Intelligent Safety Relay Unit SL-R11 Instruction Manual: 3 Mounting and Installation

Pages 21 to 24 of 42, from Intelligent Safety Relay Unit SL-R11 Instruction Manual

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Keyence SL-R11

Page 21

Chapter 3 Mounting and Installation

3 Mounting and Installation 3-1 Installation Location Select an appropriate installation location taking into consideration the cable length to the SL-C Series and the SL-R11 operating environment. Install the SL-R11 in an appropriate enclosure with a minimum protective construction of IP54, such as in the control panel. The SL-R11 is a dedicated control unit for the safety light curtain SL-C Series, so be sure to use it with the SL-C Series connected.

WARNING

3-2 Installation Using a DIN Rail The SL-R11 can be mounted on a DIN rail. An explanation of how to install or remove the SL-R11 to or from a DIN rail is given below.

3

DIN Rail Installation 1. Push hook B down with a screwdriver to release the lock mechanism. (Front View)

Hook B

2.

Hook A

3.

*Push controller until hook B latches. DIN rail

* Hook A latches on DIN rail

Hook B Hook B

4.

[Locked state]

[Unlocked state]

Hook A

ENGLISH

Hook B

* Position hook B so that it is locked.

3-1

Page 22

Chapter 3 Mounting and Installation

DIN Rail Removal Method (Front View)

DIN rail

Push down using a screwdriver. Hook B

About installation inside control panels Always leave at least 30 mm (1.18") of open space between the SL-R11 and other equipment or walls.

3

30mm (1.18")

30mm (1.18")

SL-R11/SL-U2

30mm (1.18")

* When using the SL-U2, position the SL-U2 at least 30 mm (1.18") from the edge of the cabinet. Mounting Orientation Install the SL-R11 in one of the following two orientations: Ceiling

Floor

English ENGLISH 3-2

Page 23

Chapter 3 Mounting and Installation

3-3 Wall Mounting Using Screws The screw fastening holes in the SL-R11 can be used to directly attach the SL-R11 to the wall. Dimensional drawing

2-ø4.2

124

3

37

* ➮ See “1-3 External Dimensions Diagram” (page 1-3) for detailed dimensions. Attach using M4 screws tightened to a recommended torque of 0.7 N•m.

CAUTION

The SL-R11 cannot be attached to the DIN rail and to the wall by screws at the same time.

3-4 Connection to the SL-U2 Recommended Dedicated Power Supply The SL-R11 is supplied with power by connecting to the SL-U2 dedicated power supply via the connector on the side of the SL-R11. The connector is covered with a seal to protect it, so remove the seal before making the connection.

* Install while being careful of the connectors

The connection methods are as follows.

ENGLISH

[1] When mounting on a DIN rail 1. Refer to the figure above, and peel off the power supply connector seal. 2. Mount both the SL-R11 and SL-U2 to the DIN rail. 3. Slide one of the units to connect them both together. 4. Slide the SL-U2 connection hooks to fasten the units together.

3-3

Page 24

Chapter 3 Mounting and Installation

[2] When mounting on the wall with screws 1. Refer to the previous figure, and peel off the power supply connector seal. 2. Refer to the previous, figure, and connect the two units. 3. Slide the SL-U2 connection hooks to fasten the units together. 4. Use M4 screws tightened to a recommended torque of 0.7 N•m to mount both of the units to the wall.

3

English ENGLISH 3-4