The text of a manual · part 18 of 31

X200 Series Inverter Instruction Manual, pages 171 to 180

Pages 171 to 180 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 171

4−22

Analog Input Current/Voltage Select The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input terminals for external frequency control. When intelligent input [AT] is ON, you can set the output frequency by applying a current input signal at [OI]-[L]. When the [AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output frequency. Note that you must also set parameter A001 = 01 to enable the analog terminal set for controlling the inverter frequency. Option Code 16

Terminal Symbol AT

Function Name Analog Input Voltage/Current Select C001~C005 A001 = 01

State ON OFF

Valid for inputs: Required settings Notes: x If the [AT] option is not assigned to any intelligent input terminal, then inverter recognizes [AT] = OFF in following table.

Description See the table down below

Example (default input configuration shown for –FU models; –FE models require input configuration - see page 3–49): AT

5

4

3

2

1

L PCS P24

Combination of A005 setting and [AT] input for analog input activation.

02

Monitoring

Operations and Monitoring Operations and

A005

03 04 05

[AT] Input ON OFF ON OFF (ignored) (ignored)

Analog Input Configuration Keypad Pot [O] Keypad Pot [OI] [O] [OI]

AM H

O OI L Å +- x Be sure to set the frequency source setting A001=01 to select the analog input terminals.

4-20 mA 0-10 V

See I/O specs on page 4–6.

NOTE: You cannot use both the [O] and [OI] inputs at the same time on the X200 inverter.

Page 172

4−23

Reset Inverter The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation. The minimum pulse width for [RS] must be 12 ms or greater. The alarm output will be cleared within 30 ms after the onset of the Reset command.

12 ms minimum

1 [RS] 0

Approx. 30 ms Alarm 1 signal 0 t

WARNING: After the Reset command is given and the alarm reset occurs, the motor will restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel. Option Code 18

Terminal Symbol RS

Function Name Reset Inverter

State

Description

ON

The motor output is turned OFF, the Trip Mode is cleared (if it exists), and powerup reset is applied Normal power ON operation Example (default input configuration shown - see page 3–49):

OFF Valid for inputs: Required settings Notes:

C001~C005 (none)

x Pressing the Stop/Reset key of the digital operator can generate a reset operation only when an alarm occurs.

5

4

3

2

1

L PCS P24

- FE models

See I/O specs on page 4–6.

x A terminal configured with the [RS] function can only be configured for normally open operation. The terminal cannot be used in the normally closed contact state. x When input power is turned ON, the inverter performs the same reset operation as it does when a pulse on the [RS] terminal occurs. x The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a hand-held remote operator is connected to the inverter. x If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting). x If you are using the output terminal OFF delay feature (any of C145, C147, C149 > 0.0 sec.), the [RS] terminal affects the ON-to-OFF transition slightly. Normally (without using OFF delays), the [RS] input causes the motor output and the logic outputs to turn OFF together, immediately. However, when any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an additional 1 sec. period (approximate) before turning OFF.

OperationsOperations and and MonitoringMonitoring x While the control terminal [RS] input is ON, the keypad displays alternating segments. The SRW optional remote keypad displays “HELLO!!”. After RS turns OFF, the display recovers automatically.

RS

Page 173

4−24

Thermistor Thermal Protection Motors that are equipped with a thermistor can be protected from overheating. Input terminal [5] has the unique ability to sense a thermistor resistance. When the resistance value of the thermistor connected to terminal [TH] (5) and [L] is more than 3 k Ÿ ±10%, the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the trip status E35. Use this function to protect the motor from overheating. Option Code 19

Terminal Symbol TH

Function Name

State

Description

Thermistor Thermal Protection

ON

When a thermistor is connected to terminals [5] and [L], the inverter checks for over-temperature and will cause trip (E35) and turn OFF the output to the motor An open circuit in the thermistor causes a trip, and the inverter turns OFF the output Example (requires input configuration - see page 3–49):

Valid for inputs: C005 only Required settings (none) Notes: x Be sure the thermistor is connected to terminals [5] and [L]. If the resistance is above the threshold the inverter will trip. When the motor cools down enough, the thermistor resistance will change enough to permit you to clear the error. Press the STOP/Reset key to clear the error. Monitoring

Operations and Monitoring Operations and

OFF

TH

5

4

3

2

1

Motor thermistor

NOTE: The trip level is hardware wise fixed and cannot be changed.

