For the Honeywell RM7890

Page 1

RM7890; RM7895 100 Vac 7800 SERIES Relay Modules PRODUCT DATA The RM7890; RM7895 provides on/off automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. The RM7895 includes an output for the blower motor to provide purging. This document provides installation and static checkout instructions. Other applicable publications are: Form Number

APPLICATION The Honeywell RM7890B; RM7895A Relay Modules are microprocessor based integrated burner controls for automatically fired gas, oil or combination fuel single burner On/Off applications. The RM7890B; RM7895A System consists of the relay module, wiring subbase, amplifier and the RM7895A also requires a purge timer. Options include Keyboard Display Module (KDM), Data ControlBus™ Module, remote display mounting and Modbus communications is available using the S7810M Modbus Module or configuring the S7800 KDM. The RM7890; RM7895 is programmed to provide a level of safety, functional capability and features beyond the capacity of conventional controls.

Description

65-0249

S7810M Modbus Module

65-0084

Q7800A,B 22-Terminal Wiring Subbase Product Data

65-0090

S7800A Keyboard Display Module Product Data.

65-0091

S7810A Data ControlBus Module™ Product Data

65-0095

S7820 Remote Reset Module Product Data

65-0097

221729C Dust Cover Packing Sheet

65-0109

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Flame Amplifiers for the 7800 SERIES Product Data

65-0131

221818A Extension Cable Assembly Product Data

65-0229

7800 SERIES Relay Modules Checkout and Troubleshooting

FEATURES • Safety features:, - - - - Closed loop logic test. Dynamic AMPLI-CHECK™ circuitry. Dynamic input check. Dynamic safety relay test. Dynamic self-check logic.

Contents Application ........................................................................ 1 Features ........................................................................... 1 Specifications ................................................................... 2 Principal Technical Features ............................................. 6 Installation ........................................................................ 7 Wiring ............................................................................... 10 Assembly .......................................................................... 13 Troubleshooting ................................................................ 24

66-1195-01

Page 2

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES, - - Expanded safe-start check. Internal hardware status monitoring. Tamper resistant timing and logic., - Total hours of operation. Fault history providing the six most recent faults: • Cycles of operation at the time of the fault.

• Access for external electrical voltage checks.

• Fault message and code.

• Application flexibility.

• Hours of operation at the time of the fault.

• Dependable, long-term operation provided by microcomputer technology.

• Sequence status at the time of the fault. • Sequence time at the time of the fault.

• Five light emitting diodes (LEDs) for sequence information., Diagnostic information:

• Interchangeable type plug-in flame amplifiers.

• Device type.

• Nonvolatile memory retains history files and sequencing status after loss of power.

• Flame amplifier type. • Flame failure response time.

• Selectable relight or lockout on loss of flame.

• Manufacturing code. • On/Off status of all digital inputs and outputs.

OPTIONAL FEATURES

• Software revision and version of RM7890/ RM7895 and optional Keyboard Display Module.

• Communication interface capability.

• Status of configuration jumpers.

• First-out annunciation and system diagnosis are provided by a two-row by 20-column display located on the optional keyboard display module (KDM).

SPECIFICATIONS

• Local or remote annunciation operation and fault information.

Electrical Ratings: See Table 1.

• Remote reset.

Voltage and Frequency: 100 Vac (+10/-15%), 50/60 Hz (± 10%). Power Dissipation: 10W maximum. Maximum Total Connected Load: 2000 VA. Fusing Total Connected Load: 15A maximum, type SC or equivalent.

• Burner controller data using S7800 Keyboard Display:, - - - - - Flame signal strength. Hold status. Lockout/alarm status. Sequence status. Sequence time. Total cycles of operation.

