For the Honeywell RM7890

Page 21

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

NOTE: Low fuel pressure limits, if used, could be open; if so, bypass with jumpers during this check. POSITIVE (+) METER LEAD NEGATIVE (-) METER LEAD

1. 2.

ONE MEGOHM/VOLT METER

3.

4.

5. M7382

Fig. 16. Flame signal measurement.

6.

1.

Use a one megohm per volt meter with a 0 to 10 Vdc capability. 2. Set the one megohm per volt meter to the 0 to 10 Vdc range. 3. Insert the positive (red) probe into the + jack of the flame amplifier and the negative (black) probe into the (Com) jack of the flame amplifier (see Fig. 17). 4. Allow a few seconds for the meter reading to stabilize. 5. If using AMPLI-CHECKTM or shutter check amplifiers, read the average stable voltage, disregarding the peaks and valleys caused by the self-checking operation. 6. The meter reading must be as specified in Table 10 after all tests are made and all adjustments are made. As an option, check the flame signal by using the optional KDM.

7.

If the signal is unstable or less than the minimum acceptable voltage, check the flame detector installation and circuitry. 1.

2.

3.

4. 5.

Check the supply voltages at terminals 3 (L1) and L2 (N) for the RM7890 and terminals 5 (L1) and L2 (N) for the RM7895. Make sure the master switch is closed, connections are correct and the power supply is of the correct voltage, frequency and is sinusoidal. Check the detector wiring for defects: a. Deteriorated wiring. b. Incorrect connections. c. Leakage paths caused by moisture, soot or accumulated dirt. d. Open circuits. e. Short circuits. f. Wrong type of wire. For a flame rod, make sure: a. Flame rod is properly located in the flame. b. Ground area is large enough. c. Temperature at the flame rod insulator is no greater than 500°F (260°C). Make sure that the flame adjustment is not too lean. If necessary, reposition the flame detector.

Initial Lightoff Check for Proved Pilot

Open the master switch. Make sure the manual main fuel shutoff valve(s) is closed. Open the manual pilot shutoff valve. If the pilot takeoff is downstream from the manual main fuel shutoff valve(s), slightly open the manual main valve to supply pilot gas flow. Make sure the main fuel is shut off just upstream from the burner inlet, or disconnect power from the automatic main fuel valve(s). Close the master switch and start the system with a call for heat by raising the setpoint of the operating controller, see Fig. 15 or the relay module sequence. The sequence should start the ten-second INITIATE sequence. Let the sequence advance through STANDBY and SAFE-START CHECK (PREPURGE in the RM7895). Ignition spark should occur and the pilot should light. If the pilot ignites, the FLAME LED will be lighted. Proceed to step 8. If the pilot flame is not established in 15 or 30 seconds, safety shutdown occurs. Let the sequence complete its cycle. Consult the equipment operating manual for further information. Push the reset pushbutton and let the system recycle once. If the pilot still does not ignite, make the following ignition/pilot adjustments. a. Open the master switch and remove the relay module from the subbase. b. On the subbase, jumper terminal 3 on the RM7890 (terminal 5 on the RM7895) to ignition terminal 8 or 10, refer to the appropriate wiring diagram (Fig. 4 through 7) to determine the proper terminal. Disconnect the leadwire to the pilot valve if it is connected to the same terminal. c. Close the master switch to energize only the ignition transformer. d. If the ignition spark is not strong and continuous, open the master switch and adjust the ignition electrode spark gap setting to the manufacturer recommendations. e. Make sure the ignition electrodes are clean. f. Close the master switch and observe the spark. g. After a continuous spark is obtained, open the master switch and add a jumper on the subbase from terminal 3 (L1) (RM7890) or terminal 5 (L1) (RM7895) to the pilot terminal 8. Reconnect the leadwire from the pilot valve if it was disconnected in step b. h. Close the master switch to energize both the ignition transformer and the pilot valve. i. If the pilot does not ignite and if the ignition spark is still continuous, adjust the pressure regulator until a pilot is established. j. When the pilot ignites properly and stays ignited, open the master switch and remove the subbase jumper(s) from terminals 3 to 8 or 3 to 10 (terminals 5 to 8 or 5 to 10 on the RM7895). k. Check for adequate bleeding of the fuel line. l. Reinstall the relay module on the subbase, close the master switch and return to step 4.

