Page 161
4−12
Multi-Speed Select The inverter can store up to 16 different target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are accessible through programming five of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table to the right. These can be any of the six inputs, and in any order. You can use fewer inputs if you need eight or fewer speeds.
Multispeed Speed 0 Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Speed 8 Speed 9 Speed 10 Speed 11 Speed 12 Speed 13 Speed 14 Speed 15
NOTE: When choosing a subset of speeds to use, always start at the top of the table, and with the least-significant bit: CF1, CF2, etc. 3rd 7th 5th 2nd 1st 6th 4th 0th
[CF2]
Monitoring
Operations and Monitoring Operations and
[CF1]
[CF3] [FW]
Speed
Input Function CF4 CF3 CF2 CF1 0 0 0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0 1 0 0 1 1 0 1 0 1 0 1 1 1 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1
The example with eight speeds in the figure below shows how input switches configured for CF1–CF3 functions can change the motor speed in real time.
1 0 1 0 1 0 1 0
NOTE: Speed 0 is set by the A020 parameter value.
Option Code 02
Terminal Symbol CF1
03
CF2
04
CF3
05
CF4
Valid for inputs: Required settings
Function Name
State
Description
Multi-speed Select, Bit 0 (LSB) Multi-speed Select, Bit 1 Multi-speed Select, Bit 2 Multi-speed Select, Bit 3 (MSB) C001~C005 F001, A001=02, A020 to A035
ON OFF ON OFF ON OFF ON OFF
Binary encoded speed select, Bit 0, logical 1 Binary encoded speed select, Bit 0, logical 0 Binary encoded speed select, Bit 1, logical 1 Binary encoded speed select, Bit 1, logical 0 Binary encoded speed select, Bit 2, logical 1 Binary encoded speed select, Bit 2, logical 0 Binary encoded speed select, Bit 3, logical 1 Binary encoded speed select, Bit 3, logical 0 Example (some CF inputs require input configuration; some are default inputs - see page 3– 49):
Notes: x When programming the multi-speed settings, be sure to press the Store key each time and then set the next multi-speed setting. Note that when the key is not pressed, no data will be set. x When a multi-speed setting more than 50Hz (60Hz) is to be set, it is necessary to program the maximum frequency A004 high enough to allow that speed
CF4 CF3 CF2 CF1
5
4
3
2
See I/O specs on page 4–6.
1
L PCS P24
Page 162
4−13
While using the multi-speed capability, you can monitor the present frequency with monitor function D001 during each segment of a multi-speed operation. NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F001 or change the value of F001 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F001 during Run Mode, please monitor D001 instead of F001. There are two ways to program the speeds into the registers A020 to A035: 1. Standard keypad programming: a. Select each parameter A020 to A035. b. Press the FUNC key to view the parameter value. c. Use the
1 and d. Use the
STR key to save the data to memory.
2 keys to edit the value.
2. Programming using the CF switches. Set the speed by following these steps: a. Turn the Run command OFF (Stop Mode). b. Turn inputs ON to select desired Multi-speed. Display the value of F001 on the digital operator.
d. Press the
STR
1 and
2 keys.
key once to store the set frequency. When this occurs, F001 indicates the output frequency of Multi-speed n. e. Press the
FUNC key once to confirm that the indication is the same as the set frequency. can f. Repeat operations in 2. a) to 2. e) to set the frequency of other Multi-speeds. Itޓ be set also by parameters A020 to A035 in the first procedure 1. a) to 1. d).
OperationsOperations and and MonitoringMonitoring c. Set the desired output frequency by pressing the
Page 163
4−14
Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small increments for manual operation. The speed is limited to 10 Hz. The frequency for the jogging operation is set by parameter A038. Jogging does not use an acceleration ramp, so we recommend setting the jogging frequency A038 to 5 Hz or less to prevent tripping.
[JG] [FW], [RV]
1 0 1 0
Jog speed A038
When the terminal [JG] is turned ON and the Run command is issued, the inverter outputs the programmed jog frequency to the motor. To enable the Run key on the digital operator for jog input, set the value 01 (terminal mode) in A002 (Run command source).
