Page 141
3−58
Output Function Adjustment Parameters
The frequency arrival signal, [FA1] or [FA2], is intended to indicate when the inverter output has reached (arrived at) the target frequency. You can adjust the timing of the leading and trailing edges of the signal via two parameters specified to acceleration ad deceleration ramps, C042 and C043. The Error for the PID loop is the magnitude (absolute value) of the difference between the Set point (desired value) and Process Variable (actual value). The PID output deviation signal [OD] (output terminal function option code 04) indicates when the error magnitude has exceeded a magnitude you define.
Output current C041 t
0 [OL] output 1 0 t
Output freq. C043
C042 t [FA2] output 1 0 t
PID Error (PV-SP) deviation threshold Output C044 t [OD] output 1 0 t
Configuring Drive Parameters
Parameters
The following parameters work in conjunction with the intelligent output function, when configured. The overload level parameter (C041) sets the motor current level at which the overload signal [OL] turns ON. The range of setting is from 0% to 200% of the rated current for the inverter. This function is for generating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).
Page 142
3−59
“C” Function Func. Code C041
Name / SRW Display Overload level setting
OV LVL C241
2OV LVL C042
0100.0%
PID FBV function variable low limit
PID LtL
0000.0%
Configuring Drive Parameters
Sets the overload signal level between 0% and 200% (from 0 to two time the rated current of the inverter) Sets the overload signal level between 0% and 200% (from 0 to two time the rated current of the inverter) Sets the frequency arrival setting threshold for the output frequency during acceleration, range is 0.0 to 400.0 Hz Sets the frequency arrival setting threshold for the output frequency during deceleration, range is 0.0 to 400.0 Hz Sets the allowable PID loop error magnitude (absolute value), SP-PV, range is 0.0 to 100% When the PV exceeds this value, the PID loop turns OFF the PID second stage output, range is 0.0 to 100% When the PV goes below this value, the PID loop turns ON the PID second stage output, range is 0.0 to 100%
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
U
Rated current for each inverter model
A
U
Rated current for each inverter model
A
U
0.0
0.0
Hz
U
0.0
0.0
Hz
U
3.0
3.0
%
U
100.0 100.0
%
U
0.0
%
0.0
Parameters
003.0%
PID FBV function high limit
PID LtU C053
0000.0Hz
PID deviation level setting
ARV PID C052
0000.0Hz
Frequency arrival setting for deceleration
ARV DEC C044
001.60A
Frequency arrival setting for acceleration
ARV ACC C043
001.60A
Overload level setting, 2nd motor
Description
Page 143
3−60
Network Communications Settings The following table lists parameters that configure the inverter’s serial communications port. The settings affect how the inverter communication with a digital operator (such as SRW-0EX), as well as a ModBus network (for networked inverter applications). The settings cannot be edited via the network, in order to ensure network reliability. Refer to “ModBus Network Communications” on page B-1 for more information on controlling any monitoring your inverter from a network.
Func. Code C070
Parameters
C072 C074
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
Communication parity selection
COM PRTY C075
COM STP C076
None
Communication error timeout
COM ETIM C078
000.00s
Communication wait time
COM Wait
02
02
U
06
04 baud
U
1.
1.
Three option codes: 00}No parity 01}Even parity 02}Odd parity
U
00
00
Range is 1 to 2
U
1
1 bit
Selects inverter response to communications error. Five options: 00}Trip (Error code E60) 01}Decelerate to a stop and trip (Error code E60) 02}Disable 03}Free run stop (coasting) 04}Decelerate to a stop Sets the communications watchdog timer period. Range is 0.00 to 99.99 sec Time the inverter waits after receiving a message before it transmits. Range is 0. to 1000. ms
U
02
02
U
0.00
0.00 sec.
U
0.
0.
msec.
