The text of a manual · part 23 of 31

X200 Series Inverter Instruction Manual, pages 221 to 230

Pages 221 to 230 of 305

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Hitachi X200 Series

Page 221

6−2

Troubleshooting Safety Messages Please read the following safety messages before troubleshooting or performing maintenance on the inverter and motor system. WARNING: Wait at least five (5) minutes after turning OFF the input power supply before performing maintenance or an inspection. Otherwise, there is the danger of electric shock. WARNING: Make sure that only qualified personnel will perform maintenance, inspection, and part replacement. Before starting to work, remove any metallic objects from your person (wristwatch, bracelet, etc.). Be sure to use tools with insulated handles. Otherwise, there is a danger of electric shock and/or injury to personnel. WARNING: Never remove connectors by pulling on its wire leads (wires for cooling fan and logic P.C.board). Otherwise, there is a danger of fire due to wire breakage and/or injury to personnel.

General Precautions and Notes x Always keep the unit clean so that dust or other foreign matter does not enter the inverter. x Take special care in regard to breaking wires or making connection mistakes. x Firmly connect terminals and connectors. x Keep electronic equipment away from moisture and oil. Dust, steel filings and other foreign matter can damage insulation, causing unexpected accidents, so take special care.

Inspection Items This chapter provides instructions or checklists for these inspection items: x Daily inspection

Maintenance

Troubleshooting and Maintenance Troubleshooting and x Periodical inspection (approximately once a year) x Insulation resistance test

Page 222

6−3

Troubleshooting Tips The table below lists typical symptoms and the corresponding solution(s). Symptom/condition

Troubleshooting and Troubleshooting and MaintenanceMaintenance

Probable Cause Solution x Is the frequency command source x Make sure the parameter A001 parameter setting correct? setting A001 is correct x Is the Run command source A002 x Make sure the parameter parameter setting correct? setting A002 is correct x Is power being supplied to terminals x Check terminals [L1], [L2], [L1], [L2], and [L3/N]? If so, the and [L3/N], then [U/T1], POWER lamp should be ON. [V/T2], and [W/T3]. x Turn ON the power supply or check fuses. x Press the Func. key and x Is there an error code E X X displayed? determine the error type. The inverter Eliminate the error cause, outputs [U], [V], then clear the error (Reset). [W] are not x Are the signals to the intelligent x Verify the terminal functions supplying input terminals correct? for C001–C005 are correct. voltage x Is the Run Command active? x Turn ON Run Command enable. x Is the [FW] terminal (or [RV]) The motor connected to [PCS] (via switch, etc.) x Supply 24V to [FW] or [RV] will not run terminal, if configured. x Has the frequency setting for F001 x Set the parameter for F001 to a safe, non-zero value. been set greater than zero? x If the potentiometer is the x Are the control circuit terminals frequency setting source, [H], [O], and [L] connected to the verify voltage at [O] > 0V. potentiometer? x Is the RS (reset) function or FRS x Turn OFF the command(s) (free-run stop) function ON? Inverter x Is the motor load too heavy? x Reduce the load, and test the outputs [U], motor independently. [V], [W] are supplying voltage. The optional x Are the operational settings x Check the operator type remote between the remote operator and setting. operator is the inverter unit correct? used (SRW). x Make connections according to x Are the connections of output terminals [U/T1], [V/T2], and [W/T3] the phase sequence of the motor. In general: correct? FWD = U-V-W, and REV=Ux Is the phase sequence of the motor The direction of the motor is W-V. forward or reverse with respect to reversed [U/T1], [V/T2], and [W/T3]? x Are the control terminals [FW] and x Use terminal [FW] for [RV] wired correctly? forward, and [RV] for reverse. x Is parameter F004 properly set? x Set motor direction in F004.

Page 223

6−4

Symptom/condition

Probable Cause x If using the analog input, is the current or voltage at [O] or [OI]? x Is the load too heavy?

The motor speed will not reach the target frequency (desired speed). x Is the inverter internally limiting the output frequency?

The rotation is unstable x Is the maximum frequency setting A004 correct? x Does the monitor function D001 display the expected output frequency? x Was power turned OFF after a x Edit the data and press the parameter edit but before pressing Store key once. the Store key? No download has x Edits to data are permanently x Wait six seconds or more occurred Inverter stored at power down. Was the time before turning power OFF data us not from power OFF to power ON less after editing data. correct than six seconds? The download x Was the power turned OFF within x Copy the data to the inverter to the inverter six seconds after the display again, and keep power ON for was attempted changed from REMT to INV? six seconds or more after copying. A x Is the inverter in Run Mode? Some x Put inverter in Stop Mode parameter True for parameters cannot be edited during (press the Stop/reset key). certain will not Run Mode. Then edit the parameter. parameters change after an True for all x If you’re using the [SFT] intelligent x Change the state of the SFT edit input (software lock function) - is input, and check the B031 (reverts to parameters the [SFT] input ON? parameter (SFT mode). old

Maintenance

The RPM of the motor does not match the inverter output frequency setting.

