Page 151
4−2
Introduction The previous material in Chapter 3 gave a reference listing of all the programmable functions of the inverter. We suggest that you first scan through the listing of inverter functions to fain a general familiarity. This chapter will build on that knowledge in the following ways: 1. Related functions – Some parameters interact with or depend on the settings in other functions. This chapter lists “required settings” for a programmable function to serve as a cross-reference and an aid in showing how function interacts. 2. Intelligent terminals – Some functions rely on an input signal on a control logic connector terminal, or generate output signals in other cases. 3. Electrical interfaces – This chapter shows how to make connections between the inverter and other electrical devices. 4. PID Loop Operation – The X200 has a built-in PID loop that calculates the optimal inverter output frequency to control an external process. This chapter shows the parameters and input/output terminals associated with PID loop operation.
Monitoring
Operations and Monitoring Operations and
5. Multiple motors – A single X200 inverter may be used with two or more motors in some types of applications. This chapter shows the electrical connections and inverter parameters involved in multiple-motor applications. The topics in this chapter can help you decide the features that are important to your application, and how to use them. The basic installation covered in Chapter 2 concluded with the powerup test and running the motor. Now, this chapter starts from that point and shows how to make the inverter part of a larger control or automation system.
Caution Messages for Operating Procedures Before continuing, please read the following Caution messages. CAUTION: The heat sink fins will have a high temperature. Be careful not to touch them. Otherwise, there is the danger of getting burned. CAUTION: The operation of the inverter can be easily changed from low speed to high speed. Be sure to check the capability and limitations of the motor and machine before operating the inverter. Otherwise, it may cause injury to personnel. CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage.
Page 152
4−3
Warning Messages for Operating Procedures WARNING: Be sure to turn ON the input power supply only after closing the front case. While the inverter is energized, be sure not to open the front case. Otherwise, there is the danger of electric shock. WARNING: Be sure not to operate electrical equipment with wet hands. Otherwise, there is the danger of electric shock. WARNING: While the inverter is energized, be sure not to touch the inverter terminals even when the motor is stopped. Otherwise, there is the danger of electric shock. WARNING: If the retry mode is selected, the motor may suddenly restart after a trip stop. Be sure to stop the inverter before approaching the machine (be sure to design the machine so that safety for personnel is secure even if it restarts.) Otherwise, it may cause injury to personnel. WARNING: If the power supply is cut OFF for a short period of time, the inverter may restart operating after the power supply recovers if the Run command is active. If a restart may pose danger to personnel, so be sure to use a lock-out circuit so that it will not restart after power recovery. Otherwise, it may cause injury to personnel.
WARNING: During a trip event, if the alarm reset is applied and the Run command is present, the inverter will automatically restart. Be sure to apply the alarm reset only after verifying the Run command is OFF. Otherwise, it may cause injury to personnel. WARNING: Be sure not to touch the inside of the energized inverter or to put any conductive object into it. Otherwise, there is a danger of electric shock and/or fire. WARNING: If power is turned ON when the Run command is already active, the motor will automatically start and injury may result. Before turning ON the power, confirm that the RUN command is not present. WARNING: When the Stop key function is disabled, pressing the Stop key does not stop the inverter, nor will it reset a trip alarm. WARNING: Be sure to provide a separate, hard-wired emergency stop switch when the application warrants it.
OperationsOperations and and MonitoringMonitoring
WARNING: The Stop Key is effective only when the stop function is enabled. Be sure to enable the Stop Key separately from the emergency stop. Otherwise, it may cause injury to personnel.
Page 153
4−4
Connecting to PLCs and Other Devices Hitachi inverters (drives) are useful in many types of applications. During installation, the inverter keypad (or other programming device) will facilitate the initial configuration. After installation, the inverter will generally receive its control commands through the control logic connector or serial interface from another controlling device. In a simple application such as single-conveyor speed control, a Run/Stop switch and potentiometer will give the operator all the required control. In a sophisticated application, you may have a programmable logic controller (PLC) as the system controller, with several connections to the inverter. It is not possible to cover all the possible types of application in this manual. It will be necessary for you to know the electrical characteristics of the devices you want to connect to the inverter. Then, this section and the following sections on I/O terminal functions can help you quickly and safely connect those devices to the inverter.