A039 Jog decel type
• 00 Free-run stop (coasting) Monitoring
Operations and Monitoring Operations and
The type of deceleration used to end a motor jog operation is selectable by programming function A039. The options are:
• 01 Deceleration (normal level) and stop • 02 Use DC braking and stop Option Code 06
Terminal Symbol JG
Function Name Jogging
State
Description
ON
Inverter is in Run Mode, output to motor runs at jog parameter frequency Inverter is in Stop Mode Example (requires input configuration - see page 3–49):
OFF Valid for inputs: Required settings
C001~C005 A002=01, A038>B082, A038>0, A039
Notes: x No jogging operation is performed when the set value of jogging frequency A038 is smaller than the start frequency B082, or the value is 0Hz. x Be sure to stop the motor when switching the function [JG] ON or OFF.
JG
5
4
3
2
See I/O specs on page 4–6.
1
L PCS P24
Page 164
4−15
External Signal for DC Braking When the terminal [DB] is turned ON, the DC braking feature is enabled. Set the following parameters when the external DC braking terminal [DB] is to be used: x A053 – DC braking delay time setting. The range is 0.1 to 5.0 seconds. x A054 – DC braking force setting. The range is 0 to 100%. The scenarios to the right help show how DC braking works in various situations. 1. Scenario 1 – The [FW] or [RV] terminal is ON. When [DB] is ON, DC braking is applied. When [DB] is OFF again, the output frequency ramps to the prior level.
3. Scenario 3 – The Run command is applied from the operator keypad. When the [DB] terminal is ON, DC braking is applied after the delay time set by A053 expires. The motor is in a free-running (coasting) condition. When the [DB] terminal is OFF again, the inverter output remains OFF. Option Code 07
Terminal Symbol DB
Function Name External DC Braking
1 0 1 0
[DB] Output frequency t Scenario 2 Run command 1 from operator 0 1 [DB] 0 Output frequency t Scenario 3 Run command 1 from operator 0 1 [DB] 0 delay
Output frequency
A053 t
State
Description
ON OFF
Applies DC injection braking during deceleration Does not apply DC injection braking during deceleration Example (requires input configuration - see page 3–49):
Valid for inputs: C001~C005 Required settings A053, A054 Notes: x Do not use the [DB] input continuously or for a long time when the DC braking force setting A054 is high (depends on the motor application). x Do not use the [DB] feature for continuous or high duty cycle as a holding brake. The [DB] input is designed to improve stopping performance. Use a mechanical brake for holding a stop position.
DB
5
4
3
2
See I/O specs on page 4–6.
1
L PCS P24
OperationsOperations and and MonitoringMonitoring
2. Scenario 2 – The Run command is applied from the operator keypad. When the [DB] terminal is ON, DC braking is applied. When the [DB] terminal is OFF again, the inverter output remains OFF.
Scenario 1 [FW,RV]
Page 165
4−16
Set Second Motor, Special Set If you assign the [SET] function to an intelligent input terminal, you can select between two sets of motor parameters. The second parameters store an alternate set of motor characteristics. When the terminal [SET] is turned ON, the inverter will use the second set of parameters to generate the frequency output to the motor. When changing the state of the [SET] input terminal, the change will not take effect until the inverter is stopped. Special Set [SP-SET] is for changing the second motor parameters without stopping the motor. However the changeable parameters are limited.
Parameters F002/F202 F003/F203 A001/A201 A002/A202 A003/A203 A004/A204 A020/A220 A041/A241 A042/A242 A043/A243 A044/A244 A045/A245 A061/A261 A062/A262 A092/A292
Monitoring
Operations and Monitoring Operations and
When you turn ON the [SET] input, the inverter operates per the second set of parameters. When the terminal is turned OFF, the output function returns to the original settings (first set of motor parameters). Refer to “Configuring the Inverter for Multiple Motors” on page 4–58 for details.