Troubleshooting and Maintenance Troubleshooting and x Is the load fluctuation too great? x Is the supply voltage unstable? x Is the problem occurring at a particular frequency?

Solution x Check the wiring. x Check the potentiometer or signal generating device. x Reduce the load. x Heavy loads activate the overload restriction feature (reduces output as needed). x Check max frequency setting (A004) x Check frequency upper limit setting (A061) x Increase the motor capacity (both inverter and motor). x Fix power supply problem. x Change the output frequency slightly, or use the jump frequency setting to skip the problem frequency. x Verify the V/f settings match motor specifications. x Make sure all scaling (such as A011 to A014) is properly set.

setting).

Page 224

6−5

Monitoring Trip Events, History, & Conditions Fault Detection and Clearing The microprocessor in the inverter detects a variety STOP RESET of fault conditions and captures the event, Run Stop recording it in a history table. The inverter output RUN turns OFF, or “trips” similar to the way a circuit STOP RESET breaker trips due to an over-current condition. Most faults occur when the motor is running (refer Trip Fault Fault to the diagram to the right). However, the inverter could have an internal fault and trip in Stop Mode. In either case, you can clear the fault by pressing the Stop/Reset key. Additionally, you can clear the inverter’s cumulative trip history by performing the procedure “Restoring Factory Default Settings” on page 6–8 (setting B084=00 will clear the trip history but leave inverter settings intact).

Error Codes An error code will appear on the display automatically when a fault causes the inverter to trip. The following table lists the cause associated with the error. Error Code

Name

E 01 Over-current event while at constant speed

E 02 Over-current event during E 03 E 04 E 05 deceleration Over-current event during acceleration Over-current event during other conditions Overload protection

E 07 Over-voltage protection E 08 EEPROM error

E 11 CPU error E 12 External trip

When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output. When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor. When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor. A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. The inverter trips and turns OFF its output. A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor. A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.

Troubleshooting and Troubleshooting and MaintenanceMaintenance

E 09 Under-voltage error

Cause(s) The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor is wired incorrectly.

Page 225

6−6

Error Code

Name

E 13 USP

E 14 Ground fault

E 15 Input over-voltage

E 21 Inverter thermal trip

E 30 Driver error

E 35 Thermistor E 37 Emergency Stop E 60 Communications error ---

Under-voltage (brownout) with output shutoff

Cause(s) When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode until the error is cleared. The inverter is protected by the detection of ground faults between the inverter output and the motor upon during powerup tests. This feature protects the inverter, and does not protect humans. The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state. After the fault is cleared, the inverter can enter Run Mode again. When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips, turning the inverter output OFF. An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. The inverter has turned OFF the IGBT module output. When a thermistor is connected to terminals [5] and [L] and the inverter has sensed the temperature is too high, the inverter trips and turns OFF the output. Emergency stop signal is given. The inverter’s watchdog timer for the communications network has timed out. Due to low input voltage, the inverter turns its output OFF and tries to restart. If it fails to restart, then the alarm trips to record the under-voltage error event.

NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still

Maintenance

Troubleshooting and Maintenance Troubleshooting and correct. If the power is turned OFF while the [RS] (Reset) intelligent input terminal is ON, an EEPROM error will occur when power is restored.

Page 226

6−7

Trip History and Inverter Status We recommend that you first find the cause of the fault before clearing it. When a fault occurs, the inverter stores important performance data at the moment of the fault. To access the data, use the monitor functions (Dxxx) and select D081 for details about the present fault (En). The previous two faults are stored in D082 and D083, with D(En-1 and En-2). Each error shifts D081–D082 to D082–D083, and writes the new error to D081. The following Monitor Menu map shows how to access the error codes. When fault(s) exist, you can review their details by first selecting the proper function: D081 is the most recent, and D083 is the oldest. Monitor Menu 1

2

1

2

1

2

FUNC

No error FUNC

No

Error exists? Yes

2

Trip Conditions Error Code

1

2

Output frequency at trip point 2

Motor current at trip point 1

2

DC bus voltage at trip point 1

2

Cumulative inverter operation time at trip point 1

2

Cumulative power-ON time at trip point 1 FUNC

Troubleshooting and Troubleshooting and MaintenanceMaintenance

1

Page 227

6−8

Restoring Factory Default Settings You can restore all inverter parameters to the original factory (default) settings for the intended country of use. After initializing the inverter, use the powerup test in Chapter 2 to get the motor running again. To initialize the inverter, follow the steps below. No. 1

2 3 4 5

Action

Display

Use the FUNC , 1 , and 2 keys to navigate to the “B” Group.

b---

Press the FUNC key.

b001

7 8 9 10

Maintenance

Troubleshooting and Maintenance Troubleshooting and

11

First “B” parameter selected.

Country code for initialization selected 00=Japan, 01=Europe Press the FUNC key. 02 02=USA Confirm the country code is correct. Do not change it unless you are absolutely sure the power input voltage range and frequency matches the country code setting. Press and hold the

1 b085 key until Æ

To change the country code, press 6

Func./Parameter “B” Group selected

1 or

2

Press the FUNC key.

b085

Press the

2 key.

b084

Press the FUNC key.

