B084
INIT Mode B085
EU
Frequency scaling conversion factor
Cnv Gain B087
TRP
Country for initialization
INIT Slct B086
0003.0
Initialization mode (parameters or trip history)
0001.0
STOP key enable
STP Key
ON
Parameters
“B” Function Name / Description SRW Display [AM] analog signal gain Adjust of analog output at terminal [AM], AM-Adj 00100% range is 0 to 255
Page 125
3−42
B091/B088: Stop Mode / Restart Mode Configuration – You can configure how the inverter performs a standard stop (each time Run FWD and REV signals turn OFF). Setting B091 determines whether the inverter will control the deceleration, or whether it will perform a free-run stop (coast to a stop). When using the free-run stop selection, it is imperative to also configure how you want the inverter to resume control of motor speed. Setting B088 determines whether the inverter will ensure the motor always resumes at 0 Hz, or whether the motor resumes from its current coasting speed (also called frequency pull-in). The run command may turn OFF briefly, allowing the motor to coast to a slower speed from which normal operation can resume.
Parameters
NOTE: Other events can cause (or be configured to cause) a free-run stop, such as power loss (see “Automatic Restart Mode” on page 3-32), or an intelligent input terminal [FRS] signal. If all free-run stop behavior is important to your application (such as HVAC), be sure to configure each event accordingly. An additional parameter further configures all instances of a free-run stop. Parameter B003, Retry Wait Time Before Motor Restart, sets the minimum time the inverter will free-run. For example, if B003 = 4 seconds (and B091=01) and the cause of the free-run stop lasts 10 seconds, the inverter will freerun (coast) for a total of 14 seconds before driving the motor again. The figure at below right describes how Frequency pull-in resume operates. After waiting the time set in B003, the inverter tries to catch the speed of the motor shaft and outputs the speed set in B011. At this time, if the motor current rises up to the value set in B030, the inverter decreases the frequency according to the deceleration time set in B029, and finally comes to the required speed. Following are the related parameters for this control. Code B011 B029 B030 B088 B091
Parameter contents Start freq to be used in case of freq matching restart Deceleration rate of frequency matching restart setting Current level of frequency matching restart setting Restart mode after FRS Stop mode selection
Zero frequency resume B091 = 01
Stop mode = free-run stop
B088 = 00
Resume from 0Hz
[FRS] t
0 Zero-frequency start
Motor speed t
0 Frequency pull-in resume B091 = 01
Stop mode = free-run stop
B088 = 01
Resume from current speed
[FRS] t
0 Wait time B003
B011
B029
Motor speed t
0 B030
Motor current RMS 0 t
Configuring Drive Parameters
In most applications a controlled deceleration is desirable, corresponding to B091=00. However, applications such as HVAC fan control will often use a free-run stop (B091=01). This practice decreases dynamic stress on system components, prolonging system life. In this case, you will typically set B088=01 in order to resume from the current speed after a free-run stop (see diagram down below: frequency pull-in resume). Note that using the default setting, B088=00, can cause trip events when the inverter attempts to force the load quickly to zero speed.
Page 126
3−43
“B” Function Func. Code B088
Name / SRW Display Restart mode after FRS
RUN FRS B091
STOP
DEC
Selects how the inverter resumes operation when free-run stop (FRS) is cancelled, two options: 00}Restart from 0Hz 01}Restart from frequency detected from real speed of motor (frequency pull-in) Select how the inverter stops the motor, two option codes: 00}DEC (decelerate to stop) 01}FRS (free-run to stop)
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
U
00
00
U
00
00
Parameters
Configuring Drive Parameters
ZST
Stop mode selection
Description
Page 127
3−44
B089: Monitor display select for networked inverter – When the X200 inverter is controlled via network, the inverter’s keypad display can still provide Monitor Mode. The D00x parameter selected by function B089 will be displayed on the keypad. See “Local Monitoring During Network Operation” on page 3-8 for more details. B092: Cooling Fan Control – You can select the performance of the cooling fan (if your inverter model includes a fan). This function controls whether the cooling fan stops or keeps on running after the inverter stops the motor. This can result in an additional energy saving and extends fan life.
B092
“B” Function Defaults Run Mode -FE -FU Name / Description Units Edit (EU) (USA) SRW Display Monitor display select for Selects the parameter displayed on the 01 01
9 networked inverter keypad display when the inverter is networked, 7 options: 01}Output frequency monitor 02}Output current monitor 03}Rotation direction monitor 04}Process variable (PV), PID feedback monitor 05}Intelligent input terminal status 06}Intelligent output terminal status PANEL d001 07}Scaled output frequency monitor Cooling fan control Selects when the fan is ON during 00
U 00 inverter operation, three options: 00}Fan is always ON 01}Fan is ON during run, OFF during FAN-CTRL OFF stop (5 minute delay from ON to OFF) 02}Fan is temperature controlled
Configuring Drive Parameters
Parameters
Func. Code B089
Page 128
3−45
The graph at right shows an inverter output profile that starts deceleration to a stop. At two different points during the deceleration, regenerative voltage elevates the DC bus level, exceeding the LADSTOP threshold set by B131.
t
Resumes decel t
0 Set decel time (F003) Actual decel time
When the Over-voltage LADSTOP feature is enabled by setting B130 = 01, the inverter stops the deceleration ramp in each case until the DC bus level is again less than the threshold value. When using the Over-voltage LADSTOP feature, please note the following: x When the feature is enabled (B130 = 01), the actual deceleration is sometimes longer than the value set by parameters F003/F203. x The over-voltage LADSTOP feature does not operate by maintaining a constant DC bus voltage. So it is still possible to have an over-voltage trip event during extreme deceleration. x If B131 is set lower than the normal DC bus voltage (when not in decel) by mistake, or if the inverter’s input voltage increases enough, then the inverter will apply LADSTOP (if enabled) all the time. In this case, the inverter can accelerate and run the motor, but it cannot decelerate. If you are not sure that B131 > DC bus voltage, measure the DC bus voltage in your installation and verify that the B131 value is higher.