Perform this check immediately following the preliminary inspection on all installations that use a pilot:

21

66-1195 - 01

Page 22

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

8.

9. 10.

11.

12. 13.

14.

15.

16. 17. 18.

19.

20. 21.

22. 23.

Initial Lightoff Check for Direct Spark Ignition (DSI)

When the pilot ignites, measure the flame signal. If the pilot flame signal is unsteady or approaching the 1.25 Vdc minimum value, adjust the pilot flame size or detector position to provide a maximum and steady flame signal. Recycle the system to recheck lightoff and pilot flame signal. When the RUN period (MAIN IGN period for the RM7895) is displayed by the MAIN LED, make sure the automatic main fuel valve is open; then smoothly open the manual main fuel shutoff valve(s) and watch for main burner flame ignition. When the main burner flame is established, proceed to step 17. If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer, close the manual main fuel shutoff valve(s). Recycle the system to recheck lightoff and pilot flame signal. Let the relay module recycle to the RUN period (MAIN IGN period for the R7895). Smoothly open the manual fuel shutoff valve(s) and try lightoff again. (The first attempt may have been required to purge the lines and bring sufficient fuel to the burner.) If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer, close the manual fuel shutoff valve(s). Check all burner adjustments. If the main burner flame is not established after two attempts: a. Check for improper pilot size. b. Check for excess combustion air. c. Check for adequate fuel flow. d. Check for proper gas supply pressure. e. Check for proper valve operation. f. Check for proper pilot flame positioning. Repeat steps 11 through 15 to establish the main burner flame, then proceed to step 17. With the sequence in RUN, make burner adjustments for flame stability and BTU input rating. Shut down the system by opening the burner switch or by lowering the setpoint of the operating controller. Make sure the main flame goes out. There may be a delay due to gas trapped between the valve(s) and the burner. Make sure all automatic fuel valve(s) close. Restart the system by closing the burner switch and/or raising the setpoint of the operating controller. Observe that the pilot is established during PILOT IGN and the main burner flame is established during RUN (MAIN IGN for RM7895) within the normal lightoff time. Measure the flame signal. Continue to check for the proper signal, see Table 10, through the RUN period. Run the burner through another sequence, observing the flame signal for: a. Pilot flame alone (unless using direct spark ignition). b. Pilot and main flame together. Also observe the time it takes to light the main flame. Ignition of the main flame should be smooth. Return the system to normal operation. Make sure all readings are in the required ranges before proceeding.

Use this check for gas and oil burners that do not use a pilot immediately following the preliminary inspection. Refer to the appropriate sample block diagram of field wiring for the ignition transformer and fuel valve(s) hookup. NOTE: Low fuel pressure limits, if used, could be open; if so, bypass them with jumpers during this check. 1. 2. 3. 4.

5.

6. 7. 8. 9. 10.

11. 12.

13.

14. 15.

16.

17.

NOTE: Upon completing these tests, open the master switch and remove all test jumpers from the subbase terminals, limits/controls or switches.

66-1195 - 01

18.