00

Press the

1 key.

01

Press the STR key.

b084

2 Press and hold the FUNC , and STOP keys. Do not release yet. RESET b084 to set, STR

12

When your country code appears in the display, release all the keys.

EU USA JP

13

Initialization is complete d001 to store.

Country code for initialization selected Initialization function selected 00=initialization disabled, clear trip history only 01=initialization enabled Initialization now enable to restore all defaults First part of special key sequence

Default parameter country code shown during initialization process (left-most char displays alternating pattern) Function code for output frequency monitor shown

NOTE: Initialization cannot be performed with a remote operator panel. Disconnect the dovice and use the inverter’s front keypad.

Page 228

6−9

Maintenance and Inspection Monthly and Yearly Inspection Chart Item Inspected Ambient environment Major devices Overall Power supply voltage

Ground Insulation Mounting

Main circuit

Check for… Extreme temperatures & humidity Abnormal noise & vib. Voltage tolerance

9 9

9

Components

Overheating

9

Housing

Dirt, dust

9 9

Terminal block Secure connections Smoothing Leaking, capacitors swelling Relay(s) Chattering

Cooling fan

Cracks or discoloring Noise Dust

Overall

Display LEDs

Criteria

9

Ambient temperature between – 10 to 40qC, non-condensing Visual and aural Stable environment for electronic controls Digital volt meter, 200V class: measure between 200 to 240V 50/60 Hz inverter terminals 400V class: [L1], [L2], [L3] 380 to 460V 50/60 Hz Digital volt meter, 5 M: or greater GND to terminals Torque wrench M3: 0.5 – 0.6 Nm M4: 0.98 – 1.3 Nm M5: 1.5 – 2.0 Nm Thermal trip No trip events events Visual No abnormalities Visual

No abnormalities

Visual

No abnormalities

9

Aural

9

Visual Power down, manually rotate Visual

Single click when switching ON or OFF Check Ohms of optional braking res. Rotation must be smooth Vacuum to clean

Visual

No abnormalities

Visual

Undistorted appearance

Visual

All LED segments work

9

9 9 9

Note 1:

The life of a capacitor is affected by the ambient temperature. See “Capacitor Life Curve” on page 6–11.

Note 2:

The inverter must be cleaned periodically. If dust accumulates on the fan and heat sink, it can cause overheating of the inverter.

Troubleshooting and Troubleshooting and MaintenanceMaintenance

Capacitor

No odor, discoloring, corrosion No leaks or deformation Legibility

Inspection Method Thermometer, hygrometer

9

Adequate resistance No loose screws

Resistors

Control circuit

Inspection Cycle Month Year

Page 229

6−10

Megger test The megger is a piece of test equipment that uses a high voltage to determine if an insulation degradation has occurred. For inverters, it is important that the power terminals be isolated from the Earth GND terminal via the proper amount of insulation. The circuit diagram below shows the inverter wiring for performing the megger test. Just follow the steps to perform the test: 1. Remove power from the inverter and wait at least 5 minutes before proceeding. 2. Open the front housing panel to access the power wiring. 3. Remove all wires to terminals [R, S, T, PD/+1, PD/+, N/–, U, V, and W]. Most importantly, the input power and motor wires will be disconnected from the inverter. 4. Use a bare wire and short terminals [R, S, T, PD/+1, PD/+, N/–, U, V, and W] together as shown in the diagram. 5. Connect the megger to the inverter Earth GND and to the shorted power terminals as shown. Then perform the megger test at 500 VDC and verify 5MŸ or greater resistance.

Maintenance

Troubleshooting and Maintenance Troubleshooting and

X200

6. After completing the test, disconnect the megger from the inverter. 7. Reconnect the original wires to terminals [R, S, T, PD/+1, PD/+, N/–, U, V, and W]. CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, analog terminals, etc. Doing so could cause damage to the inverter. CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge protector between the main circuit terminals above and the chassis ground. CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable.

Page 230

6−11

Spare parts We recommend that you stock spare parts to reduce down time, including these parts: Part description

Symbol

Cooling fan

FAN

Case

CV

Quantity Used Spare 1 1

1

1

Notes 015S, 022S, 015N, 022N, 015L to 075L 015H to 075H x Housing cover x Main case x Terminal covers

Capacitor Life Curves The DC bus inside the inverter uses a large capacitor as shown in the diagram below. The capacitor handles high voltage and current as it smoothes the power for use by the inverter. So, any degradation of the capacitor will affect the performance of the inverter. Power Input L1 L2

Variable-frequency Drive Motor Converter Rectifier

Internal DC Bus

Inverter

U/T1 V/T2

L3

W/T3

Troubleshooting and Troubleshooting and MaintenanceMaintenance

Capacitor life is reduced in higher ambient temperatures, as the graph below demonstrates. Be sure to keep the ambient temperature at acceptable levels, and perform maintenance inspections on the fan, heat sink, and other components. If the inverter is installed on a cabinet, the ambient temperature is the temperature inside the cabinet.