66-1195 - 01

2

Page 3

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

Terminal No. G Earth G

Table 1. RM7890, RM7895 Terminal Ratings. Description Ratings, Flame Sensor Grounda, L2(N) 3 (RM7890)

Earth Grounda Line Voltage Common Line Voltage Supply (L1)

3 (RM7895) 4 (RM7890) 4 (RM7895) 5 (RM7890) 5 (RM7895)

Alarm Alarm Burner Motor Unused Line Voltage Supply (L1)

6 (RM7890)

Burner Controller and Limits

6 (RM7895) 7 (RM7890) 7 (RM7895) 8 9 10 F(11) 12 to 22

Burner Controller and Limits Unused Airflow Interlock Pilot Valve/Ignition Main Fuel Valve Ignition Flame Sensor Unused, 100 Vac (+10%/-15%), 50/60 Hz (±10%).b 100 Vac, 1A pilot duty. 100 Vac, 1A pilot duty. 100 Vac, 9.8AFL, 58.8ALR (inrush)., 100 Vac (+10%/-15%), 50/60 Hz (±10%).b 100 Vac 8A Run, 43A inrush.b 100 Vac, 1 mA., 100 Vac, 8A run, 43A inrush. 100 Vac.c

60–220 Vac, current limited., a The RM7890 and RM7895 must have an earth ground providing a connection between the wiring subbase and the control panel or equipment. The earth ground wire must be capable of conducting the current to blow a 15A Fast Blow, Type SC, fuse (or equivalent) in the event of an internal short circuit. The RM7890 and RM7895 need a low impedance ground connection to the equipment frame, which, in turn, needs a low impedance connection to earth ground. b 2000 VA maximum connected load to the Relay Module. c See Table 2 and 3. Table 2. Combinations for terminals 8, 9 and 10. Pilot Valve (Terminal 8)

Main Fuel Valve (Terminal 9)

Ignition (Terminal 10)

C

F

A

B

F

No Load

F

F

A

F

No Load

A

D

F

A

D

D

A

D

No Load

A

Table 3. Composition of Each Combination. A 4.5A ignition

B 50 VA Pilot Duty plus 4.5A ignition.

C

D

180 VA ignition plus motor valves with: 660 VA inrush 360 VA open 250 VA hold.

Environmental Ratings: Ambient Temperature: Operating: -40°F to 140°F (-40°C to 60°C). Storage: -60°F to 150°F (-51°C to 66°C). Humidity: 85% relative humidity continuous, noncondensing.

2A Pilot Duty

F 65 VA Pilot Duty plus Motor valves with: 3850 VA inrush 700 VA open 250 VA hold.

Vibration: 0.5G environment. Dimensions: See Fig. 1 and 2.

3

66-1195 - 01

Page 4

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

BURNER CONTROL

5 (127)

1

POWER PILOT FLAME MAIN ALARM RESET

5-1/4 (133)

5 (127) 1

M5148A

OPTIONAL TERMINAL TEST ACCESS SLOT COVER.

Fig. 1. Mounting dimensions of RM7890, RM7895 Relay Module and Q7800A Subbase in in. (mm).

BURNER CONTROL

5 (127)

POWER PILOT

1

FLAME MAIN ALARM RESET

6-3/32 (155)

5 (127) 1

REMOVE ONLY FOR TERMINAL TEST ACCESS.

M5149

Fig. 2. Mounting dimensions of RM7890, RM7895 Relay Module and Q7800B Subbase in in. (mm). Weight: RM7890, RM7895 with Dust Cover: 1 lb, 13 oz (829 grams) unpacked.

Required Components: Plug-in Flame Signal Amplifier (See Table 4). ST7800A Purge Timer (for RM7895 only).

Approvals: Underwriters Laboratories Inc. Listed: File No. MP268, Guide no. MCCZ. Canadian Standards Association Certified: LR9S329-3. Factory Mutual Approved: Report No. J.I.1V9A0.AF. Swiss Re (formerly IRI) Acceptable. Federal Communications Commission: Part 15, Class B, Emissions.