22

Open the master switch. Complete the normal checkout of the fuel supply and equipment as recommended by the equipment manufacturer. Close all manual main fuel shutoff valve(s). Check that the automatic fuel valve(s) are closed. Make sure fuel is not entering the combustion chamber. Close the master switch and start the system with a call for heat by raising the setpoint of the operating controller; see Fig. 15 or the relay module operating sequences. The primary sequence should start with the 10-second INITIATE sequence. Let the sequence advance through STANDBY and SAFE-START CHECK for the RM7890 (PREPURGE for the RM7895) to Ignition Trial. Ignition spark should occur. Listen for the click of the first stage fuel solenoid valve(s). Let the program sequence complete its cycle. Open the manual fuel shutoff valve(s). Push the reset button and recycle the program sequence through STANDBY and SAFE-START CHECK for the RM7890 (PREPURGE for the RM7895). Watch for the FLAME LED to help determine when the first stage burner flame is established. If it is established, go to step 15. If the first stage burner flame is not established within four seconds, or within the normal lightoff time specified by the equipment manufacturer, close the manual fuel shutoff valve(s) and open the master switch. Check all burner adjustments. Wait about three minutes. Close the master switch, open the manual fuel shutoff valve(s), and try again to light off the burner. The first attempt may have been required to purge the lines and bring sufficient fuel to the burner. If the first stage burner flame is not established within four seconds or within the normal lightoff time specified by the equipment manufacturer, close the manual fuel shutoff valve(s) and open the master switch. If necessary, repeat steps 8 through 13 to establish the first stage burner flame. Then proceed to step 15. When the first stage burner flame is established, the sequence will advance to RUN. Make burner adjustments for flame stability and input rating. If a second stage is used, proceed to step 18. Shut down the system by opening the burner switch or by lowering the setpoint of the operating controller. Make sure the burner flame goes out and make sure all automatic fuel valves close. If used, remove the bypass jumpers from the low fuel pressure limit and subbase. If a second stage is used, make sure the automatic second stage fuel valve(s) opened, and check the lightoff as follows (otherwise proceed to step 19):

Page 23

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

19.

20.

21.

PREPURGE. If the Flame Failure Action jumper is clipped: push the reset pushbutton and allow the RM7890D to recycle to PILOT IGNITION or the RM7895E,F to recycle through PREPURGE. b. As the control attempts to relight the pilot, increase the pilot pressure immediately until the FLAME LED comes on, and then turn it down slowly to obtain a pressure reading just above the dropout point or until the flame signal increases to approximately 1.25 Vdc. This step must be completed within 4 or 10 seconds, depending on the selected PFEP, or lockout occurs. c. Turn the pilot back down slightly but not enough to cause the FLAME LED to go out. (Keep the pilot gas pressure just above the reading noted in step 6 above.)

a. Open the manual second stage fuel valve(s). b. Restart the system by raising the setpoint of the operating controller. c. When the first stage burner flame is established, watch for the automatic second stage fuel valve(s) top open. Observe that the second stage lights off properly. d. Make burner adjustments for flame stability and input rating. e. Shut down the system by lowering the setpoint of the operating controller. Make sure the burner flame goes out and that all automatic fuel valve(s) close. Restart the system by closing the burner switch and/or raising the setpoint of the operating controller. Observe that the burner flame is established during PILOT IGN, within the normal lightoff time specified by the equipment manufacturer. Measure the flame signal. Continue to check for the proper signal, see Table 10, through the RUN period. Any pulsating or unsteady readings will require further attention. Make sure all readings are within the required ranges before proceeding.

NOTE: Step d requires two people, one to open the manual main fuel valve(s) and one to watch for ignition.

NOTE: Upon completing these tests, open the master switch and remove all test jumpers from the subbase terminals, limits/controls or switches. 22.

Return the system to normal operation.

Pilot Turndown Test (All Installations Using a Pilot)

7.

Perform this check on all installations that use a pilot. The purpose of this test is to verify that the main burner can be lit by the smallest pilot flame that will hold in the flame amplifier and energize the FLAME LED. If using AMPLI-CHECK™ and one megohm per volt meter, the flame signal will fluctuate every time the amplifier does a self check.

8. 9. 10.

NOTE: Low fuel pressure limits, if used, could be open. If so, bypass them with jumpers during this test. 1. 2. 3. 4. 5.

6.

11.

Open the master switch. Close the manual main fuel shutoff valve(s). Connect a manometer (or pressure gauge) to measure pilot gas pressure during the turndown test. Open the manual pilot shutoff valve(s). Close the master switch and start the system with a call for heat by raising the setpoint of the operating controller. The primary sequence should start and PILOT IGNITION for the RM7890 (PREPURGE for the RM7895) should begin. After the sequence has entered the normal burner run period, turn the pilot gas pressure down very slowly, reading the manometer (or gauge) as the pressure drops. Stop immediately when the FLAME LED goes out. Note the pressure at this point.

