The text of a manual · part 6 of 8
Intelligent Safety Relay Unit SL-R11 Instruction Manual: 4 Wiring
Pages 25 to 34 of 42, from Intelligent Safety Relay Unit SL-R11 Instruction Manual
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Keyence SL-R11
Page 25
Chapter 4 Wiring
4 Wiring 4-1 Method for Connection to the SL-C Series • The SL-C Series can be connected to the SL-R11 using only the following cable combinations: SL-PC5P/SL-PC10P and SL-CC10PT/SL-CC10PR. • The maximum length of the SL-C Series connection cables (transmitter and receiver cables) is 30m (98.43 ft.) each. • Using cables that exceed 30m (98.43 ft.) in length could result in unstable operation of the SL-C Series and SL-R11 and cause a serious accident leading to serious injury or death of the machine operator.
WARNING
Use the special cables to connect the SL-C and SL-R11 as shown in the figure below. Connect and secure the cables from the SL-C to the connectors for receiver and transmitter provided on the SL-R11. Connection 2
Connection 1 Connector for transmitter (gray) Connector for Receiver (black) Receiver cable (black) SL-PC PR or SL-CC10PR
4
Transmitter cable (gray) SL-PC PT or SL-CC10PT
* Use the following minimum bend radius when routing SL-C Series cables: 10mm (0.39") or greater for the base of the connector that is connected to the SL-R11, and 5mm (0.2") or greater for all other positions.
4-2 Method for Wiring to the Relay Output Terminal As shown in the table below, the SL-R11 has a relay output terminal block. This is a quick-disconnect type terminal block. Relay output terminal
Wiring example
TR
TR
MODE SWITCH 1,5
MPCE MONITOR
2,6
START INTERLOCK
MODE SWITCH POWER RESTART
RESTART 3,7 INTERLOCK
FSD-ON
TEST
FSD-OFF
MPCE
1,5
MPCE MONITOR
2,6
START INTERLOCK
3,7
RESTART INTERLOCK
INTERLOCK E-STOP1
4,8
POWER RESTART
4,8
LOCKOUT E-STOP2
FSD-ON
TEST
FSD-OFF
MPCE
+24V
0V
INTERLOCK E-STOP1 LOCKOUT E-STOP2
1 FSD1
3 FSD2
4 5 6 7
Unused
8
+24V
9
0V
MPCE 2 IN
ENGLISH
AUX
Name FSD 1 FSD 2 AUX Not used + 24V 0V
MPCE1
See Instruction Manual.
See Instruction Manual.
2
Terminal No. 1, 2 3, 4 5, 6 7 8 9
PLC
OUT 24V 0V
CAUTION
CAUTION
Electric shock
Electric shock
MPCE 1
MPCE 2
Machine Control
M
4-1
Page 26
Chapter 4 Wiring Tighten with flat-head screwdriver.
Loosen with flat-head screwdriver.
Insert wire
• Tightening torque 4.4 lb•in (0.5 N•m) • Wire rating AWG # 22 to 12 (Stranded only, Copper only, min. 60 °C) • Cable stripping dimension 7mm (0.28")
4
4-2-1 How to Replace the Relay Output Terminal Block Loosen the two terminal block replacement screws and pull the terminal block upwards. To install the new terminal block, tighten the two terminal block replacement screws after attaching the terminal block and the SL-R11. (The recommended tightening torque is 0.4 N•m.)
WARNING
English ENGLISH 4-2
• Always turn off the power supply when performing electrical wiring. • The two control outputs (FSDs) provided in the SL-R11 must both be used to build a safety system. Building a safety system with just one of these outputs could cause the system not to stop due to a control output malfunction, which could result in a serious accident, including serious injury or death to the machine operator. • The AUX relay output provided in the SL-R11 is not an output for the safety system, so it cannot be used as a control output (so called FSD) to stop the machine. Using an AUX relay as an output relay is used to build a safety system and stop the machine, could result in the serious injury or death. • When wiring the SL-R11 output terminals to the control circuit of a machine containing the SL-C, check with the machine manufacturer to make sure the wiring is appropriate for the machine being used to ensure that the machine can be stopped correctly. If the wiring is not done correctly for the machine, a serious accident, such as serious injury or death to the machine operator could result. • Follow electrical articles, regulations, standards, and laws for the country or region in which the SL-R11 is being used when performing electrical wiring. • Do not place cables or electrical lines used in wiring the SL-R11 in the same duct as high-voltage electrical or power lines or in parallel with such lines.
