Page 181

4−32

Emergency Stop -

The emergency stop function shuts off the inverter output (i.e. stops the switching operation of the main circuit elements) in response to a command from a hardware circuit via an intelligent input terminal without the operation by internal CPU software.

Note: The emergency stop function does not electrically shut off the inverter but merely stops the switching operation of the main circuit elements. Therefore, do not touch any terminals of the inverter or any power lines, e.g., motor cables. Otherwise, electric shock, injury, or ground fault may result. -

When the emergency stop function is enabled, intelligent input terminals 1 and 3 are used exclusively for this function, and no other functions can be assigned to these terminals. Even if other functions have been assigned to these terminals, these are automatically disabled and these terminals are used exclusively for the emergency stop function.

Monitoring

Operations and Monitoring Operations and

Terminal [4] function: This terminal always serves as the a (NO) contact for the reset (RS) signal. This signal resets the inverter and releases the inverter from the trip due to emergency stop (E37.*). Terminal [3] function: This terminal always serves as the b (NC) contact for the emergency stop (EMR) signal. This signal shuts off the inverter output without the operation by internal CPU software. This signal makes the inverter trip due to emergency stop (E37.*). Note: If intelligent input terminal 3 is left unconnected, the cable connected to the terminal is disconnected, or the signal logic is improper, the inverter trips due to emergency stop (E37.*). If this occurs, check and correct the wiring and signal logic, and then input the reset (RS) signal. Only the reset (RS) signal input from intelligent input terminal [4] can release the inverter from tripping due to emergency stop (E37.*). (The inverter cannot be released from the E37.* status by any operation from the digital operator.)

Page 182

4−33

How to go into Emergency Stop mode The Emergency Stop function of X200 is activated by turning ON the hardware switch (S8) located on the control card. Be sure to power OFF the inverter when changing the switch S8.

SW7 485 SW8 ON OPE OFF Default = OFF

Terminal Number

Default setting Emergency Stop switch S8 = OFF

1

FW

2

RV

3

CF1

4

CF2 [US ver. :USP]

5

RS (PTC assignable)

Emergency Stop switch condition Emergency Stop switch Emergency Stop switch S8 = ON S8 = ON Æ OFF FW

FW

RV

RV

EMR [HW based for 1b input] RS [HW based for 1a input] - (No function)

- (No function) RS [Normal 1a] - (No function)

This means that terminal 5 will be changed to “no function” when S8 is set to ON. If you want to use terminal 5 with a specific function when switch S8 is turned ON, you need to assign it manually. Additionally, terminal 3 will also change to “no function” when the switch S8 is set to OFF again. Please do not change the setting of switch S8 during operation. Otherwise there might be unexpected system behavior.

Operations and Monitoring

When the switch S8 is set to ON, input terminal for the emergency signal and the terminal for the reset signal will be assigned automatically to terminal 3 and 4. Parameter C003 is changed to EMR and parameter C004 is changed to RS automatically, and cannot be changed manually. The following table shows the assignments of each terminal according to the switch S8 condition.

Operations and Monitoring

HIGH VOLTAGE: Dangerous voltage exists even after the Emergency Stop is activated. It does NOT mean that the main power has been removed.

Page 183

4−34

Option Code 64

Terminal Symbol EMR

Valid for inputs: Required settings Notes:

Function Name Emergency Stop C003, C004

State ON OFF

Description Emergency signal is activated Emergency signal is not activated Example (default input configuration shown - see page 3–49): RS EMR

5

4

3

2

Monitoring

Operations and Monitoring Operations and

See I/O specs on page 4–6.

1

L PCS P24

Page 184

4−35

Operations and Monitoring

Operations and Monitoring

… this page is left intentionally blank.

Page 185

4−36

Using Intelligent Output Terminals The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The inverter has several output functions that you can assign individually to two physical logic outputs. One of the outputs is an open-collector transistor, and the other output is the alarm relay (form C – normally open and normally closed contacts). The relay is assigned the alarm function by default, but you can assign it to any of the functions that the open-collector output uses.

Sinking Outputs, Open Collector X200 Inverter Logic output common

CM2

11

+

Load Monitoring

Operations and Monitoring Operations and

The open-collector transistor output can handle up to 50mA. We highly recommend that you use an external power source as shown at the right. It must be capable of providing at least 50mA to drive the output at full load. To drive loads that require more than 50mA, use external relay circuits as shown below right.