Func. Code B130
B131
“B” Function Defaults Run Mode -FE -FU Name / Description Units Edit (EU) (USA) SRW Display Over-voltage LADSTOP Pauses deceleration ramp when DC bus U 00 00 enable voltage rises above threshold level, in order to avoid over-voltage trip. 00}Disable OVLADSTOP OFF 01}Enable Over-voltage LADSTOP Sets the threshold level for over-voltage 9 380/ 380/ V level LADSTOP. When the DC bus voltage is 760 760 above the threshold value, the inverter stops deceleration until the DC bus voltage is less than the threshold setting again. Two voltage ranges with 1V resolution: 330 to 395V (200V class) LADST LVL 0 0380V 660 to 790V (400V class)
Parameters
Configuring Drive Parameters
B130, B131: Over-voltage LAD Stop Enable B130 = 01 OV LADSTOP = Enable / Level – The over-voltage LADSTOP function monitors the DC bus voltage and DC bus actively changes the output frequency voltage profile to maintain the DC bus voltage B131 within settable limits. Although “LAD” refers to “linear acceleration / deceleration”, the inverter only “STOPs” the deceleration 0 ramp so that regenerative voltage will not cause the DC bus to rise enough to cause an Output over-voltage trip event. Note that frequency Stops decel acceleration is not affected.
Page 129
3−46
DC Bus AVR for Deceleration Settings This function is to achieve stable DC bus voltage in case of deceleration. DC bus voltage rises due to regeneration during deceleration. When this function is activated (B133=01), inverter controls the deceleration time so that the DC bus voltage not to go up to the overvoltage trip level, and leads to the trip-less operation during deceleration.
DC bus voltage Threshold voltage to start DC bus AVR (B134)
t Freq
Please note that the actual deceleration time may be longer in this case.
t
Parameters
“B” Function Func. Code B055
Name / SRW Display DC bus AVR for decel. P-gain
VpnP B056
VpnI B133
0000.2s
DC bus AVR selection
Vpn AVR B134
0000.2s
DC bus AVR for decel. I-time
OFF
Threshold voltage of DC bus AVR setting
Vpn LVL
00380V
Description
DC bus AVR
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
Proportional gain adjustment for DC bus AVR function. Range is: 0.2 to 5.0
9
0.2
0.2
Integration time adjustment for DC bus AVR function. Range is: 0.0 to 150.0
9
0.2
0.2 sec
00}Disabled 01}Enabled
U
00
00
Setting of threshold voltage of DC bus voltage to start DC bus AVR function. Range is: 200V class}330 to 395 400V class}660 to 790
U
380 /760
380 /760
V
Difference between OV LAD STOP and DC bus AVR This function is similar to OV LAD STOP (B130,B131) from the OV trip-less point of view. The DC bus AVR has the higher priority when both OV LAD STOP function and DC bus AVR function is set enabled. OV LAD STOP
DC bus AVR
Actual deceleration time
Short
Long
Fluctuation of the DC bus voltage
Big
Small
Please select the suitable function according to your system.
Configuring Drive Parameters
Normal operation
Page 130
3−47
Miscellaneous Settings (continued)
The graph at right shows an inverter output profile that starts acceleration to a constant speed. At two different points during the acceleration, motor current increases and exceeds the fixed level of Over-current Trip Suppression level.
B140 = 01
OC LADSTOP = Enabled
Motor current
Approx. 150% of the inverter rated current t
0 Output frequency
Stops accel
Resumes accel t
0 Set acc time (F002) Actual acc time
When the Over-current Trip Suppression feature is enabled by B140 = 01, the inverter stops the acceleration ramp in each case until the motor current level is again less than the threshold value, which is approximately 150% of the rated current of the inverter. When using the Over-current Trip Suppression feature, please note the following: x When the feature is enabled (B140 = 01), the actual acceleration may be longer than the value set by parameters F002/F202 in some cases. x The Over-current Trip Suppression feature does not operate by maintaining a constant motor current. So it is still possible to have an over-current trip event during extreme acceleration. B150: Carrier Mode – When the Carrier Mode is enabled (B150 = 01), the inverter detects the motor current and automatically reduces the carrier frequency when it rises up to a certain level. B151: Selection of Ready function – When the Ready function is enabled (B151 = 01), then the inverter outputs devices are ON even when the motor is stopped. Keeping all the internal power output components energized allows the idle time between the RUN command and actual PWM output to be shortened. HIGH VOLTAGE: When set RDY function ON, there will be a voltage appearing at motor output terminals U, V and W even if the motor is in stop mode. Never touch the inverter power terminal when the inverter is powered up.
Parameters
Configuring Drive Parameters
B140: Over-current Trip Suppression – The Over-current Trip Suppression function monitors the motor current and actively changes the output frequency profile to maintain the motor current within the limits. Although “LAD” refers to “linear acceleration / deceleration”, the inverter only “STOPs” the acceleration and deceleration ramp so that it will not cause an overcurrent trip event.