The text of a manual · part 14 of 31
X200 Series Inverter Instruction Manual, pages 131 to 140
Pages 131 to 140 of 305
The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Hitachi X200 Series
Page 131
3−48
“B” Function Func. Code B140
Name / SRW Display Over-current trip suppression
I-SUP Mode B150
OFF
Selection of RDY function
RDY-FUNC
OFF
Two option codes: 00}Disable 01}Enable Automatically reduces the carrier frequency as the ambient temperature increases. 00}Disable 01}Enable Select Ready function. 00}Disable 01}Enable
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
U
01
01
U
00
00
9
00
00
Configuring Drive Parameters
Parameters
OFF
Carrier mode
Cr-DEC B151
Description
Page 132
3−49
“C” Group: Intelligent Terminal Functions The five input terminals [1], [2], [3], [4], and [5] can be configured for any of 31 different functions. The next two tables show how to configure the five terminals. The inputs are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1. The inverter comes with default options for the five terminals. These settings are initially unique, each one having its own setting. Note that European and US versions have different default settings. You can use any option on any terminal, and even use the same option twice to create a logical OR (though usually not required).
Input Terminal Configuration Functions and Options – The function codes in the following table let you assign one of twenty eight options to any of the five logic inputs for the X200 inverters. The functions C001 through C005 configure the terminals [1] through [5] respectively. The “value” of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options. For example, if you set function C001=00, you have assigned option 00 (Forward Run) to terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.
Func. Code C001 C201
C002 C202
C003 C203
C004 C204
C005 C205
“C” Function Defaults Run Mode -FE -FU Name / Description Units Edit SRW Display (EU) (USA) Terminal [1] function Select input terminal [1] function, 30 00
U 00 IN-TM 1 FW options(see next section) [FW] [FW] Terminal [1] function, Select input terminal [1] function for U 2nd motor 2nd motor, 30 options(see next 2IN-TM 1 FW section) Terminal [2] function Select input terminal [2] function, 30 01
U 01 IN-TM 2 RV options(see next section) [RV] [RV] Terminal [2] function, Select input terminal [2] function for U 2nd motor 2nd motor, 30 options(see next 2IN-TM 2 RV section) Terminal [3] function Select input terminal [3] function, 30 16
U 02 IN-TM 3 AT options(see next section) [CF1] [AT] Terminal [3] function, Select input terminal [3] function for 16 U 02 2nd motor 2nd motor, 30 options(see next [CF1] [AT] 2IN-TM 3 AT section) Terminal [4] function Select input terminal [4] function, 30 13
U 03 [CF2] [USP] IN-TM 4 USP options(see next section) Terminal [4] function, Select input terminal [4] function for U 2nd motor 2nd motor, 30 options(see next 2IN-TM 2 USP section) Terminal [5] function Select input terminal [5] function, 30 18
U 18 [RS] [RS] IN-TM 5 2CH options(see next section) Terminal [5] function, Select input terminal [5] function for U 2nd motor 2nd motor, 30 options(see next IN-TM 5 2CH section)
Parameters
Configuring Drive Parameters
NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a thermistor device when PTC function (option code 19) is assigned to that terminal.
Page 133
3−50
The input logic conversion is programmable for each of the six inputs default to normally open (active high), but you can select normally closed (active low) in order to invert the sense of the logic.
Func. Code C011
C012
C013
Parameters
C015
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
U
00
00
U
00
00
U
00
00
U
00
01
U
00
00
NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.
Intelligent Input Terminal Overview Each of the five intelligent terminals may be assigned any of the options in the following table. When you program one of the option codes for terminal assignments C001 to C005, the respective terminal assumes the function role of that option code. The terminal functions have a symbol or abbreviation that we use to label a terminal using that function. For example, the “Forward Run” command is [FW]. The physical label on the terminal block connector is simply 1, 2, 3, 4, or 5. However, schematic examples in this manual also use the terminal symbol (such as [FW]) to show the assigned option. The option codes for C011 to C015 determines the active state of the logical input (active high or active low).