12. 13.

d. With the sequence in the normal burner run mode, make sure the automatic fuel valve(s) is open. Smoothly open the manual main fuel shutoff valve(s) and watch for main burner lightoff. e. If the main flame is not established within five seconds or the normal lightoff period specified by the burner manufacturer, close the manual main fuel shutoff valve(s) and open the master switch. Then return to step 6a. If the burner flame is established in the normal lightoff period, proceed to step 10. Recycle the burner and let the sequence advance to the PILOT IGN period for the RM7890; advance to the PREPURGE period for the RM7895. Increase the pilot flame size by increasing its fuel flow until a smooth main flame is accomplished. Reposition the flame rod until the pilot flame signal voltage is approximately 1.25 to 1.50 Vdc. When the main burner lights reliably with the pilot at turndown, disconnect the manometer (or pressure gauge) and turn up the pilot gas flow to the level recommended by the equipment manufacturer. If used, remove the bypass jumpers from the subbase terminals, limits/control or switches. Run the system through another cycle to check for normal operation. Return the system to normal operation.

Ignition Interference Test (All Flame Rods) Test to be sure that a false signal from a spark ignition system is not superimposed on the flame signal. Ignition interference can subtract from (decrease) or add to (increase) the flame signal. If it decreases the flame signal enough, it causes a safety shutdown. If it increases the flame signal, it can cause the FLAME LED to come on when the true flame signal is below the minimum acceptable value.

NOTE: If there is no flame present for the selected Flame Failure Response Test (FFRT), the relay module will lock out.

Start the burner and measure the flame signal with both ignition and pilot (or main burner) on, and then with only the pilot (or main burner) on. Any significant difference (greater than 0.5 Vdc) indicates ignition interference.

a. If the Flame Failure Action jumper (see Table 6 or 7, JR2) is not clipped: allow the RM7890 to recycle to PILOT IGNITION or the RM7895 to recycle through

23

66-1195 - 01

Page 24

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

To Eliminate Ignition Interference 1. 2. 3.

4. 5.

Make sure there is enough ground area. Be sure the ignition electrode and the flame rod are on opposite sides of the ground area. Check for correct spacing on the ignition electrode: a. 6,000V systems 1/16 in. to 3/32 in. (1.6 mm to 2.4 mm). b. 10,000V systems 1/8 in. (3.2 mm). Make sure the leadwires from the flame rod and ignition electrode are not too close together. Replace any deteriorated leadwires.

5.

Flame Signal with Hot Combustion Chamber (All Installations) 1. 2. 3. 4. 5. 6.

7. 8. 9. 10.

After all initial start-up tests and burner adjustments are completed, operate the burner until the combustion chamber is at the maximum expected temperature. Observe the equipment manufacturer warmup instructions. Recycle the burner under these hot conditions and measure the flame signal. Check the pilot alone for non-DSI (Direct Spark Ignition) applications or the main burner flame for DSI applications. Check the FFRT of the flame amplifier. Lower the setpoint of the operating controller and observe the time it takes for the burner flame to go out. This should be within 0.8 or 3 seconds maximum, depending on the amplifier selected. If the flame signal is too low or unsteady, check the flame detector temperature. Relocate the detector if the temperature is too high. If the response time is still too slow, replace the Plug-in Flame Signal Amplifier. If the detector is relocated or the amplifier is replaced, repeat all required Checkout tests.

IMPORTANT 1. If the relay module fails to shut down on any of these tests, take corrective action (refer to the Troubleshooting section or RM7890, RM7895 diagnostics) and return to the beginning of all checkout tests. 2. When all Checkout tests are completed, reset all switches to original states.

TROUBLESHOOTING RM7890, RM7895 System Diagnostics Troubleshooting control system equipment failures is easier with the relay module self-diagnostics and first-out annunciation through the optional KDM. In addition to an isolated spdt alarm relay (audible annunciation), the relay module provides visual annunciation by displaying the ALARM LED.

