Page 211
Page 212
5−1
Inverter System Accessories In This Chapter…
5 page
-
Introduction...................................................................................... 2
-
Component Description .................................................................. 3
-
Dynamic Braking.............................................................................. 5
Inverter System Inverter System Accessories Accessories
Page 213
5−2
Introduction Introduction A motor control system will obviously include a motor and inverter, as well as fuses for safety. If you are connecting a motor to the inverter on a test bench just to get started, that’s all you may need for now. But a fully developed system can also have a variety of additional components. Some can be for noise suppression, while others may enhance the inverter’s braking performance. The figure below shows a system with several possible optional components, and the table gives part number information. From power supply Name Breaker, MCCB or GFI AC reactor (Input choke) RF noise filter EMI filter
Capacitive filter L1
L2
L3
Accessories
Inverter System Accessories Inverter System
+1 Inverter
DC link choke
+ Braking Unit GND T1
T2
T3 RF noise filter AC reactor (Input choke) or LCR filter
Motor
Thermal switch
AC reactor, input side RF noise filter, input side EMI filter (for CE) Capacitive filter DC link choke Braking resistor Braking resistor NEMA-rated Braking unit RF noise filter, output side AC reactor, output side LCR filter
Part No. Series EU, Japan USA ALI-xxx2 HRL-x ZCL-xxx ZCL-xxx FFL100-xxx FFL100-xxx CFI-x CFI-x DCL-x-xx HDC-xxx JRB-xxx-x JRB-xxx-x SRB-xxx-x SRB-xxx-x HRB-x,
NSRBx00-x NJRB-xxx BRD-xxx BRD-xxx ZCL-xxx ZCL-xxx ACL-x2-xxx HRL-xxx Combination: HRL-xxC ACL-x2-xxx LPF-xxx R-2-xxx
See page 5-3 5-4 5-4 5-4 5-5 5-5 5-5
5-5 5-4 5-3 5-3
NOTE: The Hitachi part number series for accessories includes different sizes of each part type, specified by the –x suffix. Hitachi product literature can help match size and rating of your inverter to the proper accessory size. Each inverter accessory comes with its own printed instruction manual. Please refer to those manuals for complete installation details. This chapter gives only an overview of these optional system devices.
Page 214
5−3
Component Descriptions AC Reactors, Input Side This is useful in suppressing harmonics induced on the power supply lines, or when the main power voltage imbalance exceeds 3% (and power source capacity is more than 500 kVA), or to smooth out line fluctuations. It also improves the power factor. In the following cases for a general-purpose inverter, a large peak current flows on the main power supply side, and is able to destroy the inverter module: x If the unbalanced factor of the power supply is 3% or higher x If the power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more) x If abrupt power supply changes are expected Examples of these situations include: 1. Several inverters are connected in parallel, sharing the same power bus 2. A thyristor converter and an inverter are connected in parallel, sharing the same power bus 3. An installed phase-advance (power factor correction) capacitor opens and closes Where these conditions exist or when the connected equipment must be highly reliable, you MUST install an input-side AC reactor of 3% (at a voltage drop at rated current) with respect to the supply voltage on the power supply side. Also, where the effects of an indirect lightning strike are possible, install a lightning conductor. Example calculation: VRS = 205V, VST = 203V, VTR = 197V, where VRS is R-S line voltage, VST is S-T line voltage, VTR is T-R line voltage
Max. line voltage(min .) Mean Line voltage u 100 Meanline voltage
VRS
VRS VST VTR
VRS VST VTR
3
3 u100
205 202 u100 1.5% 202
Please refer to the documentation that comes with the AC reactor for installation instructions.
AC Reactors, Output Side This reactor reduces the vibrations in the motor caused by the inverter’s switching waveforms, by smoothing the waveforms to approximate commercial power quality. It is also useful to reduce the reflected voltage wave phenomenon when wiring from the inverter to the motor is more than 10m in length. Please refer to the documentation that comes with the AC reactor for installation instructions.