Sinking Outputs, Open Collector X200 Inverter

If you need output current greater than 50mA, use the inverter output to drive a small relay. Be sure to use a diode across the coil of the relay as shown (reversebiased) in order to suppress the turn-off spike, or use a solid-state relay.

Logic output common

CM2

11

+ RY

Page 186

4−37

Internal Relay Output The inverter has an internal relay output with normally open and normally closed contacts (Type 1 form C). The output signal that controls the relay is configurable; the Alarm Signal is the default setting. Thus, the terminals are labeled [AL0], [AL1], [AL2], as shown to the right. However, you can assign any one of the nine intelligent outputs to the relay. For wiring purposes, the general terminal functions are:

Inverter logic circuit board

AL0

AL1

AL2 x [AL0] – Common contact x [AL1] – Normally open contact x [AL2] – Normally closed contact The relay itself can be configured as “normally open or closed.” Parameter C036, Alarm Relay Active State, is the setting. This setting determines whether or not the relay coil is energized when its output signal is OFF: x C036=00 – “Normally open” (relay coil is de-energized when output signal is OFF) x C036=01 – “Normally closed” (relay coil is energized when the output signal is OFF)

Inverter logic circuit board determine whether or not an inverter power loss causes the relay to change state. The

C036=01 default relay configuration is the Alarm Signal (C026=05), as shown to the right. And, C036=01 sets the relay to “normally closed” (relay coil normally energized). The reason for this is that a typical system design will require an inverter power loss to assert an alarm signal to external devices. The relay can be used for other intelligent output signals, such as the Run Signal (set C026=00). For these remaining output signal types, the relay coil typically must NOT change state upon inverter power loss (set C036=00). The figure to the right shows the relay settings for the Run Signal output. If you assign the relay an output signal other than the Alarm Signal, the inverter can still have an Alarm Signal output. In this case, you can assign it to terminal [11] , providing an open collector output.

AL

C026=05 AL0

AL1

AL2

Relay shown with inverter power ON, Alarm Signal OFF

Inverter logic circuit board

RUN

C026=00 C036=00 AL0

AL1

AL2

Relay shown with inverter power ON, Run Signal OFF

OperationsOperations and and MonitoringMonitoring

Since the relay already has normally open [AL1] and normally closed [AL2] contacts, the purpose of the ability to invert the relay coil’s active state may not be obvious. It allows you to

Page 187

4−38

Output Signal ON/OFF Delay Function Intelligent outputs including terminals [11], and the output relay, have configurable signal transition delays. Each output can delay either the OFF-to-ON or ON-to-OFF transitions, or both. Signal transition delays are variable from 0.1 to 100.0 seconds. This feature is useful in applications that must tailor inverter output signals to meet timing requirements of certain external devices. The timing diagram below shows a sample output signal (top line) and the results of various ON/OFF delay configurations. x Original signal - This example signal waveform consists of three separate pulses named “A,” “B,” and “C.” x ...with ON delay - Pulse A is delayed by the duration of the ON delay time. Pulses B and C do not appear at the output, because they are shorter than the ON delay. x ...with OFF delay - Pulse A is lengthened by the amount of the OFF delay time. The separation between pulses B and C does not appear at the output, because it is shorter than the OFF delay time.

Monitoring

Operations and Monitoring Operations and x ...with ON/OFF delays - Pulse A is delayed on both leading and trailing edges by the amounts of the ON and OFF delay times, respectively. Pulses B and C do not appear at the output, because they are shorter than the ON delay time. ON delay

Output Signals: Original (no delays) …with ON delay …with OFF delay …with ON/OFF delays

1 0 1 0 1 0 1 0

OFF delay

A

ON delays

B

C OFF delays t

Func. C144 C145 C148 C149

Description Terminal [11] ON delay Terminal [11] OFF delay Output relay ON delay Output relay OFF delay

Range 0.0 to 100.0 sec. 0.0 to 100.0 sec. 0.0 to 100.0 sec. 0.0 to 100.0 sec.

Default 0.0 0.0 0.0 0.0

Use of the ON/OFF signal delay functions are optional. Note that any of the intelligent output assignments in this section can be combined with ON/OFF signal timing delay configurations.