1BIT
Communication error select
COM ESlct C077
NON
Communication stop bit selection
U
00000ms
Configuring Drive Parameters
C071
“C” Function Name / Description SRW Display Selection of OPE / ModBus Two option codes: 02}OPE or option PARAM REM 03}ModBus (485) Communication speed Three option codes: selection 04}4800 bps 05}9600 bps COM BAU 4800 06}19200 bps Node allocation Set the address of the inverter on COM ADR 00001 the network. Range is 1 to 32
Page 144
3−61
Analog Signal Calibration Settings The functions in the following table configure the signals for the analog input terminals. Note that these settings do not change the current/voltage or sink/source characteristics – only the zero and span (scaling) of the signals.
Freq setpoint Max. freq 200%
50%
C082
“C” Function Name / Description SRW Display O input span calibration Scale factor between the external frequency command on terminals L–O (voltage input) and the frequency output, O-ADJ 0100.0% range is 0.0 to 200% OI input span calibration
OI-ADJ C086
0100.0%
AM offset calibration
AM OFFST
0000.0V
Scale factor between the external frequency command on terminals L–OI (voltage input) and the frequency output, range is 0.0 to 200% Offset adjustment of AM output. Range is 0.0 to 10.0 Adjust together with B080 (AM gain adjustment) - See page 3-40, 4-55 for details.
5V, 12mA
10V, 20mA
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
9
100.0 100.0
%
9
100.0 100.0
%
9
0.0
V
0.0
NOTE: When you restore factory default settings, the values will change to those listed above. Be sure to manually reconfigure the values for your application, if needed, after restoring factory defaults.
Parameters
Configuring Drive Parameters
0 0V, 4mA
Func. Code C081
100%
Max. freq /2
Page 145
3−62
Miscellaneous Functions The following table contains miscellaneous functions not in other function groups. “C” Function Func. Code C091
Name / SRW Display Debug mode enable *
DBG Slct C101
OFF
Up/Down memory mode selection
NO-STR
Parameters
Reset selection
RS Slct
ON
Displays debug parameters. Two option codes: 00}Disable 01}Enable <Do not set> (for factory use) Controls speed setpoint for the inverter after power sycle. Two option codes: 00}Clear last frequency (return to default frequency F001) 01}Keep last frequency adjusted by UP/DWN Determines response to Reset input [RS]. Three option codes: 00}Cancel trip state at input signal ON transition, stops inverter if in Run Mode 01}Cancel trip state at signal OFF transition, stops inverter if in Run Mode 02}Cancel trip state at input ON transition, no effect if in Run Mode
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
9
00
00
U
00
00
U
00
00
CAUTION: Do not change Debug mode for safety reasons. Otherwise unexpected performances may occur.
Configuring Drive Parameters
UP/DWN C102
Description
Page 146
3−63
Output Logic and Timing Logic Output Function – The inverter has a built-in logic output feature. You can select any two of the other nine intelligent output options for internal inputs. Then, configure the logic function to apply the logical AND, OR, or XOR (exclusive OR) operates as desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021, or C026 to route the logical result to terminal [11] or the relay terminals. Intelligent outputs used as internal inputs: RUN, FA1, FA2, OL, OD, AL, Dc, FBV, NDc, ODc, LOC
C021 C141
11
Input A
C026
AL0
RUN, FA1, FA2, OL, OD, AL, Dc, FBV, NDc, ODc, LOC
Input B
AL2
The following table shows all four possible input combinations with each of the three available logic operations. Input Status A B 0 0 0 1 1 0 1 1
[LOG] Output State AND OR XOR 0 0 0 0 1 1 0 1 1 1 1 0 “C” Function
Func. Code C141
Name / SRW Display Input A select for logic output
LogicOut1 C142
U
00
00
U
01
01
FA1
U
00
00
AND
Applies a logic function to calculate [LOG] output state, Three options: 00}[LOG] = A AND B 01}[LOG] = A OR B 02}[LOG] = A XOR B
RUN
Logic function select
LogicOPE
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
11 programmable functions available for logic (discrete) outputs 00}RUN 01}FA1 02}FA2 03}OL 04}OD 05}AL 06}Dc 07}FBV 08}NDc 09}LOG 10}ODc 43}LOC
Input B select for logic output
LogicOut2 C143
Description
Parameters
Configuring Drive Parameters
AL1
Logic function AND, OR, XOR
C142
Page 147
3−64
Output Signal ON/OFF Delay Function – Intelligent outputs including terminals [11] and the output relay, have configurable signal transition delays. Each output can delay either the OFF-to-ON or ON-to-OFF transitions, or both. Signal transition delays are variable from 0.1 to 100.0 seconds. This feature is useful in applications that must tailor inverter output signals to meet timing requirements of certain external devices.