Option Code 08
Terminal Symbol SET
53
SP-SET
SET 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9
SP-SET 9 9 9 9 9 9 9 9
Function Name
Parameters A093/A293 A094/A294 A095/A295 A096/A296 b012/b212 b013/b213 b021/b221 b022/b222 b023/b223 b028/b228 C001~C005/ C201~C205 C041/C241 H003/H203 H004/H204 H006/H206
SET 9 9 9 9 9 9 9 9 9 9
SP-SET 9 9 9 9 -
9
-
9 9 9 9
-
State
Description
Set (select) 2nd Motor data
ON
Set 2nd motor data Special SET
OFF causes the inverter to use the 2nd set of motor parameters for generating the frequency output to motor causes the inverter to use the 1st (main) set of motor parameters for generating the frequency output to motor Example (requires input configuration - see page 3–49):
Valid for inputs: C001~C005 Required settings (none) Notes: x If the terminal state is changed while the inverter is running, the inverter continues using the current set of parameters until the inverter is stopped.
SET / SP-SET
5
4
3
2
See I/O specs on page 4–6.
1
L PCS P24
Page 166
4−17
Two Stage Acceleration and Deceleration When terminal [2CH] is turned ON, the inverter changes the rate of acceleration and deceleration from the initial settings (F002 and F003) to use the second set of acceleration/ deceleration values. When the terminal is turned OFF, the inverter is returned to the original acceleration and deceleration time (F002 acceleration time 1, and F003 deceleration time 1). Use A092 (acceleration time 2) and A0093 (deceleration time 2) to set the second stage acceleration and deceleration times.
Target frequency second
Output frequency initial 1 0 1 0
[2CH] [FW,RV] t
In the graph shown above, the [2CH] becomes active during the initial acceleration. This causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092). Option Code 09
Terminal Symbol 2CH
State
Description
ON
Frequency output uses 2nd-stage acceleration and deceleration values Frequency output uses the initial acceleration 1 and deceleration 1 values Example (default input configuration shown - see page 3–49):
OFF Valid for inputs: C001~C005 Required settings A092, A093, A094=00 Notes: x Function A094 selects the method for second stage acceleration. It must be set = 00 to select the input terminal method in order for the [2CH] terminal assignment to operate.
2CH
5
4
3
2
- FU models
See I/O specs on page 4–6.
1
L PCS P24
OperationsOperations and and MonitoringMonitoring
Function Name Two-stage Acceleration and Deceleration
Page 167
4−18
Free-run Stop When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending power to the motor if the Run command is still active. The free-run stop feature works with other parameters to provide flexibility in stopping and starting motor rotation. In the figure below, parameter B088 selects whether the inverter resumes operation from 0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS] terminal turns OFF. The application determines the best setting. Parameter B003 specifies a delay time before resuming operation from a free-run stop. To disable this feature, use a zero delay time. B088 = 00
B088 = 01 Resume from motor speed
Zero frequency start Motor speed
[FW,RV] Monitoring
Operations and Monitoring Operations and
[FRS]
Wait time
B003 Motor speed
1 0 1 0
[FRS] [FW,RV]
1 0 1 0 t Option Code 11
Terminal Symbol FRS
Function Name Free-run Stop t
State
Description
ON
Causes output to turn OFF, allowing motor to free run (coast) to stop Output operates normally, so controlled deceleration and stops motor Example (requires input configuration - see page 3–49):
OFF Valid for inputs: C001~C005 Required settings B003, B088, C011 to C015 Notes: x When you want the [FRS] terminal to be active low (normally closed logic), change the setting (C011 to C015) that corresponds to the input (C001 to C005) that is assigned the [FRS] function.
FRS
5
4
3
See I/O specs on page 4–6.