Safety Shutdown Tests (All Installations)

Self-diagnostics of the relay module enable it to detect and annunciate both external and internal system problems. External faults such as flame failures and false flame signals are annunciated by a lockout of the relay module that energizes the ALARM LED. Refer to the 7800 SERIES Relay Modules Checkout and Troubleshooting, form 65-0229 for additional information.

Perform these tests at the end of Checkout, after all other tests are completed. If used, the external alarm should turn on. 1. 2.

3.

4.

Press the relay module reset pushbutton to restart the system. Open the Airflow Interlock during PREPURGE, PILOT IGN, MAIN IGN or RUN period (RM7895). a. Safety shutdown occurs if the Airflow ILK Switch Failure configuration jumper (JR3) is clipped (RM7895). Detect flame 240 seconds after entry to STANDBY. a. Simulate a flame to cause the flame signal voltage level to be at least 1.25 Vdc for 30 seconds after the initial 40 second entry into STANDBY (PREPURGE for RM7895). b. Safety shutdown occurs. Observe that pilot does not ignite. a. Close the pilot and main fuel manual shutoff valve(s). b. Depress the reset pushbutton. c. Start the system.

66-1195 - 01 d. Automatic pilot valve(s) should be energized but the pilot cannot ignite. e. Safety shutdown will occur. Observe loss of flame during RUN (if Flame Failure Action configuration jumper, JR2, is selected for Lockout, see Tables 6 and 7). a. Open the main fuel manual shutoff valve(s) and open the manual pilot shutoff valve(s). b. Depress the reset pushbutton. c. Start the system. Startup should be normal and the main burner should light normally. d. After the sequence is in the normal RUN period for at least ten seconds with the main burner firing, close the manual main and pilot fuel shutoff valve(s) to extinguish the main burner flame. e. The flame signal drops below 1.25 Vdc within 0.8 or 3 seconds (depending upon the FFRT of the amplifier) after the main flame goes out. f. Safety shutdown occurs.

The relay module provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system. See Table 13. The optional KDM displays sequence status messages indicating INITIATE, STANDBY, PREPURGE, PILOT IGN, MAIN IGN and RUN. The selectable messages also provide visual indication, current status and historical status of the equipment such as Flame Signal, Total Cycles, Total Hours, Fault History and Diagnostic Information. With this information most problems can be diagnosed without extensive trial and error testing. Information available in the Diagnostic Information file includes: Device Type, Device Suffix, Software Revision, Manufacturing Code, Flame Amplifier Type, Flame Failure Response Time, Selectable Jumper Configuration Status and Terminal Status.

24

Page 25

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

Diagnostic Information Index

Historical Information Index

The relay module with the optional KDM can monitor input/ output terminals and can display the status of the terminal on the KDM display (for example, Pilot Valve T8 1<); see S7800 Keyboard Display Module specification, form 65-0090. A complete terminal description and terminal number are provided. The display shows the actual status of the terminal. If voltage is detected at the terminal, 1 is displayed; but if voltage is not present at the terminal, 0 is displayed.

The relay module has nonvolatile memory that allows it to retain historical information for the six most recent lockouts. Each of the six lockout files retains the cycle when the fault occurred, the hour of operation when the fault occurred, and the fault message and burner status when the fault occurred. The historical information can be viewed by the optional S7800 KDM.

25

66-1195 - 01

Page 26

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

SERVICE NOTE:

SERVICE NOTE:

Remove the access slot covers on the sides of the Q7800 Wiring Subbase to check voltages.

A lockout condition or restart of a relay module can be accomplished by pressing the reset pushbutton on the relay module or by pressing a remote reset pushbutton wired through an optional KDM, Data ControlBus™ Module, extension cable assembly, or remote reset module. A power-up reset module causes an electrical reset of the relay module but does not reset a lockout condition.

WARNING

Electrical Shock Hazard. Can cause severe injury, death or property damage. Replace access slot covers on the Q7800B Wiring Subbase after performing voltage checks.