Func. Code C144
“C” Function Name / Description SRW Display Terminal [11] ON delay Range is 0.0 to 100.0 sec.
DLAY 11 C145
C148 sec.
Range is 0.0 to 100.0 sec.
U
0.0
0.0 sec.
Range is 0.0 to 100.0 sec.
U
0.0
0.0 sec.
Range is 0.0 to 100.0 sec.
U
0.0
0.0 sec.
000.0s
NOTE: If you are using the output terminal OFF delay feature (any of C145, C149 > 0.0 sec.), the [RS] (reset) terminal affects the ON-to-OFF transition slightly. Normally (with using OFF delays), the [RS] input causes the motor output and the logic outputs to turn OFF together, immediately. However, when any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an additional 1 sec. period (approximate) before turning OFF.
Configuring Drive Parameters
Parameters
0.0
000.0s
Output relay OFF delay
HOLD RY
0.0
000.0s
Output relay ON delay
DLAY RY C149
U
000.0s
Terminal [11] OFF delay
HOLD 11
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
Page 148
3−65
“H” Group: Motor Constants Functions The “H” Group parameters configure the inverter for the motor characteristics. You must manually set H003 and H004 values to match the motor. Parameter H006 is factory-set. If you want to reset the parameters to the factory default settings, use the procedure in “Restoring Factory Default Settings” on page 68. Use A044 to select the torque control algorithm as shown in the diagram.
Inverter Torque Control Algorithms A044 V/f control, constant torque
Output V/f control, variable torque
Name / SRW Display Motor capacity
AUX K H203
0.4 kW
Motor capacity, 2nd motor
2AUXK H004
0.4 kW
Motor poles setting
AUX P H204
U
Ten selections: 0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.7/ 5.5/7.5
U
Four selections: 2/4/6/8
U
4
4 poles
Four selections: 2/4/6/8
U
4
4 poles
Motor constant (factory set), range is 0 to 255
9
100
100
Motor constant (factory set), range is 0 to 255
9
100
100
Specified by the capacity of each inverter model kW kW
100
Motor stabilization constant, 2nd motor
2AUXKCD
Ten selections: 0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.7/ 5.5/7.5
4p
Motor stabilization constant
AUX KCD H206
Defaults Run Mode -FE -FU Units Edit (EU) (USA)
4p
Motor poles setting, 2nd motor
2AUXP H006
Description
01
100
Parameters
Configuring Drive Parameters
“H” Function Func. Code H003
00
Page 149
Page 150
4−1
Operations and Monitoring In This Chapter…
4 page
-
Introduction...................................................................................... 2
-
Connecting to PLCs and Other Devices ........................................ 4
-
Control Logic Signal Specifications............................................... 6
-
Intelligent Terminal Listing ............................................................. 7
-
Using Intelligent Input Terminals.................................................... 8
-
Using Intelligent Output Terminals............................................... 36
-
Analog Input Operation ................................................................. 55
-
Analog Output Operation .............................................................. 57 PID Loop Operation ....................................................................... 58 Configuring the Inverter for Multiple Motors............................... 60
Operations and Monitoring
-