Page 188

4−39

Run Signal When the [RUN] signal is selected as an intelligent output terminal, the inverter outputs a signal on that terminal when it is in Run Mode. The output logic is active low, and is the open collector type (switch to ground).

[FW,RV]

Terminal Symbol RUN

Valid for inputs: Required settings

Function Name Run Signal

State ON OFF

11, AL0 – AL2 (none)

Notes:

start freq.

1 0

ON t

Description when inverter is in Run Mode when inverter is in Stop Mode Example for terminal [11] (default output configuration shown – see page 3-54): Inverter output terminal circuit

RUN

CM2

11 x The example circuit for terminal [11] drives a relay coil. Note the use of a diode to prevent the negative going turn-off spike generated by the coil from damaging the inverter’s output transistor.

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): RUN

Inverter logic circuit board

AL0

AL1

Power supply See I/O specs on page 4-6

AL2 Load

OperationsOperations and and MonitoringMonitoring x The inverter outputs the [RUN] signal whenever the inverter output exceeds the start frequency specified by parameter B082. The start frequency is the initial inverter output frequency when it turns ON.

B082

Output frequency Run signal

Option Code 00

1 0

Page 189

4−40

Frequency Arrival Signals The Frequency Arrival group of outputs helps coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility. For example, you can have an output turn ON at one frequency during acceleration, and have it turn OFF at a different frequency during deceleration. All transitions have hysteresis to avoid output chatter if the output frequency is near one of the thresholds. Option Code 01

Terminal Symbol FA1

02

FA2

Function Name

State

Description

Frequency Arrival Type 1 – Constant Speed Frequency Arrival Type 2 – Over frequency

ON OFF when output to motor is at the set frequency when output to motor is OFF, or in any acceleration or deceleration ramp when output to motor is at or above the set frequency thresholds for, even if in acceleration or deceleration ramps when output to motor is OFF, or during acceleration or deceleration before the respective thresholds are crossed Example for terminal [11] (default output configuration shown – see page 3-54):

ON

OFF

Monitoring

Operations and Monitoring Operations and

Valid for inputs: Required settings

11, AL0 – AL2 (none)

Notes: x For most applications you will need to use only one type of frequency arrival outputs (see examples). However, it is possible assign both output terminals to output functions [FA1] and [FA2].

Inverter output terminal circuit

FA1

CM2

11 x For each frequency arrival threshold, the output anticipates the threshold (turns ON early) by 1.5Hz. x The output turns OFF as the output frequency moves away from the threshold, delayed by 0.5Hz. x The delay time of the output signal is 60 ms (nominal). x The example circuit for terminal [11] drives a relay coil. Note the use of a diode to prevent the negative going turn-off spike generated by the coil from damaging the inverter’s output transistor.

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 54): FA1

Inverter logic circuit board

AL0

AL1

Power supply See I/O specs on page 4-6

AL2 Load

Page 190

4−41

Frequency arrival output [FA1] uses the standard output frequency (parameter F001) as the threshold for switching. In the figure to the right, Frequency Arrival [FA1] turns ON when the output frequency gets within Fon Hz below or Fon Hz above the target constant frequency, where Fon is 1% of the set maximum frequency and Foff is 2% of the set maximum frequency. This provides hysteresis that prevents output chatter near the threshold value. The hysteresis effect causes the output to turn ON slightly early as the speed approaches the threshold. Then the turn-OFF point is slightly delayed. The timing is further modified by a small 60 ms delay. Note the active low nature of the signal, due to the open collector output.

Foff

F001

Fon

F001 Foff Fon

0 FA1 signal

ON

ON

60ms

60ms

Fon=1% of max. frequency Foff=2% of max. frequency

Output freq. thresholds C042 accel.

Fon Foff

C043 decel. 0 FA2 signal

ON 60ms

Fon=1% of max. frequency Foff=2% of max. frequency

60ms

OperationsOperations and and MonitoringMonitoring

Frequency arrival output [FA2] works the same way; it just uses two separate thresholds as shown in the figure to the right. These provide for separate acceleration and deceleration thresholds to provide more flexibility than for [FA1]. [FA2] uses C042 during acceleration for the ON threshold, and C043 during deceleration for the OFF threshold. This signal also is active low and has a 60 ms delay after the frequency thresholds are crossed. Having different accel and decel thresholds provides an asymmetrical output function. However, you can use equal ON and OFF thresholds, if desired.

Output freq.