Configuring Drive Parameters
C014
“C” Function Name / Description SRW Display Terminal [1] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-1 NO 01}normally closed [NC] Terminal [2] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-2 NO 01}normally closed [NC] Terminal [3] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-3 NO 01}normally closed [NC] Terminal [4] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-4 NC 01}normally closed [NC] Terminal [5] active state Select logic conversion, two option codes: 00}normally open [NO] O/C-5 NO 01}normally closed [NC]
Page 134
3−51
Input Function Summary Table – This table shows all thirty-one intelligent input functions at a glance. Detailed description of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4-8.
Terminal Symbol FW
01
RV
Reverse Run/Stop
02
CF1 *1
03
CF2
04
CF3
05
CF4
06
JG
Multi-speed Select, Bit 0 (LSB) Multi-speed Select, Bit 1 Multi-speed Select, Bit 2 Multi-speed Select, Bit 3 (MSB) jogging
07
DB
External DC braking
08
SET
Set (select) 2nd Motor Data
Function Name FORWARD Run/Stop
Description ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
09
2CH
2-stage Acceleration and Deceleration
ON OFF
11
FRS
Free-run Stop
ON OFF
12
EXT
External Trip
ON OFF
13
USP
Unattended Start Protection
ON OFF
15
SFT
16
AT
18
RS
Software Lock
ON
Analog Input Voltage/Current Select Reset Inverter
OFF ON OFF ON OFF
Inverter is in Run Mode, motor runs forward Inverter is in Stop Mode, motor stops Inverter is in Run Mode, motor runs reverse Inverter is in Stop Mode, motor stops Binary encoded speed select, Bit 0, logical 1 Binary encoded speed select, Bit 0, logical 0 Binary encoded speed select, Bit 1, logical 1 Binary encoded speed select, Bit 1, logical 0 Binary encoded speed select, Bit 2, logical 1 Binary encoded speed select, Bit 2, logical 0 Binary encoded speed select, Bit 3, logical 1 Binary encoded speed select, Bit 3, logical 0 Inverter is in Run Mode, output to motor runs at jog parameter frequency Inverter is in Stop Mode DC braking will be applied during deceleration DC braking will not be applied The inverter uses 2nd motor parameters for generating frequency output to motor The inverter uses 1st (main) motor parameters for generating frequency output to motor Frequency output uses 2nd-stage acceleration and deceleration values Frequency output uses standard acceleration and deceleration values Causes output to turn OFF, allowing motor to free run (coast) to stop Output operates normally, so controlled deceleration stop motor When assigned input transitions OFF to ON, inverter latches trip event and displays E12 No trip event for ON to OFF, any recorded trip events remain in history until reset On powerup, the inverter will not resume a Run command (mostly used in the US) On powerup, the inverter will resume a Run command that was active before power loss The keypad and remote programming devices are prevented from changing parameters The parameters may be edited and stored Refer to “Analog Input Settings” on page 3-13. The trip condition is reset, the motor output is turned OFF, and powerup reset is asserted Normal power-ON operation
Parameters
Configuring Drive Parameters
Input Function Summary Table Option Code 00
Page 135
3−52
Input Function Summary Table Option Code 19
Terminal Symbol PTC
Function Name PTC thermistor Thermal Protection
Description ANLG
OPEN 20
STA
21
STP
22
F/R
Start (3-wire interface) Stop (3-wire interface) FWD, REV (3-wire interface)
ON OFF ON OFF ON
Parameters
23
PID
PID Disable
ON
OFF
24
PIDC
PID Reset
27
UP
28
DWN
29
UDC
Remote Control UP Function (motorized speed pot.) Remote Control Down Function (motorized speed pot.) Remote Control Data Clearing
31
OPE
Operator Control
ON
OFF ON OFF ON OFF ON
OFF ON
OFF
Configuring Drive Parameters
OFF
When a thermistor is connected to terminal [5] and [L], the inverter checks for over-temperature and will cause trip event and turn OFF output to motor A disconnect of the thermistor causes a trip event, and the inverter turns OFF the motor Starts the motor rotation No change to present motor status Stops the motor rotation No change to present motor status Selects the direction of motor rotation: ON = FWD. While the motor is rotating, a change of F/R will start a deceleration, followed by a change in direction Selects the direction of motor rotation: OFF = REV. While the motor is rotating, a change of F/R will start a deceleration, followed by a change in direction Temporarily disables PID loop control. Inverter output turns OFF as long as PID Enable is active (A071=01) Has no effect on PID loop operation, which