Page 13
Chapter 2 Functions
2 Functions 2-1 Start Interlock This function keeps the FSD turned off when the power to the SL-R11 is turned on. At this time, the FSD will not turn on even when the SL-C Series connected to the SL-R11 is clear of any obstruction in the detection zone. In order to cancel the start interlock status (in other words, to turn the FSD ON to allow the machine to start), the start/restart input must be input when there are no obstacles in the detection zone. This will cause the FSD to turn on, allowing the cancellation of the start interlock status. Using this function prevents the machine from being automatically started when the power is turned on, or when the start switch, etc., is pressed after safety has been confirmed. ➮ For details, See page 4-4 “4-3-1 Wiring to Start/Restart Input Terminals”.
2
2-2 Restart Interlock The FSD turns off when an obstacle interrupts the detection zone, and this function keeps the FSD turned off even after the obstacle is removed from the detection zone. In order to cancel the restart interlock status (in other words, to turn the FSD ON to allow the machine to restart), the start/restart input must be input when there are no obstacles in the detection zone. This will cause the FSD to turn on, allowing the cancellation of the restart interlock status. This function prevents the machine from automatically starting even when the obstacle detected by the SL-C Series is removed from the detection zone, so after the safety check is completed, the machine can be restarted by pressing the start switch, etc. ➮ For details, See page 4-4 “4-3-1 Wiring to Start/Restart Input Terminals”. Start/restart input timing chart ON Start/restart input OFF ON FSD OFF 35ms Max.
2-3 E-STOP Input
E-STOP input
ON E-STOP input OFF Start/restart input ON FSD OFF 20ms Max.
35ms Max.
2-1
ENGLISH
E-STOP input refers to 2 normally closed signal inputs that are used to rapidly stop the machine when the emergency stop switch or similar button is operated. The SL-R11 has a terminal (E-STOP1 and E-STOP2 input terminals) for receiving the input signal from the emergency stop switch (or similar button) operation, so the machine can be emergency stopped via the SL-R11. SL-R11 requires the start/restart input in order to return to the normal operation from an emergency stop state. That is why the SL-R11 requires the start/ restart input to cancel the interlock state in addition to the manual restart of E-STOP signal input. This function not only makes emergency stopping possible when danger is detected by the SL-C, but can also cause the FSD provided in the SL-R11 to be operated by E-STOP input from an emergency stop switch, etc., so it can be used to make output systems uniform. ➮ For details, See page 4-5 “4-3-2 Wiring to E-STOP Input Terminals”.
Page 14
Chapter 2 Functions
2-4 MPCE (Machine Primary Control Element) Monitor MPCE (Machine Primary Control Element) is the machine's main control element and is used between the SL-R11 control output (FSD) and the machine to directly control the machine start/stop. The MPCE uses safety relays, contactors, and so on, and inputting the feedback signal from these to the MPCE monitor input terminal provided in the SL-R11 makes it possible to monitor MPCE errors. When an MPCE error causes the FSD and MPCE operation not to be linked, the SL-R11 immediately turns off the FSD, and the SL-C Series and SL-R11 go to the lockout condition. ➮ For details, See page 4-6 “4-3-3 Wiring to MPCE Monitor Input Terminal”.
2
MPCE monitor input Timing chart when an error occurs Clear
Clear
Blocked
Blocked
ON MPCE monitor input OFF
ON MPCE monitor input OFF 24ms Max.
292ms Max.
24ms Max.
*
ON
292ms Max.
*
ON
FSD
FSD OFF
OFF
Lockout condition
Lockout condition
Timing chart when normal Clear
Clear
Blocked
Blocked
ON MPCE monitor input OFF
* 24ms Max.
ON MPCE monitor input OFF
292ms Max.
24ms Max.
ON FSD
* Depends on response time of machine’s MPCE
English ENGLISH 2-2
ON FSD
OFF
*
OFF
292ms Max.
Page 15
Chapter 2 Functions
2-5 Main/Sub Setting This is set when making a light interference prevention connection to the SL-C Series. Be sure to read about the light interference prevention connection from the “Safety Light Curtain SL-C Series Instruction Manual.” The light interference prevention connection function is enabled only when a maximum of 4 SL-R11s are connected via a light interference prevention cable and the maximum number of beam axes of the SL-C Series connected to the SL-R11 is 192, only one SL-R11 must be set to the main mode, and all of the other SL-R11 that are connected via light interference prevention cables must be set to the sub mode. ➮ For details, See page 4-7 “4-3-4 Connecting to Main/Sub Select Input Terminal”.
2
2-6 TEST Input The test input forcefully stops light beam transmission from the transmitter by using an external input. The test input is used to see if the machine connected to the SL-C and SL-R11 can stop within the prescribed time when the FSD turns off. For example, when the test input is performed with the SL-C in the normal state (when FSD output is on when all beam axes are clear of any obstruction), the FSD is forced off and only one bar LED of the SL-C flashes red. (However, this excludes when the Fixed Blanking function is used.) This test input cannot be used when the SL-R12EX is used and the Programmable Muting Bank function is enabled. Therefore, the Programmable Muting Bank function must be canceled to enable test input. TEST input ON TEST input OFF
ON FSD OFF 50ms Max.
WARNING
155ms Max.
The TEST input cannot be used as an emergency stop input. Be sure to use the ESTOP input when using the emergency stop function.