2
1
L PCS P24
Page 168
4−19
External Trip When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of the error depends on what you connect to the [EXT] terminal. Even if the [EXT] input is turned OFF, the inverter remains in the trip state. You must reset the inverter or cycle power to clear the error, returning the inverter to the Stop Mode. In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter lets the motor free-run to a stop, and the alarm output turns ON immediately. When the operator initiates a Reset command, the alarm and error are cleared. When the Reset is turned OFF, the motor begins rotation since the Run command is already active. [EXT] terminal
1 0 Free run
Motor revolution speed [RS] terminal Alarm output terminal
Option Code 12
Terminal Symbol EXT
Function Name External Trip t
State ON OFF
Valid for inputs: C001~C005 Required settings (none) Notes: x If the USP (Unattended Start Protection) feature is in use, the inverter will not automatically restart after canceling the EXT trip event. In that case, it must receive either another Run command (OFF-to- ON transition), a keypad Reset command, or an [RS] intelligent terminal input signal.
Description When assigned input transitions OFF to ON, inverter latches trip event and displays E12. No trip event for ON to OFF, any recorded trip events remain in history until Reset. Example (requires input configuration - see page 3–49): EXT
5
4
3
See I/O specs on page 4–6.
2
1
L PCS P24
OperationsOperations and and MonitoringMonitoring
Run command [FW,RV]
1 0 1 0 1 0
Page 169
4−20
Unattended Start Protection If the Run command is already set when power is turned ON, the inverter starts running immediately after powerup. The Unattended Start Protection (USP) function prevents that automatic startup, so that the inverter will not run without outside intervention. When USP is active and you need to reset an alarm and resume running, either turn the Run command OFF, or perform a reset operation by the terminal [RS] input or the keypad Stop/reset key. In the figure below, the [USP] feature is enabled. When the inverter power turns ON, the motor does not start, even though the Run command is already active. Instead, it enters the USP trip state, and displays E13 error code. This requires outside intervention to reset the alarm by turning OFF the Run command per this example (or applying a reset). Then the Run command can turn ON again and start the inverter output. Run command [FW,RV] 1 0 [USP] terminal 1 0 Alarm output terminal 1 0
0 Inverter power supply 1 0
Monitoring
Operations and Monitoring Operations and
Inverter output frequency
Events:
Option Code 13
Terminal Symbol USP
E13
Alarm cleared t
Run command
Function Name
State
Description
Unattended Start Protection
ON
On powerup, the inverter will not resume a Run command (mostly used in the US) On powerup, the inverter will resume a Run command that was active before power loss Example (default input configuration shown for –FU models; –FE and –FR models require input configuration - see page 3–49):
OFF Valid for inputs: C001~C005 Required settings (none) Notes: x Note that when a USP error occurs and it is canceled by a reset from a [RS] terminal input, the inverter restarts running immediately. x Even when the trip state is canceled by turning the terminal [RS] ON and OFF after an under voltage protection E09 occurs, the USP function will be performed. x When the running command is active immediately after the power is turned ON, a USP error will occur. When this function is used, wait for at least three (3) seconds after the powerup to generate a Run command.
USP
5
4
3
See I/O specs on page 4–6.
2
1
L PCS P24
Page 170
4−21
Software Lock When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequency, depending on the setting of B031) is locked (prohibited from editing). When the data is locked, the keypad keys cannot edit inverter parameters. To edit parameters again, turn OFF the [SFT] terminal input. Use parameter B031 to select whether the output frequency is excluded from the lock state or is locked as well. Option Code 15
Terminal Symbol SFT
Function Name Software Lock
State
Description
ON
The keypad and remote programming devices are prevented from changing parameters The parameters may be edited and stored Example (requires input configuration - see page 3–49):
OFF Valid for inputs: C001~C005 Required settings B031 (excluded from lock) Notes: x When the [SFT] terminal is turned ON, only the output frequency can be changed. x Software lock can include the output frequency by setting B031. x Software lock by the operator is also possible without the [SFT] terminal being used (B031).
SFT
5
4
3
2
L PCS P24
OperationsOperations and and MonitoringMonitoring
See I/O specs on page 4–6.
1