Monitoring
Operations and Monitoring Operations and
CAUTION: It is possible to damage the inverter or other devices if your application exceeds the maximum current or voltage characteristics of a connection point. The connections between the inverter and other devices rely on the electrical input/output characteristics at both ends of each connection, shown in the diagram to the right. The inverter’s configurable inputs accept either a sourcing or sinking output from an external device (such as PLC). This chapter shows the inverter’s internal electrical component(s) at each I/O terminal. In some cases, you will need to insert a power source in the interface wiring. In order to avoid equipment damage and get your application running smoothly, we recommend drawing a schematic of each connection between the inverter and the other device. Include the internal components of each device in the schematic, so that it makes a complete circuit loop. After making the schematic, then:
Other device
X200 inverter
Input circuit signal return
Output circuit
Output circuit signal return
Input circuit
Other device
X200 inverter P24
+-
24V
1 2 3
Input circuits
4 5
GND 1. Verify that the current and voltage for L each connection is within the operating limits of each device. 2. Make sure that the logic sense (active high or active low) of any ON/OFF connection is correct. 3. Check the zero and span (curve end points) for analog connections, and be sure the scale factor from input to output is correct. 4. Understand what will happen at the system level if any particular device suddenly loses power, or powers up after other devices.
Page 154
4−5
Example Wiring Diagram The schematic diagram below provides a general example of logic connector wiring, in addition to basic power and motor wiring converted in Chapter 2. The goal of this chapter is to help you determine the proper connections for the various terminals shown below for your application needs. Breaker, MCCB or GFI
X200
R
Power source, 3-phase or 1phase, per inverter model
(L1)
U (T1)
S
V
(L2)
(T2)
T
W
N(L3)
(T3)
Motor
DC reactor (optional)
PD/+1 Intelligent inputs, 5 terminals
+-
24V
P/+
Forward 1 Braking unit (optional)
Reverse 2
N/-
Input circuits
3 4 AL1
5 Thermistor
[5] configurable as discrete input or thermistor input
Relay contacts, type 1 Form C
AL0 AL2
PCS
L GND for logic inputs Open collector output
Meter
Freq. arrival signal
Output circuit
11
Analog reference 0~10VDC 4~20mA
H O OI L
GND for analog signals
Load + -
AM CM2
GND for logic outputs
OperationsOperations and and MonitoringMonitoring
NOTE: For the wiring of intelligent I/O and analog inputs, be sure to use twisted pair / shielded cable. Attach the shielded wire for each signal to its respective common terminal at the inverter end only.
P24
Page 155
4−6
Control Logic Signal Specifications The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below. Relay contacts AL2 AL1 AL0 Analog output AM H
Analog inputs O OI L
Logic inputs 5
4
3
2
1
Logic output
L PCS P24 CM2 11
Monitoring
Operations and Monitoring Operations and
Short bar : default position (Source logic)
Terminal Name [P24] [PCS]
Description +24V for logic inputs Intelligent input common
[1], [2], [3], [4], [5]
Discrete logic inputs
[L] (right) *1 [11]
GND for logic inputs Discrete logic output
[CM2] [AM] [L] (left) *2 [OI]
GND for logic output Analog voltage output GND for analog signals Analog input, current
[O]
Analog input, voltage
[H] [AL0] [AL1] *3 [AL2] *3
+10V analog reference Relay common contact Relay contact, normally open Relay contact, normally closed
Note 1: Note 2: Note 3:
Ratings 24VDC, 30mA. (do not short to terminal L) Factory set: Source type for –FE and –HE models (connecting [P24] to [1]~[5] turns each input ON). To change to sink type, remove the short wire between [PCS] and [L], and connect it between [P24] and [L]. In this case, connecting [L] to [1]~[5] makes each input ON. 27VDC max. (use PCS or an external supply referenced to terminal L) Sum of input [1]~[5] currents (return) 50mA max. ON state current, 27 VDC max. OFF state voltage 100 mA: [11] current return 0~10VDC 1mA maximum Sum of [OI], [O], and [H] currents (return) 4 to 19.6 mA range, 20 mA nominal, input impedance 250 : 0 to 9.8 VDC range, 10 VDC nominal, input impedance 10 k: 10VDC nominal, 10mA max. 250VAC, 2.5A (R load) max. 250VAC, 0.2A (I load, P.F.=0.4) max. 100VAC, 10mA min. 30VDC, 3.0A (R load) max. 30VDC, 0.7A (I load, P.F.=0.4) max. 5VDC, 100mA min.
