Page 131

3−48

“B” Function Func. Code B140

Name / SRW Display Over-current trip suppression

I-SUP Mode B150

OFF

Selection of RDY function

RDY-FUNC

OFF

Two option codes: 00}Disable 01}Enable Automatically reduces the carrier frequency as the ambient temperature increases. 00}Disable 01}Enable Select Ready function. 00}Disable 01}Enable

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

01

01

U

00

00

9

00

00

Configuring Drive Parameters

Parameters

OFF

Carrier mode

Cr-DEC B151

Description

Page 132

3−49

“C” Group: Intelligent Terminal Functions The five input terminals [1], [2], [3], [4], and [5] can be configured for any of 31 different functions. The next two tables show how to configure the five terminals. The inputs are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1. The inverter comes with default options for the five terminals. These settings are initially unique, each one having its own setting. Note that European and US versions have different default settings. You can use any option on any terminal, and even use the same option twice to create a logical OR (though usually not required).

Input Terminal Configuration Functions and Options – The function codes in the following table let you assign one of twenty eight options to any of the five logic inputs for the X200 inverters. The functions C001 through C005 configure the terminals [1] through [5] respectively. The “value” of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options. For example, if you set function C001=00, you have assigned option 00 (Forward Run) to terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.

Func. Code C001 C201

C002 C202

C003 C203

C004 C204

C005 C205

“C” Function Defaults Run Mode -FE -FU Name / Description Units Edit SRW Display (EU) (USA) Terminal [1] function Select input terminal [1] function, 30 00

U 00 IN-TM 1 FW options(see next section) [FW] [FW] Terminal [1] function, Select input terminal [1] function for U 2nd motor 2nd motor, 30 options(see next 2IN-TM 1 FW section) Terminal [2] function Select input terminal [2] function, 30 01

U 01 IN-TM 2 RV options(see next section) [RV] [RV] Terminal [2] function, Select input terminal [2] function for U 2nd motor 2nd motor, 30 options(see next 2IN-TM 2 RV section) Terminal [3] function Select input terminal [3] function, 30 16

U 02 IN-TM 3 AT options(see next section) [CF1] [AT] Terminal [3] function, Select input terminal [3] function for 16 U 02 2nd motor 2nd motor, 30 options(see next [CF1] [AT] 2IN-TM 3 AT section) Terminal [4] function Select input terminal [4] function, 30 13

U 03 [CF2] [USP] IN-TM 4 USP options(see next section) Terminal [4] function, Select input terminal [4] function for U 2nd motor 2nd motor, 30 options(see next 2IN-TM 2 USP section) Terminal [5] function Select input terminal [5] function, 30 18

U 18 [RS] [RS] IN-TM 5 2CH options(see next section) Terminal [5] function, Select input terminal [5] function for U 2nd motor 2nd motor, 30 options(see next IN-TM 5 2CH section)

Parameters

Configuring Drive Parameters

NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a thermistor device when PTC function (option code 19) is assigned to that terminal.

Page 133

3−50

The input logic conversion is programmable for each of the six inputs default to normally open (active high), but you can select normally closed (active low) in order to invert the sense of the logic.

Func. Code C011

C012

C013

Parameters

C015

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

00

00

U

00

00

U

00

00

U

00

01

U

00

00

NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.

Intelligent Input Terminal Overview Each of the five intelligent terminals may be assigned any of the options in the following table. When you program one of the option codes for terminal assignments C001 to C005, the respective terminal assumes the function role of that option code. The terminal functions have a symbol or abbreviation that we use to label a terminal using that function. For example, the “Forward Run” command is [FW]. The physical label on the terminal block connector is simply 1, 2, 3, 4, or 5. However, schematic examples in this manual also use the terminal symbol (such as [FW]) to show the assigned option. The option codes for C011 to C015 determines the active state of the logical input (active high or active low).

