4−52
Option Code 09
Terminal Symbol LOG
Function Name Logic Output Function
State
Description
ON when the Boolean operation specified by C143 has a logical “1” result when the Boolean operation specified by C143 has a logical “0” result Example for terminal [11] (default output configuration shown – see page 3-54):
OFF Valid for inputs: Required settings Notes:
11, AL0 – AL2 C141, C142, C143
Inverter output terminal circuit
LOG
CM2
11
RY and installation
Operations and Monitoring Inverter Mounting
Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Inverter logic circuit board
AL0
LOG
AL1
Power supply See I/O specs on page 4-6
AL2 Load
Page 202
4−53
Network Detection Signal (FieldBus Option) The Network Detection Signal output indicates the general status of network communications when using a FieldBus option. The inverter has a programmable watchdog timer to monitor network activity. Parameter P044 sets the time-out period. If communications stop or pause longer than the specified time-out period, the ODc output turns ON. Option Code 10
Terminal Symbol ODc
Valid for inputs: Required settings
Function Name Network Disconnection Signal (Option module) 11, AL0 – AL2 P044, P045
State
Description
ON when the communication watchdog timer (period specified by P044) has timed out. when the communication watchdog timer is satisfied by regular communications activity Example for terminal [11] (default output configuration shown – see page 3-54):
OFF
Notes: x To disable the communications watchdog timer, set P044=00.00 sec.
Inverter output terminal circuit
ODc
CM2
11
Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Inverter logic circuit board
AL0
ODc
AL1
Power supply See I/O specs on page 4-6
AL2 Load
Inverter Mounting Operations and and installation Monitoring
RY
Page 203
4−54
Low Load Detection Signal The Low Load Detection Signal output indicates the general status of the inverter output current. When the output current becomes less than the value specified by C039, the LOC output turns ON. Option Code 43
Terminal Symbol LOC
Function Name
State
Description
Low Load Detection
ON when the output current becomes less than the value specified by C039 when the output current is more than the value specified by C039 Example for terminal [11] (default output configuration shown – see page 3-54):
OFF Valid for inputs: Required settings Notes:
11, AL0 – AL2 C038, C039
Inverter output terminal circuit
LOC and installation
Operations and Monitoring Inverter Mounting
CM2
11
RY
Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54): Inverter logic circuit board
AL0
LOC
AL1
Power supply See I/O specs on page 4-6
AL2 Load
Page 204
4−55
Analog Input Operation The X200 inverters provide for analog input to command the inverter frequency output value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector, which provide for Voltage [O] or Current [OI] input. All analog input signals must use the analog ground [L]. If you use either the voltage or current analog input, you must select one of them using the logic input terminal function [AT] analog type. Refer to the table on next page showing the activation of each analog input by combination of A005 set parameter and [AT] terminal condition. The [AT] terminal function is covered in “Analog Input Current/Voltage Select” on page 4–22. Remember that you must also set A001 = 01 to select analog input as the frequency source.
AM H
O OI L
+V Ref. Voltage input Current input A GND V/I input select [AT]
A001 Freq. setting
AM H
O OI L Å +-
4-20 mA 0-10 V
Using an external potentiometer is a common way to control the inverter output frequency (and a good way to learn how to use the analog inputs). The potentiometer uses the built-in 10V reference [H] and the analog ground [L] for excitation, and the voltage input [O] for the signal. By default, the [AT] terminal selects the voltage input when it is OFF. Take care to use the proper resistance for the potentiometer, which is 1~2 k:, 2 Watts. Voltage Input – The voltage input circuit uses terminals [L] and [O]. Attach the signal cable’s shield wire only to terminal [L] on the inverter. Maintain the voltage within specifications (do not apply negative voltage). Current Input – The current input circuit uses terminals [OI] and [L]. The current comes from a sourcing type transmitter; a sinking type will not work! This means the current must flow into terminal [OI], and terminal [L] is the return back to the transmitter. The input impedance from [OI] to [L] is 250 Ohms. Attach the cable shield wire only to terminal [L] on the inverter.
AM H
O OI L
1 to 2k:, 2W
AM H
0 to 9.6 VDC, 0 to 10V nominal AM H
4 to 19.6 mA DC, 4 to 20mA nominal
O OI L
+-
O OI L
Å
See I/O specs on page 4-6.
Inverter Mounting Operations and and installation Monitoring
NOTE: If no logic input terminal is configured for the [AT] function, then inverter recognizes that [AT]=OFF.