Page 27
Chapter 4 Wiring
4-3 Method for Wiring to Signal Input Terminals As shown in the table below, the SL-R11 is provided with a signal input terminal block. First loosen the terminal block screws, and then retighten the terminal block screws after inserting the signal cables. Input terminals Terminal No. 1, 2 3, 4*1 5, 6*1 7, 8 9, 10*1 11, 12*1
Name Start / Restart input TEST input M/S SELECT input *2 MPCE MONITOR input E-STOP1 input E-STOP2 input
TR
POWER RESTART TEST MPCE
LOCKOUT E-STOP2
See Instruction Manual.
*1 When the SL-R11 is shipped, short bars are connected across terminal Nos. 3 and 4, 5 and 6, 9 and 10, and 11 and 12. To use the functions assigned to these terminals, remove the short bar and wire the terminal. *2 Main/Sub select input
FSD-ON FSD-OFF
INTERLOCK E-STOP1
MPCE1 MPCE2
CAUTION
4
Electric shock
2 Insert wire
Loosen with flat-head screwdriver
Tighten with flat-head screwdriver
1
3
• Tightening torque 4.4 lb•in (0.5 N•m) • Wire rating AWG #22 to 14 (Stranded only, Copper only, min. 60 °C) • Cable stripping dimension 10mm (0.39")
ENGLISH 4-3
Page 28
Chapter 4 Wiring
4-3-1 Wiring to Start/Restart Input Terminals The start/restart input terminals are used to connect a signal input (switch, etc.) to cancel the interlock condition when the machine starts/restarts is run. To use the start/restart interlock function and E-STOP function, a signal input, such as a switch, must be connected to this input terminal. Refer to the following wiring diagram when wiring. Wiring diagram Start / Restart input TEST input M/S SELECT input MPCE MONITOR input E-STOP1 input E-STOP2 input
4 Timing chart ON
10 ms. min.
Start/Restart input OFF ON FSD OFF 35ms
WARNING
CAUTION
English ENGLISH 4-4
• When wiring the signal input, such as a switch, to this terminal, install the mechanism used to reset the interlock in a position from which the condition of the entire hazardous zone can be checked. Do not install the reset mechanism in a position where it can be operated within the hazardous zone. • Confirm that there are no people or objects in the hazardous zone before operating the start/restart input means. • Use a normally open device, for the start/restart input. • The start/restart input terminals connect to the 24V DC output terminal. Therefore, the device, using the start/restart input must be rated for 24V DC or higher. However, because this terminal is only used for start/restart input, it cannot be used to supply power to other devices.
Page 29
Chapter 4 Wiring
4-3-2 Wiring to E-STOP Input Terminals The E-STOP input terminals are used to connect a signal input, such as an emergency stop switch, for stopping the machine to which the SL-C is installed. The terminals are normally closed terminals, so jumpers are placed across the terminals at the time of shipment to create a short-circuit across the terminals. When an emergency stop switch is connected to the E-STOP input terminal, an emergency stop switch that satisfies the following specifications must be used. When a signal is input to the E-STOP input terminal, the FSD turns off and the machine stops. (For detailed requirements in addition to the following, refer to ISO13850.) 1.The emergency stop switch actuator shall be a mushroom-shaped push button or a rope type. 2.The emergency stop switch actuator shall be colored red. 3.There are positive opening operation, and the normal status of the contact is closed. 4.Resetting the emergency stop switch shall only be possible as the result of a manual action on the emergency stop switch itself. (In other words, it is a self-tripping switch.) 5.Have a third-party certification organization (UL, etc.) verify that the emergency stop switch complies with the regulations, standards, and laws of the country or region where the SL-R11 will be used. In addition, when connecting one emergency stop switch to the E-STOP input terminal, the wiring is as shown below, so refer to the following wiring.
4
Wiring diagram Start / Restart input TEST input M/S SELECT input MPCE MONITOR input E-STOP1 input E-STOP2 input
Timing chart ON E-STOP input OFF Start/restart input
10 ms. min.