operates normally if PID Enable is active (A071=01) Resets the PID loop controller. The main consequence is that the integrator sum is forced to zero No effect on PID controller Accelerates (increases output frequency) motor from current frequency Output to motor operates normally Decelerates (decreases output frequency) motor from current frequency Output to motor operates normally Clears the UP/DWN frequency memory by forcing it to equal the set frequency parameter F001. Setting C101 must be set=00 to enable this function to work UP/DWN frequency memory is not changed Forces the source of the output frequency setting A001 and the source of the Run command A002 to be from the digital operator Source of output frequency set by A001 and source of Run command set by A002 is used
Page 136
3−53
Input Function Summary Table Option Code 50
Terminal Symbol ADD
51
F-TM
Function Name ADD frequency enable Force Terminal Mode
Description ON OFF ON
52
RDY *
Inverter Ready
ON
53
SP-SET
Special set
OFF ON
OFF 64
EMR *
255
-
Emergency Stop ON
(No function)
OFF ON OFF
NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F001 or change the value of F001 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F001 during Run Mode, lease monitor D001 instead of F001. HIGH VOLTAGE: When set RDY function ON, there will be a voltage appears at motor output terminals U, V and W even if the motor is in stop mode. So never touch the inverter power terminals even the motor is not running. NOTE: The EMR is not programmable, but will be assigned automatically when the hardware switch S8 is made ON. When the EMR is assigned, function assignments of terminal 3, 4 and 5 are automatically changed as follows. Please also refer to Emergency Stop paragraph. Emergency Stop switch condition Emergency Stop switch Emergency Stop switch S8 = ON S8 = ON Æ OFF
Terminal Number
Default setting Emergency Stop switch S8 = OFF
1
FW
FW
FW
2
RV
RV
RV
3
CF1
4
CF2 [US ver. :USP]
5
RS (PTC assignable)
EMR [HW based for 1b input] RS [HW based for 1a input] - (No func.)
- (No func.) RS [Normal 1a] - (No func.)
Parameters
Configuring Drive Parameters
OFF
Adds the A145 (add frequency) value to the output frequency Does not add the A145 value to the output frequency Force inverter to use input terminals for output frequency and Run command sources Source of output frequency set by A001 and source of Run command set by A002 is used To charge up the internal boot-strap capacitor so to start motor immediately after the RUN command is given. Inverter operates normal. The inverter uses 2nd motor parameters for generating frequency output to motor. The selection of 1st or 2nd motor is available during Stop Mode or Run Mode. The inverter uses 1st (main) motor parameters for generating frequency output to motor. Inverter recognizes that the emergency signal is given, and shuts off the output. Refer to “Safe Stop” on page 4-32. Inverter operates normal (input ignored) (input ignored)
Page 137
3−54
Output Terminal Configuration The inverter provides configuration for logic (discrete) and analog outputs, shown in the table below. “C” Function Func. Code C021
Name / SRW Display Terminal [11] function
OUT-TM 11 C026
Parameters
01 01 [FA1] [FA1]
U
05 [AL]
AL
12 programmable functions available for logic (discrete) outputs (see next section)
U
00 00 [freq] [freq]
F
Two available functions: 00}motor speed 01}motor current (see after next section)
AM signal selection
05 [AL]
The output logic conversion is programmable for terminal [11] and the alarm relay terminal. The open-collector output terminal [11] defaults to normally open (active low), but you can select normally closed (active high) for the terminal in order to invert the sense of the logic. You can invert the logical sense of the alarm relay output as well. “C” Function Func. Code C031
Name / SRW Display Terminal [11] active state
O/C-11 C036
Description
NO
Alarm relay active state
O/C-RY
NC
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
Select logic conversion, two option codes: 00}normally open [NO] 01}normally closed [NC]
U
00
00
Select logic conversion, two option codes: 00}normally open [NO] 01}normally closed [NC]
U
01
01
Configuring Drive Parameters
U
FA1
AM-KIND
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
12 programmable functions available for logic (discrete) outputs (see next section)
Alarm relay terminal function
OUT-TM RY C028
Description
Page 138
3−55
Output Function Summary Table – This table shows all twelve functions for the logical outputs (terminals [11] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 4-34.