Accessories: Keyboard Display Modules (KDM): S7800A1118 Katakana (Japanese) language. Communications: Modbus using S7810M1003 Modbus Module or configuring the S7800 Keyboard Display. S7810A1009 Data ControlBus™ Module (if no KDM used). Miscellaneous: A7800A1002 7800 SERIES Tester. S7820A1007 Remote Reset Module. 203541 Data ControlBus Connector, 5-wire. 203765 Remote Display Mounting Bracket. 221729 Dust Cover, Relay Module.

Mounting: Q7800A Wiring Subbase for panel mounting. Q7800B Wiring Subbase for wall or burner mounting.

66-1195 - 01

4

Page 5

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

50023821-001 Keyboard Display Module Cover, NEMA 4, clear. 50023821-002 Keyboard Display Module Cover, NEMA 4, clear with reset button. 205321B Flush Display Mounting Kit. 221818A Extension Cable, display, 5 ft (1.52 m). 221818C Extension Cable, display, 10 ft (3.05 m). 123514A Rectification Flame Simulator.

203569 Ultraviolet Flame Simulator IMPORTANT A flame detection system is required for operation and must be ordered separately. Select the applicable flame signal amplifier and matching flame detector from Table 4.

Table 4. Flame Detection Systems. Plug-in Flame Signal Amplifiers

Type

Color

Rectification

Green

Infrared

Ultraviolet

Optical

Red/ White

Self-Checking

Applicable Flame Detectors

Model

Flame Failure Response Timea

Fuel

Type

Models

No

R7847A

No

R7847Ae

3.0 sec

Gas, Ultraviolet oil, coal (Purple Peeper®)

C7012A,C

Dynamic AMPLI-CHECK®

R7847Bc,e

0.8 or 3.0 sec

Gas

C7004, C7007, C7011. Complete Assemblies: C7008, C7009, Q179

Dynamic Ampli-Check®

R7847Bc,e

3.0 sec

Gas, Ultraviolet oil, coal (Purple Peeper®)

3.0 sec.

Gas, Infrared (Lead C7915 oil, coal Sulfide)

e

0.8 or 3.0 sec. Gas

Rectifying Flame Rod Holdersf

Rectifying Flame Rod Holdersf

C7004, C7007, C7011. Complete Assemblies: C7008, C7009, Q179

C7012A,C

No

R7852A

Dynamic AMPLI-CHECK®

R7852Bc

No

R7849A

0.8 or 3.0 sec

Gas, oil Ultraviolet (Minipeeper)

C7027, C7035, C7044d

Dynamic Ampli-Check®

R7849Bc

0.8 or 3.0 sec

Gas, oil Ultraviolet (Minipeeper)

C7027, C7035, C7044d

Dynamic Self-Check

R7861Ab

0.8 or 3.0 sec

Gas, Ultraviolet oil, coal

C7061

Blue

Dynamic Self-Check

R7886A,Mb 3.0 sec

Gas, Ultraviolet oil, coal (Adjustable Sensitivity)

C7076

White

Dynamic Ampli-Check®

R7851B

0.8 or 3.0 sec

Gas, Optical (UV, oil, coal Visible Light)

C7927, C7962

Dynamic Self-Check

R7851Cb

3.0 sec

Gas, Optical (UV oil, coal only)

C7961

Purple a Flame Failure Response Time (FFRT) depends on selection of amplifier. b Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation and shuts down burner if detection system fails.

c Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails. d Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use

C7061A,M Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for twenty-four hours or longer. e R7847A,B Amplifiers with 0.8 second FFRT should NOT be used with C7012A,C Solid State Ultraviolet Detectors. f Order flame rod separately, see flame detector Instructions for holder.

5

66-1195 - 01

Page 6

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

Table 5. Sequence Timing for Normal Operation. Device

Initiate

Standbya

Purgeb

Runa

Pilot Flame Establishing Period

RM7890

10 sec., N/A

4 or 10 sec., RM7895

10 sec., - 4 or 10 sec., a b

Standby and Run can be an infinite time period. Purge is determined by the ST7800 Purge Timing Card selected (RM7895 only).

