The text of a manual · part 20 of 31

X200 Series Inverter Instruction Manual, pages 191 to 200

Pages 191 to 200 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 191

4−42

Overload Advance Notice Signal When the output current exceeds a preset Output value, the [OL] terminal signal turns ON. current The parameter C041 sets the overload C041 threshold. The overload detection circuit operates during powered motor operation C041 and during regenerative braking. The output circuits use open-collector transistors, and are active low. [OL] 1 signal 0

Threshold Power running Regeneration Threshold

ON

ON t Option Code 03

Terminal Symbol OL

Function Name

State

Description

Overload Advance Notice Signal

ON when output current is more than the set threshold for the overload signal when output current is less than the set threshold for the overload signal Example for terminal [11] (default output configuration shown – see page 3-35):

OFF Valid for inputs: Required settings

11, AL0 – AL2 C041

Monitoring

Operations and Monitoring Operations and

Notes: x The default value is 100%. To change the level from the default, set C041 (overload level). x The accuracy of this function is the same as the function of the output current monitor on the [FM] terminal (see “Analog Output Operation” on page 4–55). x The example circuit for terminal [11] drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

Inverter output terminal circuit

OL

CM2

11

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Inverter logic circuit board

AL0

OL

AL1

Power supply See I/O specs on page 4-6

AL2 Load

Page 192

4−43

Output Deviation for PID Control SP,PV

Process variable

The PID loop error is defined as the magnitude (absolute value) of the difference C044 between the Setpoint (target value) and the C044 Process Variable (actual value). When the error magnitude exceeds the preset value for C044, the [OD] terminal signal turns ON. Refer to “PID Loop Operation” on page 4– [OD] 1 56. signal

Setpoint

ON

ON

0 t

Option Code 04

Terminal Symbol OD

Function Name

State

Description

Output Deviation for PID Control

ON when PID error is more than the set threshold for the deviation signal. when PID error is less than the set threshold for the deviation signal Example for terminal [11] (default output configuration shown – see page 3-54):

OFF Valid for inputs: Required settings

11, AL0 – AL2 C044

Notes:

x The example circuit for terminal [11] drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

Inverter output terminal circuit

OD

CM2

11

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): OD

Inverter logic circuit board

AL0

AL1

Power supply

See I/O specs on page 4-6

AL2 Load

OperationsOperations and and MonitoringMonitoring x The default difference value is set to 3%. To change this value, change parameter C044 (deviation level).

Page 193

4−44

Alarm Signal The inverter alarm signal is active when a fault has occurred and it is in the Trip Mode (refer to the diagram at right). When the fault is cleared the alarm signal becomes inactive.

STOP RESET

Run

Stop RUN STOP RESET

We must make a distinction between the alarm Trip Fault signal AL and the alarm relay contacts [AL0], [AL1] Fault and [AL2]. The signal AL is a logic function, which Alarm signal active you can assign to the open collector output terminal [11] or the relay outputs. The most common (and default) use of the relay is for AL, thus the labeling of its terminals. Use an open collector output (terminal [11]) for a low-current logic signal interface or to energize a small relay (50 mA maximum). Use the relay output to interface to higher voltage and current devices (10 mA minimum). Option Code 05

Terminal Symbol AL

Function Name Alarm Signal

State

Description

ON when an alarm signal has occurred and has not been cleared when no alarm has occurred since the last clearing of alarm(s) Example for terminal [11] (default output configuration shown – see page 3-54):

Monitoring

Operations and Monitoring Operations and

OFF Valid for inputs: Required settings

11, AL0 – AL2 C026, C036

Notes: x By default, the relay is configured as normally closed (C036=01). Refer to the next page for an explanation. x In the default relay configuration, an inverter power loss turns ON the alarm output. the alarm signal remains ON as long as the external control circuit has power.

Inverter output terminal circuit

AL

CM2

11 x When the relay output is set to normally closed, a time delay of less than 2 seconds occurs after powerup before the contact is closed. x Terminal [11] is an open collector output, so the electric specifications of [AL] are different from the contact output terminals [AL0], [AL1], [AL2]. x This signal output has the delay time (300 ms nominal) from the fault alarm output. x The relay contact specifications are in “Control Logic Signal Specifications” on page 4–6. The contact diagrams for different conditions are on the next page.

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Inverter logic circuit board

AL0

AL

AL1

Power supply See I/O specs on page 4-6

AL2 Load

Page 194

4−45

The alarm relay output can be configured in two main ways: x

Trip/Power Loss Alarm – The alarm relay is configured as normally closed (C036=1) by default, shown below (left). An external alarm circuit that detects broken wiring also as an alarm connects to [AL0] and [AL1]. After powerup and short delay (< 2 seconds), the relay energizes and the alarm circuit is OFF. Then, either an inverter trip event or an inverter power loss will de-energize the relay and open the alarm circuit x

Trip Alarm – Alternatively, you can configure the relay as normally open (C036=0), shown below (right). An external alarm circuit that detects broken wiring also as an alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only when an inverter trip event occurs, opening the alarm circuit. However, in this configuration, an inverter power loss does not open the alarm circuit.

