Page 1 of RM7890; RM7895 100 Vac 7800 SERIES Relay Modules Product Data

Spec sheet · Honeywell

RM7890; RM7895 100 Vac 7800 SERIES Relay Modules Product Data

Spec sheet28 pagesPDF 2.0 MB

Product data for the Honeywell RM7890 and RM7895 100 Vac 7800 SERIES relay modules (burner controls): specs, wiring and checkout.

Download the PDF2.0 MB

Covers · 1 model

The models it covers

Summary

What is in it

Honeywell product data for the RM7890 and RM7895 100 Vac 7800 SERIES relay modules, microprocessor based burner controls that provide on/off burner sequencing, flame supervision, status indication and self-diagnostics; the RM7895 adds a blower motor output for purging. It gives features, specifications, terminal ratings, flame detection systems, safety provisions, installation, wiring, assembly, sequence of operation, static checkout, checkout tests and troubleshooting.

Its parts

  1. Application
  2. Features
  3. Optional Features
  4. Specifications
  5. Principal Technical Features
  6. Safety Provisions
  7. Installation
  8. Wiring
  9. Assembly
  10. Operation
  11. Initiate
  12. Standby
  13. Static Checkout
  14. Checkout
  15. Troubleshooting

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

Honeywell product data for the RM7890 and RM7895 100 Vac 7800 SERIES relay modules, microprocessor burner controls for single-burner on/off gas, oil or combination fuel applications. It gives the electrical and environmental ratings, accessories, flame amplifier and detector choices, subbase wiring, the operating sequence, checkout tests and troubleshooting.

Read for this summary: pages 1 to 6, 10 to 12, 15 to 16 and 24 to 28 of 28.

Device
Microprocessor-based integrated burner control for single-burner on/off gas, oil or combination fuel firing p. 1
Supply voltage
100 Vac (+10/-15%), 50/60 Hz (± 10%) p. 2
Power dissipation
10W maximum p. 2
Connected load
2000 VA maximum total; fuse 15A maximum, type SC or equivalent p. 2
Operating temperature
-40°F to 140°F (-40°C to 60°C) p. 3
Weight
1 lb, 13 oz (829 grams) with dust cover, unpacked p. 4
Flame detection
Plug-in flame signal amplifier and matching flame detector required, ordered separately p. 4, 5
Wiring subbase
Q7800A for panel mounting; Q7800B for wall or burner mounting p. 4
Communications
Modbus via S7810M1003 Modbus Module or the S7800 Keyboard Display; S7810A1009 Data ControlBus Module if no KDM p. 4
RM7890 jumpers
RM7890: JR1 sets pilot flame establishing period (10 s intact, 4 s clipped); JR2 sets flame failure action (relight intact, lockout clipped) p. 16
Fault history
Six most recent lockouts kept in nonvolatile memory, viewable on the optional S7800 KDM p. 25
Display cables
221818A extension cable 5 ft (1.52 m); 221818C extension cable 10 ft (3.05 m) p. 5
Accessories
A7800A1002 7800 SERIES Tester; S7820A1007 Remote Reset Module; 221729 relay module dust cover; 203765 remote display mounting bracket p. 4
Approvals
The manual states UL Listed (File No. MP268), CSA Certified (LR9S329-3) and Factory Mutual Approved p. 4

What this sheet walks you through

  • Checking mounting dimensions with the Q7800A or Q7800B subbase p. 4
  • Choosing a flame signal amplifier and matching flame detector p. 5
  • What causes a safety shutdown in each sequence period p. 6
  • Wiring the RM7890 subbase and choosing wire sizes p. 11
  • Following the operating sequence from initiate to run p. 15
  • Setting the site-configurable jumpers p. 16
  • Eliminating ignition interference p. 24
  • Running the safety shutdown tests p. 24
  • Reading diagnostics and lockout history p. 24, 25
  • Meaning of each sequence and hold status p. 26, 27

Good to know

  • Clipping the configuration jumpers after 200 hours of operation causes a hard lockout, Fault Code 110. p. 16
  • On the RM7890, a 3-second amplifier needs jumper JR2 clipped and removed, or an F46 lockout occurs. p. 16
  • The earth ground wire must be able to carry enough current to blow a 15A fast blow, type SC fuse. p. 3
  • No wires may be connected to the unused terminals. p. 11
  • R7847A,B amplifiers with 0.8 second flame failure response time are not to be used with C7012A,C ultraviolet detectors. p. 5

Questions this sheet answers

What supply voltage does the RM7890 take?

100 Vac (+10/-15%) at 50/60 Hz (± 10%). p. 2

Does the RM7890 come with a flame amplifier?

No. A flame detection system, a plug-in flame signal amplifier with a matching detector, must be ordered separately. p. 4, 5

What causes an F46 lockout on an RM7890?

Using a 3-second amplifier without clipping and removing jumper JR2. p. 16

What does Fault Code 110 mean on the RM7890?

A hard lockout from clipping the configuration jumpers after 200 hours of operation. p. 16

How many lockouts does the RM7890 remember?

The six most recent, each with the cycle, the hour of operation, the fault message and the burner status. p. 25

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Application1
  2. Features1
  3. Optional Features2
  4. Specifications2
  5. Principal Technical Features6
    1. Safety Shutdown (Lockout) Occurs If:6
  6. Safety Provisions6
    1. Internal Hardware Status Monitoring6
    2. Closed Loop Logic Test6
    3. Dynamic AMPLI-CHECKTM Circuitry6
    4. Dynamic Input Check7
    5. Dynamic Safety Relay Test7
    6. Dynamic Self-Check Safety Circuit7
    7. Expanded Safe-Start Check7
    8. Off Cycle (Standby) Flame Signal Check7
    9. Tamper Resistant Timing and Logic7
    10. Verified Spark Termination7
    11. First-Out Annunciation and Self- Diagnostics7
    12. Interlock Requirements (RM7895 Only)7
  7. Installation7
    1. When Installing this Product…7
    2. Location8
    3. Mounting Wiring Subbase8
  8. Wiring10
  9. Assembly13
    1. Mounting RM7890; RM789513
    2. Relay Module Mounting13
    3. Dust Cover Mounting13
    4. Installing ST7800 Purge Card (RM7895 Only)13
    5. Installing Plug-In Flame Signal Amplifier13
    6. Installing Flame Detector13
  10. Operation15
    1. Sequence of Operation15
  11. Initiate15
  12. Standby16
    1. Normal Startup16
    2. Selectable Site-Configurable Jumpers16
  13. Static Checkout17
    1. Equipment Recommended17
    2. General Instructions17
14 more lines, from page 19 on
  1. Checkout19
    1. Equipment Recommended20
    2. Checkout Summary20
    3. Preliminary Inspection20
    4. Flame Signal Measurement20
    5. Initial Lightoff Check for Proved Pilot21
    6. Initial Lightoff Check for Direct Spark Ignition (DSI)22
    7. Pilot Turndown Test (All Installations Using a Pilot)23
    8. Ignition Interference Test (All Flame Rods)23
    9. To Eliminate Ignition Interference24
    10. Flame Signal with Hot Combustion Chamber (All Installations)24
    11. Safety Shutdown Tests (All Installations)24
  2. Troubleshooting24
    1. RM7890, RM7895 System Diagnostics24

From the PDF’s own bookmarks.

The whole text · 3 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 2821-28

The file

Revision and size

Revision66-1195-01
PublisherHoneywell
Pages28
PDF2.0 MB
TextText from the PDF itself.