Configuring Drive Parameters

C014

“C” Function Name / Description SRW Display Terminal [1] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-1 NO 01}normally closed [NC] Terminal [2] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-2 NO 01}normally closed [NC] Terminal [3] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-3 NO 01}normally closed [NC] Terminal [4] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-4 NC 01}normally closed [NC] Terminal [5] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-5 NO 01}normally closed [NC]

Page 134

3−51

Input Function Summary Table – This table shows all thirty-one intelligent input functions at a glance. Detailed description of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4-8.

Terminal Symbol FW

01

RV

Reverse Run/Stop

02

CF1 *1

03

CF2

04

CF3

05

CF4

06

JG

Multi-speed Select, Bit 0 (LSB) Multi-speed Select, Bit 1 Multi-speed Select, Bit 2 Multi-speed Select, Bit 3 (MSB) jogging

07

DB

External DC braking

08

SET

Set (select) 2nd Motor Data

Function Name FORWARD Run/Stop

Description ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF

09

2CH

2-stage Acceleration and Deceleration

ON OFF

11

FRS

Free-run Stop

ON OFF

12

EXT

External Trip

ON OFF

13

USP

Unattended Start Protection

ON OFF

15

SFT

16

AT

18

RS

Software Lock

ON

Analog Input Voltage/Current Select Reset Inverter

OFF ON OFF ON OFF

Inverter is in Run Mode, motor runs forward Inverter is in Stop Mode, motor stops Inverter is in Run Mode, motor runs reverse Inverter is in Stop Mode, motor stops Binary encoded speed select, Bit 0, logical 1 Binary encoded speed select, Bit 0, logical 0 Binary encoded speed select, Bit 1, logical 1 Binary encoded speed select, Bit 1, logical 0 Binary encoded speed select, Bit 2, logical 1 Binary encoded speed select, Bit 2, logical 0 Binary encoded speed select, Bit 3, logical 1 Binary encoded speed select, Bit 3, logical 0 Inverter is in Run Mode, output to motor runs at jog parameter frequency Inverter is in Stop Mode DC braking will be applied during deceleration DC braking will not be applied The inverter uses 2nd motor parameters for generating frequency output to motor The inverter uses 1st (main) motor parameters for generating frequency output to motor Frequency output uses 2nd-stage acceleration and deceleration values Frequency output uses standard acceleration and deceleration values Causes output to turn OFF, allowing motor to free run (coast) to stop Output operates normally, so controlled deceleration stop motor When assigned input transitions OFF to ON, inverter latches trip event and displays E12 No trip event for ON to OFF, any recorded trip events remain in history until reset On powerup, the inverter will not resume a Run command (mostly used in the US) On powerup, the inverter will resume a Run command that was active before power loss The keypad and remote programming devices are prevented from changing parameters The parameters may be edited and stored Refer to “Analog Input Settings” on page 3-13. The trip condition is reset, the motor output is turned OFF, and powerup reset is asserted Normal power-ON operation

Parameters

Configuring Drive Parameters

Input Function Summary Table Option Code 00

Page 135

3−52

Input Function Summary Table Option Code 19

Terminal Symbol PTC

Function Name PTC thermistor Thermal Protection

Description ANLG

OPEN 20

STA

21

STP

22

F/R

Start (3-wire interface) Stop (3-wire interface) FWD, REV (3-wire interface)

ON OFF ON OFF ON

Parameters

23

PID

PID Disable

ON

OFF

24

PIDC

PID Reset

27

UP

28

DWN

29

UDC

Remote Control UP Function (motorized speed pot.) Remote Control Down Function (motorized speed pot.) Remote Control Data Clearing