2-7 FSD Output The FSD output is the safety relay control output of the SL-R11. There are two FSD outputs, FSD1 and FSD2. They both have the same operation, but if the contacts of one of the relays gets welded together, the other relay is turned off. For this reason, FSD1 and FSD2 must be wired to form an AND circuit.
2-8 AUX Output
2-3
ENGLISH
The AUX relay output is used to monitor the SL-R11’s FSD status using a PLC, etc. The AUX relay operates the same as the FSD relay, but it cannot be used to build a safety system.
Page 16
Chapter 2 Functions
2-9 Relay Replacement and Terminal Block Installation Removal Function This function makes it possible to replace the relay without changing the SL-R11 wiring. This eliminates having to redo the wiring each time the relay is replaced and limits wiring mistakes made during rewiring. ➮ For details, See page 6-1 “6-2 Relay Circuit Board Replacement”.
2-10 Status Indicators
2
Indicators that making it possible to see the (FSD) ON/OFF state or start/restart input terminal input state at a glance are provided.
Indicators TR
Status Indicators
Status Indicators
POWER RESTART FSD-ON
TEST
FSD-OFF
MPCE
Input Status Indicators
POWER RESTART
INTERLOCK E-STOP1
FSD-ON
TEST
FSD-OFF
MPCE
LOCKOUT E-STOP2
See Instruction Manual.
INTERLOCK E-STOP1 LOCKOUT E-STOP2
CAUTION Electric shock
Status Indicators No.
Name
Light Color
1
POWER
Green
2
FSD-ON
Green
3
FSD-OFF
Red
4
INTERLOCK
Yellow
5
LOCKOUT
Red
Operation Status Shows the power status. Lights green when power is supplied. Shows the FSD status. Lights green when FSD output is on. Shows the FSD status. Lights red when the FSD output is off. Lights yellow when the SL-C Series and SL-R11 are in the start/restart interlock state, or when there is an interlock state from the E-STOP input. Turns red when the SL-C and SL-R11 are in the lockout condition.
Input Status Indicators
English ENGLISH
No. Name 6 RESTART 7 TEST 8
MPCE
9 E-STOP1 10 E-STOP2
2-4
Light Color Operation Status Orange Lights orange when the start/restart input terminal is short-circuited. Orange Lights orange when the test input terminal is open. Lights orange when the MPCE monitor function is selected and when Orange the MPCE input terminal is open. Orange Lights orange when the E-STOP1 input terminal is short-circuited. Orange Lights orange when the E-STOP2 input terminal is short-circuited.
Page 17
Chapter 2 Functions
2-11 Mode Switch Settings TR
MODE SWITCH 1,5
MPCE MONITOR
2,6
START INTERLOCK
FSD-ON
TEST
RESTART INTERLOCK
FSD-OFF
MPCE
3,7
POWER RESTART
INTERLOCK E-STOP1
2
ON
4,8
LOCKOUT E-STOP2
1 2
See Instruction Manual.
Mode switch
3 4 5 6 7 8
CAUTION Electric shock
Mode switch function and setting states No. Mode Name When Enabled * 1 MPCE monitor ON 2 Start interlock ON 3 Restart interlock ON – 4 Not used 5 MPCE monitor ON 6 Start interlock ON 7 Restart interlock ON – 8 Not used
When Disabled At Factory Shipment OFF OFF OFF OFF OFF OFF – – OFF OFF OFF OFF OFF OFF – –
(*) Both mode switches in the pair must be on. Ex: The No.1 and No.5 mode switches are on when the MPCE monitor is enabled.
Mode switch setting method 1. Turn off the SL-R11 power. 2. Use a screwdriver to remove the switch cover screws, and then open the switch cover. Mode switch setting 1
Mode switch setting 2
ENGLISH
1 Loosen screw
2 Open lid
2-5
Page 18
Chapter 2 Functions 3. Refer to the table on page 2-5 and change the mode switches.
2 4. Close the switch cover, and use a screwdriver to tighten the screws to secure the cover. (The recommended tightening torque is 0.08 N•m.) 5. Turn on the SL-R11 power, Refer to Chapter 5. Checklist (➮ page 5-1) and check the operation.
CAUTION
WARNING
English ENGLISH 2-6
• The mode switch settings cannot be changed while the power is on. Be sure to turn the power off before making changes. • As shown in the previous table, there are two mode switches provided for each function. Both mode switches must be on to turn the mode on. (Example: To enable the start interlock function, mode switches 2 and 6 must be on prior to supplying power.) • When finished setting the mode switches, be sure to close the switch cover and tighten the screws. • Mode switch settings shall only be set by the responsible personnel for using the system. It must be made so that the machine operators cannot set the mode switches.
Page 19
Chapter 2 Functions
2-12 I/O Circuit TEST input +5V
TEST input
+5V
3
2
Main Control Circuit
4
0V
0V
MPCE monitor
24 V 7 Main Control Circuit
MPCE1 MPCE2 8
0V
0V
0V
E-STOP1, E-STOP2
+ 9 -
E-STOP 1 10
+ 11 -
E-STOP control circuit
E-STOP 2 12
Start/restart input 24 V 1
ENGLISH
2
0V
0V
0V
2-7
Page 20
Chapter 2 Functions FSD1, 2 (Safety relay)
Main Control Circuit
2 AUX (Relay)1
English ENGLISH 2-8