L PCS P24

Page 174

4−25

Three-wire Interface Operation The 3-wire interface is an industry standard motor control interface. This function uses two inputs for momentary contact start/stop control, and a third for selecting forward or reverse direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] (Stop), and 22 [F/R] (Forward/Reverse) to three of the intelligent input terminals. Use a momentary contact for Start and Stop. Use a selector switch, such as SPST for the Forward/Reverse input. Be sure to set the operation command selection A002=01 for input terminal control of motor. If you have a motor control interface that needs logic-level control (rather than momentary pulse control), use the [FW] and [RV] inputs instead. Terminal Symbol STA

State

Description

Start Motor

ON

21

STP

Stop Motor

OFF ON OFF

22

F/R

Forward/Reverse

Start motor rotation on momentary contact (uses acceleration profile) No change to motor operation No change to motor operation Stop motor rotation on momentary contact (use deceleration profile) Select reverse direction of rotation Select forward direction of rotation Example (default input configuration shown - see page 3–49): STP

Function Name

ON OFF

Valid for inputs: C001~C005 Required settings A002 = 01 Notes: x The STP logic is inverted. Normally the switch will be closed, so you open the switch to stop. In this way, a broken wire causes the motor to stop automatically (safe design). x When you configure the inverter for 3-wire interface control, the dedicated [FW] terminal is automatically disabled. The [RV] intelligent terminal assignment is also disabled.

F/R

5

STA

4

3

2

1

L PCS P24

See I/O specs on page 4–6.

The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensitive input; an OFF-to-ON transition gives the Start command. The control of direction is levelsensitive, and the direction may be changed at any time. STP (Stop Motor) is also a levelsensitive input. 1 0 1 [STP] terminal 0 [F/R] terminal 1 0 [STA] terminal

Motor revolution speed t

OperationsOperations and and MonitoringMonitoring

Option Code 20

Page 175

4−26

PID ON/OFF and PID Clear The PID loop function is useful for controlling motor speed to achieve constant flow, pressure, temperature, etc. in many process applications. The PID Disable function temporarily suspends PID loop execution via an intelligent input terminal. It overrides the parameter A071 (PID Enable) to stop PID execution and return to normal motor frequency output characteristics. The use of PID Disable on an intelligent input terminal is optional. Of course, any use of the PID loop control requires setting PID Enable function A071=01. The PID Clear function forces the PID loop integrator sum = 0. So, when you turn ON an intelligent input configured as [PIDC], the integrator sum is reset to zero. This is useful when switching from manual control to PID loop control and the motor is stopped.

Monitoring

Operations and Monitoring Operations and

CAUTION: Be careful not to turn PID Clear ON and reset the integrator sum when the inverter is in Run Mode (output to motor is ON). Otherwise, this could cause the motor to decelerate rapidly, resulting in a trip. Option Code 23

Terminal Symbol PID

PID Disable

24

PIDC

PID Clear

Function Name

State ON OFF ON OFF

Valid for inputs: C001~C005 Required settings A071 Notes: x The use of [PID] and [PIDC] terminals are optional. Use A071=01 if you want PID loop control enabled all the time. x Do not enable/disable PID control while the motor is running (inverter is in Run Mode). x Do not turn ON the [PIDC] input while the motor is running (inverter is in Run Mode).

Description Disables PID loop execution Allows PID loop execution Force the value of the integrator to zero No change in PID loop execution Example (default input configuration shown - see page 3–49): PIDC PID

5

4

3

2

See I/O specs on page 4–6.

1

L PCS P24

Page 176

4−27

Remote Control Up and Down Functions The [UP] [DWN] terminal functions can adjust the output frequency for remote control while the motor is running. The acceleration time and deceleration time of this function is same as normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate according to these principles: x Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from the current value. When it is turned OFF, the output frequency maintains its current value at that moment. x Deceleration - When the [DWN] contact is turned ON, the output frequency decelerates from the current value. When it is turned OFF, the output frequency maintains its current value at that moment. In the graph below, the [UP] and [DWN] terminals activate while the Run command remains ON. The output frequency responds to the [UP] and [DWN] commands.

Motor speed

[UP]

[FW,RV] t

OperationsOperations and and MonitoringMonitoring

[DWN]

1 0 1 0 1 0

Page 177

4−28

It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the memory and return to the original set output frequency. Option Code 27

Terminal Symbol UP

28

DWN

29

UDC

Valid for inputs: Required settings

Function Name

State

Description

Remote Control UP Function (motorized speed pot.) Remote Control DOWN Function (motorized speed pot.) Remote Control Data Clear C001~C005 A001 = 02

ON

Accelerates (increases output frequency) motor from current frequency Output to motor operates normally Decelerates (increases output frequency) motor from current frequency Output to motor operates normally Clears the Up/Down frequency memory No effect on Up/Down memory Example (default input configuration shown - see page 3–49):

OFF ON OFF ON OFF

DWN UP

Notes:

5 x This feature is available only when the frequency command source is programmed for operator control. Confirm A001 is set to 02.

4

3

2

1

L PCS P24 x This function is not available when [JG] is in use. x The range of output frequency is 0 Hz to the value in A004 (maximum frequency setting).

See I/O specs on page 4–6.

x The minimum ON time of [UP] and [DWN] is 50 ms.