Page 205
4−56
The following table shows the available analog input settings. Parameter A005 and the input terminal [AT] determine the External Frequency Command input terminals that are available, and how they function. The analog inputs [O] and [OI] use terminal [L] as the reference (signal return). A005 02 03 04 05
[AT] Input ON OFF ON OFF (ignored) (ignored)
Analog Input Configuration Keypad Pot [O] Keypad Pot [OI] [O] [OI]
NOTE: You cannot use [O] and [OI] inputs simultaneously on the X200 series inverter.
and installation
Operations and Monitoring Inverter Mounting
Other Analog Input-related topics: x
“Analog Input Settings” on page 3–13 x
“Additional Analog Input Settings” on page 3–28 x
“Analog Signal Calibration Settings” on page 3–61 x
“Analog Input Current/Voltage Select” on page 4–22 x
“ADD Frequency Enable” on page 4–30 x
“Analog Input Disconnect Detect” on page 4–46
Page 206
4−57
Analog Output Operation In inverter applications it is useful to monitor the inverter operation from a remote location or from the front panel of an inverter enclosure. In some cases, this requires only a panel-mounted volt meter. In other cases, a controller such as a PLC may provide the inverter’s frequency command, and require inverter feedback data (such as output frequency or output current) to confirm actual operation. The analog output terminal [AM] serves these purposes.
AM H Analog Voltage Output
O OI L
+
A GND
10VDC full scale, 1mA max See I/O specs on page 4-6
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as analog GND reference. The [AM] can output inverter frequency or current output value. Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or reverse motor rotation. Use C028 to configure terminal [AM] as indicated below. Func.
Code 00 01
C028
Description Inverter output frequency Inverter output current
Range 0 ~ Max. Frequency (Hz) 0 ~ 200% of rated current
The [AM] signal offset and gain are adjustable, as indicated below. Description [AM] output gain adjustment [AM] output offset adjustment
Range 0.~255. 0.0~10.0
Default 100. 0.0
The graph below shows the effect of the gain and offset setting. To calibrate the [AM] output for your application (analog meter), follow the steps below: 1. Run the motor at the full scale speed, or most common operating speed. a. If the analog meter represents output frequency, adjust offset (C086) first, and then use B080 to set the voltage for full scale output. b. If [AM] represents motor current, adjust offset (C086) first, and then use B080 to set the voltage for full scale output. Remember to leave room at the upper end of the range for increased current when the motor is under heavier loads. AM output offset adjustment
AM output gain adjustment
AM output
AM output
10V
10V
B080=0~255
C086=0~10 Parallel movement 5V
5V
0
0 1/2 FS
Full scale (FS) Hz or A
1/2 FS
Full scale (FS) Hz or A
NOTE: As mentioned above, first adjust the offset, and then adjust the gain. Otherwise the required performance cannot be obtained because of the parallel movement of the offset adjustment.
Inverter Mounting Operations and and installation Monitoring
Func. B080 C086
Page 207
4−58
PID Loop Operation In standard operation, the inverter uses a reference source selected by parameter A001 for the output frequency, which may be a fixed value (F001), a variable set by the front panel potentiometer, or value from an analog input (voltage or current). To enable PID operation, set A071=01. This causes the inverter to calculate the target freq, or setpoint. A calculated target frequency can have a lot of advantages. It lets the inverter adjust the motor speed to optimize some other process of interest, potentially saving energy as well. Refer to the figure below. The motor acts upon the external process. To control that external process, the inverter must monitor the process variable. This requires wiring a sensor to either the analog input terminal [O] (voltage) or terminal [OI] (current).
Setpoint SP
+
Error
Freq. PID Calculation
Inverter
External Process
Motor
PV and installation
Operations and Monitoring Inverter Mounting
Process Variable (PV)
Sensor
When enabled, the PID loop calculates the ideal output frequency to minimize the loop error. This means we no longer command the inverter to run at a particular frequency, but we specify the ideal value for the process variable. That ideal value is called the setpoint, and is specified in the units of the external process variable. For a pump application it may be gallons/minute, or it could be air velocity or temperature for an HVAC unit. Parameter A075 is a scale factor that relates the external process variable units to motor frequency. The figure below is a more detailed diagram of the function. Standard setting F001 Multi-speed settings A020 to A035
Setpoint (Target) Scale factor Reciprocal
Frequency source select
1 A075
Scale factor A072
A001
Potentiometer on keypad
P gain A072 SP
V/I input select [AT] L
A GND
Process Variable (Feedback) Analog input scaling A012
Voltage OI Current
A015
+
I gain A073
A013
+
Frequency setting
D gain A074 Scale factor A075
A011
O
F001
Monitor D004
A014
A076 PID V/I input select
NOTE: You cannot use [O] and [OI] simultaneously. For example, if you select [OI] for the setpoint, it is not possible to use [O] for the Process Variable, and vice versa.