PRINCIPAL TECHNICAL FEATURES The RM7890 and RM7895 Relay Modules provide all customary flame safeguard functions while providing significant advancements in the areas of safety, annunciation and system diagnostics.

Safety Shutdown (Lockout) Occurs If: 1.

2.

3.

4.

5.

6.

INITIATE PERIOD a. Ac line power errors occurred; see Operations section. b. Configuration jumpers are changed after 200 hours of operation. c. Four minute INITIATE period has been exceeded. d. Purge card is not installed or was removed (RM7895 only). e. Purge card is faulty. STANDBY PERIOD a. Flame signal is present after 240 seconds. b. Ignition/intermittent pilot valve terminal is powered when it should be off. c. Internal system fault occurred. d. Main valve terminal is powered when it should be off. e. Three-second flame failure response time (FFRT) amplifier is installed and configuration jumper is selected for relight (RM7890); see Table 8. f. Purge card is not installed or was removed (RM7895). g. Purge card is faulty. SAFE START CHECK a. Ignition/intermittent pilot valve terminal is energized when it should be off. b. Internal system fault occurred. c. Main valve terminal is energized. PREPURGE PERIOD (RM7895 Only). a. Airflow lockout feature is enabled and the airflow switch does not close after ten seconds or within the specified purge card timing. b. Flame signal is detected after 30 seconds. c. Ignition/pilot valve/intermittent pilot valve terminal is energized when it should be off. d. Main valve terminal is energized when it should be off. e. Internal system fault occurred. f. Purge card is not installed or was removed. g. Purge card is faulty. PILOT FLAME ESTABLISHING PERIOD (PFEP).

66-1195 - 01 a. Ignition/intermittent pilot valve terminal is not energized. b. Internal system fault occurred. c. Main valve terminal is energized when it should be off. d. No flame present at end of PFEP. e. Airflow lockout feature is enabled and the airflow switch opens (RM7895). f. Purge card is not installed or was removed (RM7895 only). g. Purge card is faulty (RM7895 only). RUN PERIOD. a. Ignition terminal is energized when it should be off. b. Internal system fault occurred. c. Main valve terminal is not energized when it should be on. d. No flame is present and configuration jumper is selected for lockout. e. Pilot valve terminal is not energized. f. Airflow lockout feature is enabled and the airflow switch opens (RM7895). g. Purge card is not installed or was removed (RM7895 only). h. Purge card is faulty (RM7895 only).

SAFETY PROVISIONS Internal Hardware Status Monitoring The RM7890; RM7895 Relay Modules analyze the integrity of the configuration jumpers and internal hardware. The RM7895 checks the purge card for correct parity to prevent purge timing shifts and circuitry failures. The POWER LED will blink every four seconds, signifying an internal hardware check.

Closed Loop Logic Test The test verifies the integrity of all safety critical loads, terminals 8, 9 and 10. If the loads are not energized properly - that is, the main valve terminal is powered during STANDBY - the relay module locks out on safety shutdown. The relay module must react to input changes but avoid the occurrence of nuisance shutdown events. Signal conditioning is applied to line voltage inputs to verify proper operation in the presence of normal electrical line noises such as transient high voltage spikes or short periods of line dropout. Signal conditioning is tolerant of synchronous noise (line noise events that occur at the same time during each line cycle).

Dynamic AMPLI-CHECKTM Circuitry Dynamic AMPLI-CHECKTM circuitry tests the flame signal amplifier during burner operation and shuts down the relay module if the flame amplifier fails.

6

Page 7

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

Dynamic Input Check

The optional multi-functional KDM shows elapsed time during PILOT IGN. As an additional troubleshooting aid, it provides sequence timing, diagnostic information, historical information and expanded annunciator information during normal operation or when a safety shutdown or hold occurs.

All system input circuits are examined to assure that the relay module is capable of recognizing the true status of external controls, limits and interlocks. If any input fails this test, a safety shutdown occurs and the fault will be annunciated.