31

OPE

Operator Control

ON

OFF ON OFF ON OFF ON

OFF ON

OFF

Configuring Drive Parameters

OFF

When a thermistor is connected to terminal [5] and [L], the inverter checks for over-temperature and will cause trip event and turn OFF output to motor A disconnect of the thermistor causes a trip event, and the inverter turns OFF the motor Starts the motor rotation No change to present motor status Stops the motor rotation No change to present motor status Selects the direction of motor rotation: ON = FWD. While the motor is rotating, a change of F/R will start a deceleration, followed by a change in direction Selects the direction of motor rotation: OFF = REV. While the motor is rotating, a change of F/R will start a deceleration, followed by a change in direction Temporarily disables PID loop control. Inverter output turns OFF as long as PID Enable is active (A071=01) Has no effect on PID loop operation, which operates normally if PID Enable is active (A071=01) Resets the PID loop controller. The main consequence is that the integrator sum is forced to zero No effect on PID controller Accelerates (increases output frequency) motor from current frequency Output to motor operates normally Decelerates (decreases output frequency) motor from current frequency Output to motor operates normally Clears the UP/DWN frequency memory by forcing it to equal the set frequency parameter F001. Setting C101 must be set=00 to enable this function to work UP/DWN frequency memory is not changed Forces the source of the output frequency setting A001 and the source of the Run command A002 to be from the digital operator Source of output frequency set by A001 and source of Run command set by A002 is used

Page 136

3−53

Input Function Summary Table Option Code 50

Terminal Symbol ADD

51

F-TM

Function Name ADD frequency enable Force Terminal Mode

Description ON OFF ON

52

RDY *

Inverter Ready

ON

53

SP-SET

Special set

OFF ON

OFF 64

EMR *

255

-

Emergency Stop ON

(No function)

OFF ON OFF

NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F001 or change the value of F001 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F001 during Run Mode, lease monitor D001 instead of F001. HIGH VOLTAGE: When set RDY function ON, there will be a voltage appears at motor output terminals U, V and W even if the motor is in stop mode. So never touch the inverter power terminals even the motor is not running. NOTE: The EMR is not programmable, but will be assigned automatically when the hardware switch S8 is made ON. When the EMR is assigned, function assignments of terminal 3, 4 and 5 are automatically changed as follows. Please also refer to Emergency Stop paragraph. Emergency Stop switch condition Emergency Stop switch Emergency Stop switch S8 = ON S8 = ON Æ OFF

Terminal Number

Default setting Emergency Stop switch S8 = OFF

1

FW

FW

FW

2

RV

RV

RV

3

CF1

4

CF2 [US ver. :USP]

5

RS (PTC assignable)

EMR [HW based for 1b input] RS [HW based for 1a input] - (No func.)

- (No func.) RS [Normal 1a] - (No func.)

Parameters

Configuring Drive Parameters

OFF

Adds the A145 (add frequency) value to the output frequency Does not add the A145 value to the output frequency Force inverter to use input terminals for output frequency and Run command sources Source of output frequency set by A001 and source of Run command set by A002 is used To charge up the internal boot-strap capacitor so to start motor immediately after the RUN command is given. Inverter operates normal. The inverter uses 2nd motor parameters for generating frequency output to motor. The selection of 1st or 2nd motor is available during Stop Mode or Run Mode. The inverter uses 1st (main) motor parameters for generating frequency output to motor. Inverter recognizes that the emergency signal is given, and shuts off the output. Refer to “Safe Stop” on page 4-32. Inverter operates normal (input ignored) (input ignored)

Page 137

3−54

Output Terminal Configuration The inverter provides configuration for logic (discrete) and analog outputs, shown in the table below. “C” Function Func. Code C021

Name / SRW Display Terminal [11] function

OUT-TM 11 C026

Parameters

01 01 [FA1] [FA1]

U

05 [AL]

AL

12 programmable functions available for logic (discrete) outputs (see next section)

U

00 00 [freq] [freq]

F

Two available functions: 00}motor speed 01}motor current (see after next section)

AM signal selection

05 [AL]

The output logic conversion is programmable for terminal [11] and the alarm relay terminal. The open-collector output terminal [11] defaults to normally open (active low), but you can select normally closed (active high) for the terminal in order to invert the sense of the logic. You can invert the logical sense of the alarm relay output as well. “C” Function Func. Code C031

Name / SRW Display Terminal [11] active state

O/C-11 C036

Description

NO

Alarm relay active state

O/C-RY

NC

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

Select logic conversion, two option codes: 00}normally open [NO] 01}normally closed [NC]

U

00

00

Select logic conversion, two option codes: 00}normally open [NO] 01}normally closed [NC]

U

01

01

Configuring Drive Parameters

U

FA1

AM-KIND

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

12 programmable functions available for logic (discrete) outputs (see next section)

Alarm relay terminal function

OUT-TM RY C028

Description

Page 138

3−55

Output Function Summary Table – This table shows all twelve functions for the logical outputs (terminals [11] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 4-34.