Page 208
4−59
PID Loop Configuration The inverter’s PID loop algorithm is configurable for various applications. PID Output Limit - The PID loop controller has a built-in output limit function. This function monitors the difference between the PID setpoint and the loop output (inverter output frequency), measured as a percentage of the full scale range of each. The limit is specified by parameter A078. x When the difference |(Setpoint – loop output)| is smaller than or equal to the A078 limit value, the loop controller operates in its normal linear range. x When the difference |(Setpoint – loop output)| is larger than the A078 limit value, the loop controller changes the output frequency as needed so that the difference does not exceed the limit. The diagram below shows PID setpoint changes and the related output frequency behavior when a limit value in A078 exists. Limit imposed on output
% Output limit A078 PID Setpoint A078
Limit imposed on output t
Error Inversion - In typical heating loops or ventilation loops, an increase in energy into the process results in an increasing PV. In this case, the Loop Error = (SP – PV). For cooling loops, an increase in energy into the process results in a decreasing PV. In this case, the Loop Error = –(SP – PV). Use A077 to configure the error term. A077 =00 SP
+
Error
6 PV
A077 =01
Freq. PID calculation
SP
PV from process with positive correlation
Other PID-related topics: x “PID Control” on page 3–22 x “PID ON/OFF and PID Clear” on page 4–26 x “Output Deviation for PID Control” on page 4–43 x “PID Second Stage Output” on page 4–47
-
6
Error +
PV
Freq. PID calculation
PV from process with negative correlation
Inverter Mounting Operations and and installation Monitoring
Output freq. Output limit
Page 209
4−60
Configuring the Inverter for Multiple Motors Simultaneous Connections For some applications, you may need to connect two or more motors (wired in parallel) to a single inverter’s output. For example, this is common in conveyor applications where two separate conveyors need to have approximately the same speed. The use of two motors may be less expensive than making the mechanical link for one motor to drive multiple conveyors.
X200
Some of the characteristics of using multiple motors with one drive are: x The inverter output must be rated to handle the sum of the currents from the motors.
and installation
Operations and Monitoring Inverter Mounting x You must use separate thermal protection switches or devices to protect each motor. Locate the device for each motor inside the motor housing or as close to it as possible.
U/T1 V/T2 W/T3
Motor 1
U/T1 V/T2 W/T3
Motor 2 to Nth motor x The wiring for the motors must be permanently connected in parallel (do not remove one motor from the circuit during operation). NOTE: The motor speeds are identical only in theory. That is because slight differences in their loads will cause one motor to slip a little more than another, even if the motors are identical. Therefore, do not use this technique for multi-axis machinery that must maintain a fixed position reference between its axes.
Inverter Configuration for Two Motor Types Some equipment manufacturers may have a single type of machine that has to support two different motor types - and only one motor will be connected at a time. For example, an OEM may sell basically the same machine to the US market and the European market. Some reasons why the OEM needs two motor profiles are: x The inverter power input voltage is different for these markets. x The required motor type is also different for each destination. In other cases, the inverter needs two profiles because the machine characteristics vary according to these situations: x Sometimes the motor load is very light and can move fast. Other times the motor load is heavy and must move slower. Using two profiles allows the motor speed, acceleration and deceleration to be optimal for the load and avoid inverter trip (fault) events. x Sometimes the slower version of the machine does not have special braking options, but a higher performance version does have braking features.
Page 210
4−61
Having two motor profiles lets you store two “personalities” for motors in one inverter’s memory. The inverter allows the final selection between the two motor types to be made in the field through the use of an intelligent input terminal function [SET]. This provides an extra level of flexibility needed in particular situations. See the following table. Parameters for the second motor have a function code of the form x2xx. They appear immediately after the first motor’s parameter in the menu listing order. The following table lists the parameters that have the second parameter register for programming. Function Name
Inverter Mounting Operations and and installation Monitoring
Multi-speed frequency setting Acceleration (1) time setting Deceleration (1) time setting Frequency source setting Run command source setting Base frequency setting Maximum frequency setting Multi-speed frequency setting Torque boost select Manual torque boost value Manual torque boost frequency adjustment V/f characteristic curve selection V/f gain setting Frequency upper limit setting Frequency lower limit setting Acceleration (2) time setting Deceleration (2) time setting Select method to use Acc2/Dec2 Acc 1 to Acc 2 frequency transition point Dec 1 to Dec 2 frequency transition point Level of electronic thermal setting Electronic thermal characteristic Overload restriction operation mode Overload restriction level setting Deceleration rate at overload restriction Source of overload restriction selection Terminal [1] function Terminal [2] function Terminal [3] function Terminal [4] function Terminal [5] function Overload level setting Motor capacity Motor poles setting Motor stabilization constant
Parameter Codes 1st motor 2nd motor A020 A220 F002 F202 F003 F203 A001 A201 A002 A202 A003 A203 A004 A204 A020 A220 A041 A241 A042 A242 A043 A243 A044 A244 A045 A245 A061 A261 A062 A262 A092 A292 A093 A293 A094 A294 A095 A295 A096 A296 B012 B212 B013 B213 B021 B221 B022 B222 B023 B223 B028 B228 C001 C201 C002 C202 C003 C203 C004 C204 C005 C205 C041 C241 H003 H203 H004 H204 H006 H206