NOTE: Normal sequences are in bold type, while abnormal sequences are in regular type. Table 13. Sequence and Status Hold Information. Sequence INITIATE

Information The LED indicates the burner status, POWER, which is a stabilization period for the relay module to check for any fluctuations in ac ling voltage inputs or control input on power-up or during normal operation. The timing of the INITIATE period is ten seconds before entering STANDBY.

If the relay is in a HOLD status, the following conditions can exist: INITIATE HOLD: (AC Frequency/Noise)

The LED indicates the burner status, POWER, and that the relay module is waiting for excess line noise to clear up. The burner sequence will not advance into STANDBY until the excess line noise, which prevents sufficient reading of the line voltage inputs, ceases or a line frequency error is detected.

INITIATE HOLD: (AC Line Dropout)

The LED indicates the burner status, POWER, and that ac line power has momentarily dropped out. The burner sequence will not advance into STANDBY until the ac line voltage has stabilized throughout the INITIATE sequence.

INITIATE HOLD: (AC Frequency)

The LED indicates the burner status, POWER, and that line frequency is faster than the expected value. The burner sequence will not advance into STANDBY until the line frequency returns to the proper value.

INITIATE HOLD: (Low Line Voltage)

The LED indicates the burner status, POWER, and that low line voltage has occurred. The burner sequence will not advance into STANDBY until the line voltage is at a sufficient level for proper operating parameters.

STANDBY

The LED indicates the burner status, POWER. The burner can be placed in STANDBY by opening the burner switch or if the operating controller indicates its setpoint has been satisfied. If a demand is present for burner operation, the burner sequence will not advance from STANDBY until the recycle limit closes.

If the relay module is in a HOLD status, the following conditions could exist: PURGE (RM7895 only)

The LED indicates the burner status, POWER, and that it is the period of time before ignition during which time the blower motor is running. The timing of the PURGE period is selectable.

PURGE HOLD: F/G (Flame Detected) (RM7895 Only)

The LED indicates the burner status, POWER and FLAME, and that a flame is detected. The burner sequence will not advance through PREPURGE because a flame is detected as being present. The sequence will hold waiting for the flame signal to clear. If the time exceeds 30 seconds, the relay module will lockout.

PURGE HOLD: T7 (Airflow The LED indicates the burner status, POWER, and that the Airflow Interlock is not closed. The Interlock) (RM7895 Only) sequence will not advance into ignition until the Airflow Interlock proves closed. If this time exceeds a 30-second HOLD, the relay module will lockout. STANDBY HOLD: F/G (Flame Detected)

The LED indicates the burner status, POWER and FLAME, and that a flame is detected. A demand is present for burner operation. The burner sequence will not advance to SAFE START CHECK (PREPURGE in the RM7895) because a flame is detected as being present. The sequence will not advance to SAFE START CHECK until the flame signal clears. If the flame signal does not clear within 40 seconds, the relay module will lockout.

SAFE START CHECK (RM7890 Only)

The LED indicates the burner status, POWER, which is the period of time after STANDBY. The RM7890 is verifying that a flame is not present before the start of Ignition Trials. If a flame is present, the RM7890 will recycle to STANDBY.

66-1195 - 01

26

Page 27

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES

Table 13. Sequence and Status Hold Information. (Continued) Sequence

Information

PILOT IGN

The LED indicates the burner status, POWER, PILOT, and FLAME, which is the period of time the relay module permits the pilot valve and ignition to be energized and the pilot flame to be established.

MAIN IGN (RM7895 Only)

The LED indicates the burner status, POWER, PILOT, FLAME, and MAIN, which is the period of time the RM7895 permits the main valve to be open and the main flame to be tested.

RUN

The LED indicates the burner status, POWER, PILOT, FLAME and MAIN, which is the period of time after the Ignition Trials and before the operating controller setpoint is reached. During this time, the burner is firing under the control of the operating controller.

RESET/ALARM TEST

The LED indicates the burner status, POWER and ALARM. This condition indicates that the reset pushbutton is pressed. If it is held for more than four seconds, the alarm output is energized. The alarm output will be de-energized after the reset pushbutton is released.

27