Be sure to use the relay configuration that is appropriate for your system design. Note that the external circuits shown assume that a closed circuit = no alarm condition (so that a broken wire also causes an alarm). However, some systems may require a closed circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2] from the ones shown.

AL2

AL0

AL2

AL0

Load

Power supply

Load

Power supply

Power ON

Run Mode

AL0-AL1

AL0-AL2

Normal

Closed

Open

ON

Trip

Open

OFF

–

Open

AL0

AL1

Power supply

AL1

AL1

AL2

AL0

Load

Power supply

Load

Power

Run Mode

AL0-AL1

AL0-AL2

ON

Normal

Open

Closed

Closed

ON

Trip

Closed

Open

Closed

OFF

–

Open

Closed

AL1

AL2

OperationsOperations and and MonitoringMonitoring

N.C. contacts (C036=01) N.O. contacts (C036=00) During normal operation When an alarm occurs or During normal operation When an alarm occurs when power is OFF or when power is OFF

Page 195

4−46

Analog Input Disconnect Detect This feature is useful when the inverter receives a speed reference from an external device. Upon input signal loss at either the [O] or [OI] terminal, the inverter normally just decelerates the motor to a stop. However, the inverter can use the intelligent output terminal [Dc] to signal other devices that a signal loss has occurred. Voltage signal loss at [O] terminal - Parameter B082 is the Start Frequency Adjustment. It sets the beginning (minimum) output frequency when the speed reference source is greater than zero. If the analog input at terminal [O] is less than the Start Frequency, the inverter turns ON the [Dc] output to indicate a signal loss condition. Current signal loss at [OI] terminal - The [OI] terminal accepts a 4mA to 20mA signal, with 4mA representing the beginning of the input range. If the input current falls below 4mA, the inverter applies a threshold to detect signal loss. Note that a signal loss is not an inverter trip event. When the analog input value is again above the B082 value, the [Dc] output turns OFF. There is no error condition to clear. Terminal Symbol Dc

Function Name

State

Description

Analog Input Disconnect Detect

ON when the [O] input value < B082 Start Frequency Adjustment (signal loss detected), or when the [OI input current is less than 4mA when no signal loss is detected Example for terminal [11] (default output configuration shown – see page 3-54):

OFF Monitoring

Operations and Monitoring Operations and

Option Code 06

Valid for inputs: Required settings

11, AL0 – AL2 A001=01, B082

Notes: x The [Dc] output can indicate an analog signal disconnect when the inverter is in Stop Mode, as well as Run Mode. x The example circuit for terminal [11] drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

Inverter output terminal circuit

Dc

CM2

11

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Dc

Inverter logic circuit board

AL0

AL1

Power supply

See I/O specs on page 4-6

AL2 Load

Page 196

4−47

PID Second Stage Output The inverter has a built-in PID loop feature for two-stage control, useful for certain applications such as building ventilation or heating and cooling (HVAC). In an ideal control environment, a single PID loop controller (stage) would be adequate. However, in certain conditions, the maximum output energy from the first stage is not enough to maintain the Process Variable (PV) at or near the Setpoint (SP). And, the output of the first stage is in saturation. A simple solution is to add a second stage, which puts an additional and constant amount of energy into the system under control. When size properly, the boost from the second stage brings the PV toward the desired range, allowing the first stage PID control to return to its linear range of operation. The two-stage method of control has some advantages for particular applications. x The second stage is only ON in adverse conditions, so there is an energy savings during normal conditions. x Since the second stage is simple ON/OFF control, it is less expensive to add than just duplicating the first stage. x At powerup, the boost provided by the second stage helps the process variable reach the desired setpoint sooner than it would if the first stage acted alone. x Even though the second stage is simple ON/OFF control, when it is an inverter you can still adjust the output frequency to vary the boost it provides.

x Stage 1 - Inverter #1 operating in PID loop mode, with motor driving a fan x Stage 2 - Inverter #2 operating as an ON/OFF controller, with motor driving a fan Stage #1 provides the ventilation needs in a building most of the time. On some days, there is a change in the building’s air volume because large warehouse doors are open. In that situation, Stage #1 alone cannot maintain the desired air flow (PV sags under SP). Inverter #1 senses the low PV and its PID Second Stage Output at [FBV] terminal turns ON. This gives a Run FWD command to Inverter #2 to provide the additional air flow.