Terminal Symbol RUN

01

FA1

02

FA2

Frequency Arrival Type ON 2–Over frequency OFF

03

OL

Overload Advance Notice Signal

04

OD

Output Deviation for PID Control

Function Name

Description

Run Signal

ON OFF Frequency Arrival Type ON 1–Constant Speed OFF

ON OFF ON OFF

05

AL

Alarm Signal

ON OFF

06

07

Dc

FBV

Analog Input Disconnect Detect PID Second Stage Output

ON OFF ON

OFF

08

NDc

Network Detection Signal

ON OFF

09

LOG

Logic Output Function

10

ODc

Communication option error

43

LOC

Low load detection

ON OFF ON OFF ON OFF

When the inverter is in Run Mode When the inverter is in Stop Mode When output to motor is at the set frequency When output to motor is OFF, or in any acceleration or deceleration ramp When output to motor is at or above the set frequency, even if in accel. or decel rams When output to motor is OFF, or at a level below the set frequency When output current is more than the set threshold for the overload signal When output current is less than the set threshold for the deviation signal When PID error is more than the set threshold for the deviation signal When PID error is less than the set threshold for the deviation signal When an alarm signal has occurred and has not been cleared When no alarm has occurred since the last cleaning of alarm(s) When the [O] input value < B082 setting (signal loss detected), or the [OI] input current < 4mA When no signal loss is detected Transitions to ON when the inverter is in RUN Mode and the PID Process Variable (PV) is less than the Feedback Low Limit (C053) Transitions to OFF when the PID Process Variable (PV) exceeds the PID High Limit (C052), and transitions to OFF when the inverter goes from Run Mode to Stop Mode When the communications watchdog timer (period specified by C077) has time out When the communications watchdog timer is satisfied by regular communications activity When the Boolean operation specified by C143 has a logical “1” result When the Boolean operation specified by C143 has a logical “0” result No communication between communication option is detected during a time set in P044 Communication is normal Motor current is less than the set value of C039 Motor current is not less than the set value of C039

Parameters

Configuring Drive Parameters

Output Function Summary Table Option Code 00

Page 139

3−56

Analog Function Summary Table – This table shows both functions for the analog voltage output [AM] terminal, configured by C028. More information on using and calibrating the [AM] output terminal is in “Analog Output Operation” on page 4-55. Analog Function Summary Table Option Code 00

Description

Analog Frequency Monitor Analog Current Output Monitor

Inverter output frequency.

Range

0 to max. frequency in Hz Motor current (% of maximum rated output 0 to 200% current)

Configuring Drive Parameters

Parameters

01

Function Name

Page 140

3−57

Low Load Detection Parameters

This function is for generating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).

Func. Code C038

C039

Output current C039 t

0 [LOC] output 1 0 t

“C” Function Name / Description SRW Display Output mode of low load Three option codes: detection signal 00}Disabled 01}During acceleration, deceleration and constant speed LOC MODE CRT 02}During constant speed only

Defaults Run Mode -FE -FU Units Edit (EU) (USA)

U

01

01

Low load detection level

U

INV INV rated rated curr. curr.

A

LOC LVL

02.60A

Set the level of low load detection, range is 0.0 to 2.0*inverter rated current

Parameters

Configuring Drive Parameters

The following parameters work in conjunction with the intelligent output function, when configured. The output mode parameter (C038) sets the mode of the detection at which the low load detection signal [LOC] turns ON. Three kinds of modes can be selected. The detection level parameter (C039) is to set the level of the low load.