Operations and Monitoring x This setting modifies the inverter speed from using F001 output frequency setting as a starting point.

Page 178

4−29

Force Operation from Digital Operator This function permits a digital operator interface to override the following two settings in the inverter: x

A001 - Frequency source setting x

A002 - Run command source setting

When using the [OPE] terminal input, typically A001 and A002 are configured for sources other than the digital operator interface for the output frequency and Run command sources, respectively. When the [OPE] input is ON, then user has immediate command of the inverter, to start or stop the motor and to set the speed.

Option Code 31

Terminal Symbol OPE

Function Name

Description

ON

Forces the operator interface to override: A001 - Frequency Source Setting, and A002 - Run Command Source Setting Parameters A001 and A002 are in effect again, for the frequency source and the Run command source, respectively Example (default input configuration shown - see page 3–49):

OFF

Valid for inputs: Required settings

C001~C005 A001 (set not equal to 00) A002 (set not equal to 02)

OPE

Notes: x When changing the [OPE] state during Run Mode (inverter is driving the motor), the inverter will stop the motor before the new [OPE] state takes effect. x If the [OPE] input turns ON and the digital operator gives a Run command while the inverter is already running, the inverter stops the motor. Then the digital operator can control the motor.

5

4

3

2

See I/O specs on page 4–6.

1

L PCS P24

OperationsOperations and and MonitoringMonitoring

State

Force Operation from Digital Operator

Page 179

4−30

Add Frequency Enable The inverter can add or subtract an offset value to the output frequency setting which is specified by A001 (will work with any of the five possible sources). The ADD Frequency is a value you can store in parameter A145. The ADD Frequency is summed with or subtracted from the output frequency setting only when the [ADD] terminal is ON. Function A146 selects whether to add or subtract. By configuring an intelligent input as the [ADD] terminal, your application can selectively apply the fixed value in A145 to offset (positively or negatively) the inverter output frequency in real time.

Keypad potentiometer

A001

Frequency source setting

Control terminal +

Output frequency setting

Ȉ

Function F001 setting ModBus network input

+/-

Calculate function output A146 A145 ADD frequency

ADD direction select [ADD]

Monitoring

Operations and Monitoring Operations and

Intelligent input

Option Code 50

Terminal Symbol ADD

Function Name ADD Frequency Enable

State ON OFF

Valid for inputs: C001~C005 Required settings A001, A145, A146 Notes: x A001 may specify any source; the Add Frequency will be added to or subtracted from that value to yield output frequency value.

Description Applies the A145 Add Frequency value to the output frequency Does not apply the Add frequency. The output frequency retains its normal value Example (default input configuration shown - see page 3–49): ADD

5

4

3

2

See I/O specs on page 4–6.

1

L PCS P24

Page 180

4−31

Force Terminal Mode The purpose of this intelligent input is to allow a device to force the inverter to allow control of the following two parameters via the control terminals: • A001 - Frequency source setting (01 = control terminals [FW] and [RV] • A002 - Run command source setting (01 = control terminals [O] or [OI] Some applications will require one or both settings above to use a source other than the terminals. You may prefer to normally use the inverter’s keypad and potentiometer, or to use the ModBus network for control, for example. However, an external device can turn ON the [F-TM] input to force the inverter to (temporarily) allow control (frequency source and Run command) via control terminals. When the [F-TM] input is OFF, then the inverter uses the regular sources specified by A001 and A002 again. Option Code 51

Terminal Symbol F-TM

Function Name Force Terminal Mode

State ON

OFF Valid for inputs: Required settings

C001~C005 A001, A002

Notes:

Description Forces A001=01 (frequency source setting = control terminal), and A002=01(Run command source setting = control terminal) Inverter applies the user setting for A001 and A002 normally Example (default input configuration shown - see page 3–49): F-TM 5

4

3

2

1

L PCS P24

See I/O specs on page 4–6.

Inverter Ready The purpose of this intelligent input is to make the inverter ready to start the motor immediately when the RUN command is given. When the RDY input is active, motor output terminal is active even if there is no RUN command. Option Code 52

Terminal Symbol RDY

Function Name Inverter Ready

State ON OFF

Valid for inputs: Required settings Notes:

C001~C005 A001, A002

Description Inverter is ready to act immediately when the RUN command is given. Inverter performs normal start when the RUN command is given. Example (default input configuration shown - see page 3–49): RDY 5

4

3

2

1

L PCS P24

See I/O specs on page 4–6.

HIGH VOLTAGE: When RDY function is set ON, there will be a voltage at motor output terminals U, V and W even if the motor is in stop mode. Never touch the inverter power terminals while the inverter is powered up.

OperationsOperations and and MonitoringMonitoring x When changing the [F-TM] state during Run Mode (inverter is driving the motor), the inverter will stop the motor before the new [FTM] state takes effect.