First-out Annunciation reports the cause of safety shutdown or identifies the cause of a failure to start or continue the burner control sequence with text and numbered code using the optional KDM. It monitors all field input circuits, including the flame signal amplifier.

Dynamic Safety Relay Test Checks the ability of the dynamic safety relay contact to open and close. Verifies that the safety critical loads, terminals 8, 9 and 10 can be de-energized, as required, by the Dynamic Self-Check logic.

Self-Diagnostics add to the First-Out Annunciation by allowing the relay module to distinguish between field (external device) and internal (system related) problems. Faults associated within the flame detection subsystem or relay module are isolated and reported by the optional KDM. See the 7800 SERIES Relay Modules Checkout and Troubleshooting, form 65-0229.

Dynamic Self-Check Safety Circuit The microcomputer tests itself and related hardware, and at the same time, the safety relay system tests the microcomputer operation. If a microcomputer or safety relay failure occurs and does not allow proper execution of the self-check routine, safety shutdown occurs and all safety critical loads will be de-energized.

Interlock Requirements (RM7895 Only)

Expanded Safe-Start Check

The Airflow Switch Interlock input provided in the RM7895 is typically connected to an airflow switch. The Airflow Interlock (ILK) input must close ten seconds into PREPURGE or within the specified purge card timing; otherwise, a recycle to the beginning of PREPURGE or lockout occurs, depending on how the airflow switch selectable jumper is configured (see Table 5 in the Operation section).

The conventional safe-start check, which prevents burner startup when flame is indicated at startup, is expanded to include a flame signal check during STANDBY and a safety critical load check.

Off Cycle (Standby) Flame Signal Check

INSTALLATION

The flame detection subsystem (flame detector and amplifier) is monitored during STANDBY. If a flame simulating condition or an actual flame exists for 240 seconds in STANDBY, a system hold occurs and startup is prevented. If the flame signal exists at any time after the 240 seconds during STANDBY, a safety shutdown occurs and is annunciated. An AMPLI-CHECK™ Amplifier is energized continually through STANDBY (and PREPURGE in the RM7895) to detect any possibility of a runaway detector or a flame. When a flame exists, a safety shutdown occurs. A standard amplifier is energized continually through STANDBY (and PREPURGE in the RM7895). When a flame exists, a safety shutdown occurs.

WARNING

Fire or Explosion Hazard. Can cause severe injury, death or property damage. To prevent possible hazardous burner operation, verify local safety requirements are observed each time a control is installed on a burner.

WARNING

Electrical Shock Hazard or Equipment Damage Hazard. Can cause severe injury, death or equipment and control damage. Disconnect the power supply before beginning installation.

Tamper Resistant Timing and Logic Safety and logic timings are inaccessible and cannot be altered or defeated.

Verified Spark Termination

When Installing this Product…

The ignition terminal is monitored to assure spark termination.

1.

First-Out Annunciation and SelfDiagnostics

2.

Sequence Status Lights (LED) provide positive visual indication of the program sequence: POWER, PILOT, FLAME, MAIN and ALARM. The green POWER LED blinks every four seconds, signifying that the relay module hardware is running correctly.

3. 4.

7

Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application. Installer must be a trained, experienced, flame safeguard service technician. After installation is complete, check out the product operation as provided in these instructions.

66-1195 - 01

Page 8

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

Location

IMPORTANT 1. Wiring connections for the relay modules are unique; refer to Fig. 6 and 7 or the correct Specifications for proper subbase wiring. 2. Wiring must comply with all applicable codes, ordinances and regulations. 3. Wiring must comply with NEC Class 1 (Line Voltage) wiring. 4. Loads connected to the relay module must not exceed those listed on the relay module label or the Specifications; see Table 1. 5. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s). 6. All external timers must be Listed or ComponentRecognized by authorities who have proper jurisdiction. 7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s). 8. Two flame detectors can be connected in parallel with the exception of Flame Detectors C7915, C7927,C7961 and C7962. 9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, can cause interference with radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference; in which case, the users at their own expense may be required to take whatever measures are required to correct this interference. 10.This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

66-1195 - 01

Humidity Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85% relative humidity continuous, noncondensing, moisture environment. Condensing moisture can cause a safety shutdown.