OperationsOperations and and MonitoringMonitoring

Refer to the example diagram below. Its two stages of control are defined as follows:

Page 197

4−48

To use the PID Second Stage Output feature, you will need to choose upper and lower limits for the PV, via C053 and C052 respectively. As the timing diagram below shows, these are the thresholds Stage #1 inverter uses to turn ON or OFF Stage #2 inverter via the [FBV] output. The vertical axis units are percent (%) for the PID setpoint, and for the upper and lower limits. The output frequency, in Hz, is superimposed onto the same diagram. When the system control begins, the following events occur (in sequence in the timing diagram): 1. Stage #1 inverter turns ON via the [FW] Run command. 2. Stage #1 inverter turns ON the [FBV] output, because the PV is below the PV low limit C053. So, Stage #2 is assisting in loop error correction from the beginning. 3. The PV rises and eventually exceeds the PV high limit C052. Stage #1 inverter then turns OFF the [FBV] output to Stage #2, since the boost is no longer needed.

5. The PV continues to decrease until it crosses under the PV low limit (apparent external process disturbance). Stage #1 inverter turns ON the [FBV] output, and Stage #2 inverter is assisting again. Monitoring

Operations and Monitoring Operations and

4. When the PV begins decreasing, only Stage #1 is operating, and it is in the linear control range. This region is where a properly configured system will operate most often.

6. After the PV rises above the PV low limit, the [FW] Run command to Stage #1 inverter turns OFF (as in a system shutdown). 7. Stage #1 inverter enters Stop Mode and automatically turns OFF the [FBV] output, which causes Stage #2 inverter to also stop.

%/Hz PV high limit

Output frequency

PID feedback (PV)

1,2

4

C052

PID setpoint (SP) PV low limit

C053

Stage #1 [FW]

1 0

[FBV] to Stage #2 [FW]

1 0

Events:

3

5

The terminal [FBV] configuration table is on the following page.

6

7 t

Page 198

4−49

Option Code 07

Terminal Symbol FBV

Function Name Feedback Value Check

State

Description

ON x Transitions to ON when the inverter is in RUN Mode and the PID Process Variable (PV) is less than the Feedback Low Limit (C053) x Transitions to OFF when the PID Feedback Value (PV) exceeds the PID High Limit (C052) x Transitions to OFF when the inverter goes from Run Mode to Stop Mode Example for terminal [11] (default output configuration shown – see page 3-54):

OFF

Valid for inputs: Required settings

11, AL0 – AL2 A076, C052, C053

Notes: x The [FBV] is designed for implementing twostage control. The PV high limit and PV low limit parameters, C052 and C053, do not function as process alarm thresholds. Terminal [FBV] does not provide a PID alarm function.

Inverter output terminal circuit

FBV

CM2

11 x The example circuit for terminal [11] drives a relay coil. Note the use of a diode to prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor.

RY

Inverter logic circuit board

AL0

FBV

AL1

Power supply See I/O specs on page 4-6

AL2 Load

OperationsOperations and and MonitoringMonitoring

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54):

Page 199

4−50

Network Detection Signal (Integrated ModBus) The Network Detection Signal output indicates the general status of network communications (integrated ModBus communication). The inverter has a programmable watchdog timer to monitor network activity. Parameter C077 sets the time-out period. If communications stop or pause longer than the specified time-out period, the NDc output turns ON. Option Code 08

Terminal Symbol NDc

Valid for inputs: Required settings

Function Name Network Disconnection Signal (ModBus)

State

Description

ON when the communication watchdog timer (period specified by C077) has timed out. when the communication watchdog timer is satisfied by regular communications activity Example for terminal [11] (default output configuration shown – see page 3-54):

OFF

11, AL0 – AL2 C076, C077

Notes: x To disable the communications watchdog timer, set C077=00.00 sec.

and installation

Operations and Monitoring Inverter Mounting x If you set Communications Error Select to “Disable” (C076=02), you still have the option of using the Network Detection Signal and setting the watchdog time-out period with C077.

Inverter output terminal circuit

NDc

CM2

11

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Inverter logic circuit board

AL0

NDc

AL1

Power supply

AL2 Load

See I/O specs on page 4-6

Additionally, the inverter can respond to a communications time-out in various ways. Refer to the following diagram (top of next page). You configure the desired response via function C076, Communications Error Select. This selects whether or not you want the inverter to trip (alarm with error code E60) and whether to stop the motor or just let it coast. Together, parameters C076 and C077 set the network detection watchdog timeout and the inverter’s response.

Page 200

4−51

Master

Slave Time-out

Watchdog timer C077 = xx.xx sec. [NDc] Alarm C076 = 00 or 01

Logic Output Function The Logic Output Function uses the inverter’s built-in logic feature. You can select any two of the other nine intelligent output options for internal inputs (use C141 and C142). Then, use C143 to configure the logic function to apply the logical AND, OR, or XOR (exclusive OR) operator as desired to the two inputs.

RUN, FA1, FA2, OL, OD, AL, Dc, FBV, NDc

C141 Input A

C142 RUN, FA1, FA2, OL, OD, AL, Dc, FBV, NDc

Input B

Logic function AND, OR, XOR

Input Status A B 0 0 0 1 1 0 1 1

[LOG]

[LOG] Output State AND OR XOR 0 0 0 0 1 1 0 1 1 1 1 0

Inverter Mounting Operations and and installation Monitoring

Intelligent outputs used as internal inputs: