Spec sheet · Honeywell
RM7890; RM7895 100 Vac 7800 SERIES Relay Modules Product Data
Spec sheet28 pagesPDF 2.0 MB
Product data for the Honeywell RM7890 and RM7895 100 Vac 7800 SERIES relay modules (burner controls): specs, wiring and checkout.
Covers · 1 model
The models it covers
Summary
What is in it
Honeywell product data for the RM7890 and RM7895 100 Vac 7800 SERIES relay modules, microprocessor based burner controls that provide on/off burner sequencing, flame supervision, status indication and self-diagnostics; the RM7895 adds a blower motor output for purging. It gives features, specifications, terminal ratings, flame detection systems, safety provisions, installation, wiring, assembly, sequence of operation, static checkout, checkout tests and troubleshooting.
Its parts
- Application
- Features
- Optional Features
- Specifications
- Principal Technical Features
- Safety Provisions
- Installation
- Wiring
- Assembly
- Operation
- Initiate
- Standby
- Static Checkout
- Checkout
- Troubleshooting
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
Honeywell product data for the RM7890 and RM7895 100 Vac 7800 SERIES relay modules, microprocessor burner controls for single-burner on/off gas, oil or combination fuel applications. It gives the electrical and environmental ratings, accessories, flame amplifier and detector choices, subbase wiring, the operating sequence, checkout tests and troubleshooting.
- Device
- Microprocessor-based integrated burner control for single-burner on/off gas, oil or combination fuel firing p. 1
- Supply voltage
- 100 Vac (+10/-15%), 50/60 Hz (± 10%) p. 2
- Power dissipation
- 10W maximum p. 2
- Connected load
- 2000 VA maximum total; fuse 15A maximum, type SC or equivalent p. 2
- Operating temperature
- -40°F to 140°F (-40°C to 60°C) p. 3
- Weight
- 1 lb, 13 oz (829 grams) with dust cover, unpacked p. 4
- Flame detection
- Plug-in flame signal amplifier and matching flame detector required, ordered separately p. 4, 5
- Wiring subbase
- Q7800A for panel mounting; Q7800B for wall or burner mounting p. 4
- Communications
- Modbus via S7810M1003 Modbus Module or the S7800 Keyboard Display; S7810A1009 Data ControlBus Module if no KDM p. 4
- RM7890 jumpers
- RM7890: JR1 sets pilot flame establishing period (10 s intact, 4 s clipped); JR2 sets flame failure action (relight intact, lockout clipped) p. 16
- Fault history
- Six most recent lockouts kept in nonvolatile memory, viewable on the optional S7800 KDM p. 25
- Display cables
- 221818A extension cable 5 ft (1.52 m); 221818C extension cable 10 ft (3.05 m) p. 5
- Accessories
- A7800A1002 7800 SERIES Tester; S7820A1007 Remote Reset Module; 221729 relay module dust cover; 203765 remote display mounting bracket p. 4
- Approvals
- The manual states UL Listed (File No. MP268), CSA Certified (LR9S329-3) and Factory Mutual Approved p. 4
What this sheet walks you through
- Checking mounting dimensions with the Q7800A or Q7800B subbase p. 4
- Choosing a flame signal amplifier and matching flame detector p. 5
- What causes a safety shutdown in each sequence period p. 6
- Wiring the RM7890 subbase and choosing wire sizes p. 11
- Following the operating sequence from initiate to run p. 15
- Setting the site-configurable jumpers p. 16
- Eliminating ignition interference p. 24
- Running the safety shutdown tests p. 24
- Reading diagnostics and lockout history p. 24, 25
- Meaning of each sequence and hold status p. 26, 27
Good to know
- Clipping the configuration jumpers after 200 hours of operation causes a hard lockout, Fault Code 110. p. 16
- On the RM7890, a 3-second amplifier needs jumper JR2 clipped and removed, or an F46 lockout occurs. p. 16
- The earth ground wire must be able to carry enough current to blow a 15A fast blow, type SC fuse. p. 3
- No wires may be connected to the unused terminals. p. 11
- R7847A,B amplifiers with 0.8 second flame failure response time are not to be used with C7012A,C ultraviolet detectors. p. 5
Questions this sheet answers
What supply voltage does the RM7890 take?
100 Vac (+10/-15%) at 50/60 Hz (± 10%). p. 2
Does the RM7890 come with a flame amplifier?
No. A flame detection system, a plug-in flame signal amplifier with a matching detector, must be ordered separately. p. 4, 5
What causes an F46 lockout on an RM7890?
Using a 3-second amplifier without clipping and removing jumper JR2. p. 16
What does Fault Code 110 mean on the RM7890?
A hard lockout from clipping the configuration jumpers after 200 hours of operation. p. 16
How many lockouts does the RM7890 remember?
The six most recent, each with the cycle, the hour of operation, the fault message and the burner status. p. 25
Contents
Chapters and sections
Each line opens the PDF at its page.
- Application1
- Features1
- Optional Features2
- Specifications2
- Principal Technical Features6
- Safety Provisions6
- Internal Hardware Status Monitoring6
- Closed Loop Logic Test6
- Dynamic AMPLI-CHECKTM Circuitry6
- Dynamic Input Check7
- Dynamic Safety Relay Test7
- Dynamic Self-Check Safety Circuit7
- Expanded Safe-Start Check7
- Off Cycle (Standby) Flame Signal Check7
- Tamper Resistant Timing and Logic7
- Verified Spark Termination7
- First-Out Annunciation and Self- Diagnostics7
- Interlock Requirements (RM7895 Only)7
- Installation7
- Wiring10
- Assembly13
- Operation15
- Initiate15
- Standby16
- Static Checkout17
14 more lines, from page 19 on
- Checkout19
- Equipment Recommended20
- Checkout Summary20
- Preliminary Inspection20
- Flame Signal Measurement20
- Initial Lightoff Check for Proved Pilot21
- Initial Lightoff Check for Direct Spark Ignition (DSI)22
- Pilot Turndown Test (All Installations Using a Pilot)23
- Ignition Interference Test (All Flame Rods)23
- To Eliminate Ignition Interference24
- Flame Signal with Hot Combustion Chamber (All Installations)24
- Safety Shutdown Tests (All Installations)24
- Troubleshooting24