The two terminals [L] are electrically connected together inside the inverter. We recommend using [L] logic GND (to the right) for logic input circuits and [L] analog GND (to the left) for analog I/O circuits. Default relay N.O./N.C. configuration is reversed. See page 4-35.
Page 156
4−7
Intelligent Terminal Listing Intelligent Inputs Use the following table to locate pages for intelligent input material in this chapter. Code 00 01 02 03 04 05 06 07 08 09 11 12 13 15 16 18 19 20 21 22 23 24 27 28 29 31 50 51 52 53 64 255
Input Function Summary Table Function Name FORWARD Run/Stop Reverse Run/Stop Multi-speed Select, Bit 0 (LSB) Multi-speed Select, Bit 1 Multi-speed Select, Bit 2 Multi-speed Select, Bit 3 (MSB) Jogging External DC braking Set (select) 2nd Motor Data 2-stage Acceleration and Deceleration Free-run Stop External Trip Unattended Start Protection Software Lock Analog Input Voltage/Current Select Reset Inverter PTC thermistor Thermal Protection Start (3-wire interface) Stop (3-wire interface) FWD, REV (3-wire interface) PID Disable PID Reset Remote Control UP Function Remote Control Down Function Remote Control Data Clearing Operator Control ADD frequency enable Force Terminal Mode Inverter ready Special Set Emergency Stop No assign
Page 4-11 4-11 4-12 4-12 4-12 4-12 4-14 4-15 4-16 4-17 4-18 4-19 4-20 4-21 4-22 4-23 4-24 4-25 4-25 4-25 4-26 4-26 4-27 4-27 4-27 4-29 4-30 4-31 4-31 4-16 4-32 -
Intelligent Outputs Use the following table to locate pages for intelligent output material in this chapter. Symbol 00 01 02 03 04 05 06 07 08 09 10 43
Code RUN FA1 FA2 OL OD AL Dc FBV NDc LOG ODc LOC
Input Function Summary Table Function Name Run Signal Frequency Arrival Type 1–Constant Speed Frequency Arrival Type 2–Over frequency Overload Advance Notice Signal Output Deviation for PID Control Alarm Signal Analog Input Disconnect Detect PID Second Stage Output Network Detection Signal Logic Output Function Network error detection Low load detection signal
Page 4-39 4-40 4-40 4-42 4-43 4-44 4-46 4-47 4-50 4-52 4-53 4-54
OperationsOperations and and MonitoringMonitoring
Symbol FW RV CF1 CF2 CF3 CF4 JG DB SET 2CH FRS EXT USP SFT AT RS PTC STA STP F/R PID PIDC UP DWN UDC OPE ADD F-TM RDY SP-SET EMR NO
Page 157
4−8
Using Intelligent Input Terminals Terminals [1], [2], [3], [4], and [5] are identical, programmable inputs for general use. The input circuits can use the inverter’s internal (isolated) +24V field supply or an external power supply. This section describes input circuits operation and how to connect them properly to switches or transistor outputs on field devices.
Monitoring
Operations and Monitoring Operations and
The X200 inverter features selectable sinking or sourcing inputs. These terms refer to the connection to the external switching device–it either sinks current (from the input to GND) or sources current (from a power source) into the input. Note that the sink/source naming convention may be different in your particular country or industry. In any case, just follow the wiring diagrams in this section for your application. The inverter has a short bar (jumper) for configuring the choice of sinking or sourcing inputs. To access it, you must remove the front cover of the inverter housing. In the figure to the top right, the short bar is shown as attached to the logic terminal block (connector). For EU and US version (suffix –xFE, and –xFU), it is originally located as source type logic. If you need to change to the sink type connection, remove the short bar and connect it as shown in the figure at the bottom right.