Inverter System Inverter System Accessories Accessories
Unbalance factor of voltage =
Page 215
5−4
Zero-phase Reactor (RF Noise Filter) The zero-phase reactor helps reduce radiated noise from the inverter wiring. It can be used on the input or output side of the inverter. The example zero-phase reactor shown to the right comes with a mounting bracket. The wiring must go through the opening to reduce the RF component of the electrical noise. Loop the wires three times (four turns) to attain the full RF filtering effect. For larger wire sizes, place multiple zero-phase reactors (up to four) side-by-side for a greater filtering effect.
EMI Filter The EMI filter reduces the conducted noise on the power supply wiring generated by the inverter. Connect the EMI filter to the inverter primary (input side). The FFL100 series filter is required for compliance to the EMC Class A directive (Europe) and C-TICK (Australia). See “CE–EMC Installation Guidelines” on page D–2.
Accessories
NOTE: European version of X200 series have integrated EMC filter as standard. It is EN61800-3 category C1 for 200V class models (-SFE models), and EN61800-3 category C2 for 400V class models (-HFE models).
RF Noise Filter (Capacitive) This capacitive filter reduces radiated noise from the main power wires in the inverter input side. This filter is not for achieving CE compliance and is applicable to the input side only of the inverter. It comes in two versions - for 200V class inverters or 400V class inverters. Please refer to the documentation that comes with the radio noise filter for installation instructions.
DC Link Choke The DC choke (reactor) suppresses harmonics generated by the inverter. It attenuates the high-frequency components on the inverter’s internal DC bus (link). However, note that it does not protect the diode rectifiers in the inverter input circuit.
Inverter System Accessories
Inverter System Accessories Inverter System
WARNING: The EMI filter has high internal leakage current from power wiring to the chassis. Therefore, connect the chassis ground of the EMI filter before making the power connections to avoid danger of shock or injury.
Page 216
5−5
Dynamic Braking Introduction The purpose of dynamic braking is to improve the ability of the inverter to stop (decelerate) the motor and load. This becomes necessary when an application has some or all of the following characteristics: x High load inertia compared to the available motor torque x The application requires frequent or sudden changes in speed x System losses are not great enough to slow the motor as needed When the inverter reduces its output frequency to decelerate the load, the motor can temporarily become a generator. This occurs when the motor rotation frequency is higher than the inverter output frequency. This condition can cause the inverter DC bus voltage to rise, resulting in an over-voltage trip. In many applications, the over-voltage condition serves as a warning signal that we have exceeded the deceleration capabilities of the system. The X200 inverter can connect to an external braking unit, which sends the regenerative energy from the motor during deceleration to the optional braking resistor(s). The dynamic braking resistor serves as a load, developing heat to stop the motor just as brakes on an automobile develop heat during braking. A switching circuit and power resistor are the main components of the dynamic braking unit that includes a fuse and thermally activated alarm relay for safety. However, be careful to avoid overheating its resistor. The fuse and thermal relay are safeguards for extreme conditions, but the inverter can maintain braking usage in a safe zone.
Dynamic Braking Usage Dynamic braking usage must follow guidelines to avoid overheating. The timing diagram to the right shows the output frequency versus time. Dynamic braking is in effect during the deceleration ramp, and has the following constraints:
Dynamic braking Output freq.
Tb Tc
Dynamic braking maximum continuous ON time Tb ” 10 sec.
Selecting Braking Resistors for External Braking Units 200V Class Inverters The following tables specify the braking options for 200V class X200 inverters and the braking torque for each option. You can connect a single braking unit to the inverter, or two braking units for additional stopping torque.
Inverter
+
Braking unit
Braking unit t
Inverter System Accessories x Dynamic braking maximum duty cycle = 10%, where Tb/Tc ” 0.1 sec.
Page 217
5−6
Use one BRD-E3 braking unit for the braking torque listed in the following table. Note the column meanings in the tables: x
Column “A” = Average braking torque from 60Hz to 3Hz.
x
Column “B” = Average braking torque from 120Hz to 3Hz.