Vibration Do not install the relay module where it could be subjected to vibration in excess of 0.5G continuous maximum vibration.

Weather The relay module is not designed to be weather tight. When installed outdoors, locate the relay module inside an approved weather-tight enclosure.

Mounting Wiring Subbase See Fig. 1 and 2 for installation dimensions. 1.

2.

3. 4.

8

Mount the subbase in any position except horizontally with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating. Select a location on a wall, burner or electrical panel. The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for servicing, installation, access or removal of the relay module, expanded annunciator, KDM, flame amplifier, flame amplifier signal voltage probes, run/test switch, electrical signal voltage probes and electrical field connections. For surface mounting, use the back of the subbase as a template to mark the four screw locations. Drill the pilot holes. Securely mount the subbase using four no. 6 screws (not provided).

Page 9

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

L1 L2 (HOT) 1

3

100 Vac

CONFIGURATION JUMPERS

TEST JACK

FLAME SIGNAL

L2

F MICROCOMPUTER RESET PUSHBUTTON

TEST RELAY DRIVE CIRCUIT

SAFETY RELAY CIRCUIT

STATUS LEDs

6

3K

RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS

4K

1K

1K1

2K1 4K2 4K1 2K2

3K1

DDL

OPTIONAL KEYBOARD DISPLAY MODULE

1

1

2

3

CONTROL POWER 10

IGNITION

8

PILOT

9

MAIN VALVE

4

ALARM

INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS

RS485 DDL COMMUNICATIONS

G

2K

POWER SUPPLY LIMITS CONTROLLER

PLUG-IN FLAME AMPLIFIER

FIELD WIRING INTERNAL WIRING

REMOTE RESET

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M32660

Fig. 3. Internal block diagram of the RM7890 (see Fig. 5 for detailed wiring instructions).

9

66-1195 - 01

Page 10

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

L1 (HOT)

L2

1 5

L2

100 Vac PLUG-IN PURGE TIMER CARD

CONFIGURATION JUMPERS

TEST JACK

FLAME SIGNAL

F MICROCOMPUTER TEST

RESET PUSHBUTTON

RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS

6K 7K

SAFETY RELAY CIRCUIT

STATUS LEDs

1K POWER SUPPLY

LOCKOUT INTERLOCK

LIMITS CONTROLLER 6

1K1

7

2K1 5K1 4K1 2K2

6K1 3K1

OPTIONAL KEYBOARD DISPLAY MODULE

1

2

3

CONTROL POWER

10

IGNITION

8

PILOT

9

MAIN VALVE

4

BLOWER

3

ALARM

INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS

RS485 DDL COMMUNICATIONS

G

2K 3K RELAY 4K DRIVE CIRCUIT 5K

DDL

PLUG-IN FLAME AMPLIFIER

FIELD WIRING INTERNAL WIRING

REMOTE RESET

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M32661

Fig. 4. Internal block diagram of the RM7895 Relay Module (see Fig. 6 for detailed wiring instructions).

WIRING

2.

WARNING

1.

3.

Electrical Shock Hazard or Equipment and Control Damage Hazard. Can cause severe injury, death or equipment and control damage. Disconnect the power supply before beginning installation.

4.

For proper subbase wiring, refer to Fig. 5 and 6.

5.

66-1195 - 01

10

For proper remote wiring of the KDM, refer to the Specifications for the KDM (65-0090), Data ControlBus™ Module (65-0091) or Extension Cable Assembly (65-0131). Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be required. All wiring must comply with all applicable electrical codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Voltage) wiring. Recommended wire size and type: See Table 6 for the recommended wire sizes and part numbers.