Logic inputs 5
4
3
2
1
L PCS P24
Short bar Source logic connection
5
4
3
2
1
L PCS P24
Short bar Sink logic connection
CAUTION: Be sure to turn OFF power to the inverter before changing the short circuit bar position. Otherwise, damage to the inverter circuitry may occur. [PCS] Terminal Wiring – The [PCS] terminal (Programmable Logic Control terminal) is named to include various devices that can connect to the inverter’s logic inputs. In the figure to the right, note the [PCS] terminal and the short bar (jumper). Locating the short bar between [PCS] and [L] sets the input logic source type, which is the default setting for EU and US versions. In this case, you connect input terminal to [P24] to make it active. If instead you locate the short bar between [PCS] and [P24], the input logic will be sink type. In this case, you connect the input terminal to [L] to make it active.
Short bar for sink logic
X200 inverter
P24 PCS
Input common
24V + -
1 Input circuits
5
L
Logic GND
Short bar for source logic
The wiring diagram on the following pages show the four combinations of using sourcing or sinking inputs, and using the internal or an external DC supply.
Page 158
4−9
The two diagrams below input wiring circuits using the inverter’s internal +24V supply. Each diagram shows the connection for simple switches, or for a field device with transistor outputs. Note that in the lower diagram, it is necessary to connect terminal [L] only when using the field device with transistors. Be sure to use the correct connection of the short bar shown for each wiring diagram. Sinking Inputs, Internal Supply Short bar = [PCS] – [P24] position
Short bar
X200
P24 PCS
Field device GND
Logic GND
24V Input common
+ -
L
1
1 Input circuits
5
5 Input switches
OperationsOperations and and MonitoringMonitoring
Open collector outputs, NPN transistors
Sourcing Inputs, Internal Supply Short bar = [PCS] – [L] position Field device
Common to [P24]
Short bar
X200
P24 PCS
Logic GND 1
24V Input common
L 1 Input circuits
5 to PNP bias circuits PNP transistor sousing outputs
GND
5 Input switches
+ -
Page 159
4−10
The two diagrams below show input wiring circuits using an external supply. If using the “Sinking Inputs, External Supply” in below wiring diagram, be sure to remove the short bar, and use a diode (*) with the external supply. This will prevent a power supply contention in case the short bar is accidentally placed in the incorrect position. For the “Sourcing Inputs, External Supply”, please connect the short bar as drawn in the diagram below.
Sinking Inputs, External Supply Short bar = Removed
X200 P24
Field device
* + -
*
24V
PCS
24V Input common
+ -
24V GND
Logic GND
1
+ -
L 1 Input circuits
5
5
Monitoring
Operations and Monitoring Operations and
Input switches
Open collector outputs, NPN transistors
* Note: If the external power supply to GND is (optionally) connected to [L], then install the above diode.
Sourcing Inputs, External Supply Short bar = [PCS] – [L] Short bar PNP transistor sourcing outputs
X200 P24
24V
Field device
+ -
PCS
24V Input common
L 1
1 Input circuits
5 + -
5 Input switches
24V GND
+ -
Page 160
4−11
Forward Run/Stop and Reverse Run/Stop Commands: When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low). Option Code 00
Terminal Symbol FW
Function Name
State
Forward Run/Stop
01
RV
Reverse Run/Stop
ON OFF ON OFF
Valid for inputs: C001~C005 Required settings A002 = 01 Notes: x When the Forward Run and Reverse Run commands are active at the same time, the inverter enters the Stop Mode. x When a terminal associated with either [FW] or [RV] function is configured for normally closed, the motor starts rotation when that terminal is disconnected or otherwise has no input voltage.
Description Inverter is in Run Mode, motor runs forward Inverter is in Stop Mode, motor stops Inverter is in Run Mode, motor runs reverse Inverter is in Stop Mode, motor stops Example (default input configuration shown – see page 3-49) RV FW 5
4
3
2
1
L PCS P24
See I/O specs on page 4-6.
WARNING: If the power is turned ON and the Run command is already active, the motor starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active.
OperationsOperations and and MonitoringMonitoring
NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run key issues a Run FWD command or Run REV command. However, it has no effect on the [FW] and [RV] input terminal operation.