X200 Inverter 200V Models
Model Number
HP
Braking Torque with BRD-E3 Braking Unit
Braking Using built-in torque resistor only without braking unit A B
External resistor added HRB1
HRB2
A
B
120%
HRB3
A
B
A
B
002SFEF/NFU
1/4
50%
150%
120%
004SFEF/NFU
1/2
50%
150%
120%
005SFEF
3/4
50%
150%
120%
007SFEF/NFU
1
50%
100%
80%
150%
011SFEF
1.5
50%
60%
60%
100%
80%
015SFEF/NFU
2
50%
50%
50%
100%
80%
022SFEF/NFU
3
20%
50%
50%
100%
80%
037LFU
5
20%
40%
40%
60%
60%
100%
100%
150%
120%
055LFU
7.5
20%
30%
30%
50%
50%
70%
70%
100%
80%
075LFU
10
20%
20%
20%
40%
40%
50%
50%
80%
80%
Connect a second braking unit in parallel for additional braking torque listed in the following table. X200 Inverter 200V Models
Inverter System Accessories
Model Number
002SFEF/NFU 004SFEF/NFU 005SFEF 007SFEF/NFU 011SFEF 015SFEF/NFU 022SFEF/NFU 037LFU 055LFU 075LFU
HP
1/4 1/2 3/4 1 1.5 2 3 5 7.5 10
Braking Torque with BRD-E3 Braking Unit
Braking Using built-in torque resistor only without braking unit A B 50% 50% 50% 50% 50% 50% 20~40% 20~40% 20% 20%
150% 150% 150% 150% 100% 100% 70% 50% 30% 30%
120% 120% 120% 120% 80% 80% 70% 50% 30% 30%
External resistor added HRB1
HRB2
HRB3
A
B
A
B
A
B
150% 110% 80% 60%
120% 90% 80% 60%
100% 80%
100% 80%
150% 100%
150% 100%
Page 218
5−7
400V Class Inverters The following tables specify the braking options for 400V class X200 inverters and the braking torque for each option. You can connect a single braking unit to the inverter, or two braking units for additional braking torque.
+
Model Number
HP
Braking unit
Use one BRD-EZ3 braking unit for the braking torque listed in the following table. X200 Inverter 400V Models
Braking unit
Inverter
Braking Torque with BRD-EZ3 Braking Unit
Braking Using built-in torque resistor only without braking unit A B
External resistor added HRB1 x (2)
HRB2 x (2)
HRB3 x (2)
A
A
A
B
B
004HFEF/HFU
1/2
50%
150%
150%
007HFEF/HFU
1
50%
150%
150%
015HFEF/HFU
2
50%
100%
100%
022HFEF/HFU
3
20%
60%
60%
030HFEF
4
20%
50%
50%
150%
150%
040HFEF/HFU
5
20%
40%
40%
130%
130%
150%
150%
055HFEF/HFU
7.5
20%
30%
30%
100%
100%
130%
130%
075HFEF/HFU
10
20%
20%
20%
70%
70%
100%
100%
B
Connect a second braking unit in parallel for additional braking torque listed in the following table. X200 Inverter 400V Models
Model Number
HP
Braking Torque with BRD-EZ3 Braking Unit External resistor added HRB1 x (2)
HRB2 x (2)
HRB3 x (2)
A
B
A
A
004HFEF/HFU
1/2
50%
150%
150%
007HFEF/HFU
1
50%
150%
150%
015HFEF/HFU
2
50%
150%
150%
022HFEF/HFU
3
20%
130%
130%
030HFEF
4
20%
100%
100%
040HFEF/HFU
5
20%
70%
70%
055HFEF/HFU
7.5
20%
50%
50%
150%
150%
075HFEF/HFU
10
20%
40%
40%
140%
140%
B
B
Inverter System Accessories
Braking Using built-in torque resistor only without braking unit A B
Page 219
Page 220
6−1
Troubleshooting and Maintenance In This Chapter…
6 page
-
Troubleshooting............................................................................... 2
-
Monitoring Trip Events, History, & Conditions.............................. 5
-
Restoring Factory Default Settings ................................................ 8
-
Maintenance and Inspection........................................................... 9
-
Warranty ......................................................................................... 16
Troubleshooting and Troubleshooting and MaintenanceMaintenance