Terminal Symbol RUN
01
FA1
02
FA2
Frequency Arrival Type ON 2–Over frequency OFF
03
OL
Overload Advance Notice Signal
04
OD
Output Deviation for PID Control
Function Name
Description
Run Signal
ON OFF Frequency Arrival Type ON 1–Constant Speed OFF
ON OFF ON OFF
05
AL
Alarm Signal
ON OFF
06
07
Dc
FBV
Analog Input Disconnect Detect PID Second Stage Output
ON OFF ON
OFF
08
NDc
Network Detection Signal
ON OFF
09
LOG
Logic Output Function
10
ODc
Communication option error
43
LOC
Low load detection
ON OFF ON OFF ON OFF
When the inverter is in Run Mode When the inverter is in Stop Mode When output to motor is at the set frequency When output to motor is OFF, or in any acceleration or deceleration ramp When output to motor is at or above the set frequency, even if in accel. or decel rams When output to motor is OFF, or at a level below the set frequency When output current is more than the set threshold for the overload signal When output current is less than the set threshold for the deviation signal When PID error is more than the set threshold for the deviation signal When PID error is less than the set threshold for the deviation signal When an alarm signal has occurred and has not been cleared When no alarm has occurred since the last cleaning of alarm(s) When the [O] input value < B082 setting (signal loss detected), or the [OI] input current < 4mA When no signal loss is detected Transitions to ON when the inverter is in RUN Mode and the PID Process Variable (PV) is less than the Feedback Low Limit (C053) Transitions to OFF when the PID Process Variable (PV) exceeds the PID High Limit (C052), and transitions to OFF when the inverter goes from Run Mode to Stop Mode When the communications watchdog timer (period specified by C077) has time out When the communications watchdog timer is satisfied by regular communications activity When the Boolean operation specified by C143 has a logical “1” result When the Boolean operation specified by C143 has a logical “0” result No communication between communication option is detected during a time set in P044 Communication is normal Motor current is less than the set value of C039 Motor current is not less than the set value of C039
Parameters
Configuring Drive Parameters
Output Function Summary Table Option Code 00
Page 139
3−56
Analog Function Summary Table – This table shows both functions for the analog voltage output [AM] terminal, configured by C028. More information on using and calibrating the [AM] output terminal is in “Analog Output Operation” on page 4-55. Analog Function Summary Table Option Code 00
Description
Analog Frequency Monitor Analog Current Output Monitor
Inverter output frequency.
Range
0 to max. frequency in Hz Motor current (% of maximum rated output 0 to 200% current)
Configuring Drive Parameters
Parameters
01
Function Name
Page 140
3−57
Low Load Detection Parameters
This function is for generating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).
Func. Code C038
C039
Output current C039 t
0 [LOC] output 1 0 t
“C” Function Name / Description SRW Display Output mode of low load Three option codes: detection signal 00}Disabled 01}During acceleration, deceleration and constant speed LOC MODE CRT 02}During constant speed only
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
U
01
01
Low load detection level
U
INV INV rated rated curr. curr.
A
LOC LVL
02.60A
Set the level of low load detection, range is 0.0 to 2.0*inverter rated current
Parameters
Configuring Drive Parameters
The following parameters work in conjunction with the intelligent output function, when configured. The output mode parameter (C038) sets the mode of the detection at which the low load detection signal [LOC] turns ON. Three kinds of modes can be selected. The detection level parameter (C039) is to set the level of the low load.