ON FSD OFF 20ms Max.
WARNING
35ms Max.
4-5
ENGLISH
• Depending on how the emergency stop switch is used, the electrical articles, regulations, standards, and laws of the country or region where the SL-C Series and SL-R11 will be used must be complied with, so refer to all related requirements when using these devices. • When no wiring is connected to the E-STOP input terminal, do not remove the jumper (short bar) attached to the E-STOP input terminal at factory shipment. • The SL-C Series and SL-R11 interlock states are designed to remain unchanged even if the emergency stop switch is reset. To restart the SL-C Series and SLR11, emergency stop switch reset and restart input are required, be sure to ➮ See “4-3-1 Wiring to Start/Restart Input Terminals” (page 4-4) regarding restart input.
Page 30
Chapter 4 Wiring
4-3-3 Wiring to the MPCE Monitor Input Terminal Two MPCEs are used in the machine control circuit. The MPCE monitor function monitors the operation of MPCE1 and MPCE2 to detect control circuit errors and MPCE unit errors that prevent the transmission of the FSD output signal to the machine. When an error is detected, the SL-C Series and SL-R11 go to the lockout condition. To enable this feature, it is necessary to set the mode switches of MPCE monitor to “Enable” according in the instructions in section 2-11 “Mode Switch Settings” (➮ page 2-5). Use a device for the MPCE that has normally closed contacts and that has a maximum response delay time of 292ms. In addition, when connecting a MPCE to the MPCE monitor input terminal, the wiring is as shown below, so refer to the example when wiring. Wiring diagram Start / Restart input TEST input M/S SELECT input
MPCE1 MPCE2
MPCE MONITOR input
4
E-STOP1 input E-STOP2 input
1.Wire the MPCE1 relay coil to FSD1. 2.Wire the MPCE2 relay coil to FSD2. 3.To enable the MPCE monitor, connect the MPCE1 normally closed contact and MPCE2 normally closed contact in series, and then connect them to the MPCE monitor input terminal. Timing chart Timing chart when an error occurs Clear
Clear
Blocked
Blocked
ON MPCE monitor input OFF
* 24ms Max.
ON MPCE monitor input OFF
292ms Max.
* 24ms Max.
ON
292ms Max.
ON
FSD
FSD OFF
OFF
Lockout condition
Lockout condition
Timing chart when normal
English ENGLISH
Clear
Clear
Blocked
Blocked
ON MPCE monitor input OFF
* 24ms Max.
ON MPCE monitor input OFF
292ms Max.
24ms Max.
ON FSD
* Depends on response time of machine’s MPCE
4-6
ON FSD
OFF
*
OFF
292ms Max.
Page 31
Chapter 4 Wiring
WARNING
• Use an appropriate MPCE device after referring to all of the standards and regulations relating to the MPCE to be used in the machine. • To use the MPCE monitor, make the proper wiring for the machine control system, and have the machine manufacturer check the wiring for correctness to ensure that the machine can be properly stopped. If the wiring is not done correctly for the machine, the MPCE monitor could malfunction, resulting in a serious accident that could cause serious injury or death to the machine operator. • Only one MPCE monitor input terminal system exists in the SL-R11. Therefore, to use the MPCE monitor, the feedback signal output from the MPCE1 and MPCE2 must be connected in series. If they are not connected in series, the MPCE monitor could malfunction, resulting in a serious accident that could cause serious injury or death to the machine operator.
4-3-4 Connecting to Main/Sub Select Input Terminal The main/sub select input terminal is used when a light interference prevention connection is made to prevent SL-C Series light interference. Be sure to read the “Safety Light Curtain SL-C Series Instruction Manual” regarding interference prevention connections. When making a light interference prevention connection, main and sub settings must be made for the SLR11 connected to the SL-C Series. At this time, follow the instructions below to wire to this terminal. In case of main mode: In case of sub mode:
CAUTION
4
Use the attached jumper to short-circuit between these terminals. Remove the attached jumper.
Selecting between the main and sub is not possible during SL-C Series and SLR11 operation. Be sure to turn off the power before making the settings using the above wiring.
Main
Sub
ENGLISH 4-7
Page 32
Chapter 4 Wiring
4-3-5 Wiring to the Test Input Terminal Use for test Input. During normal operation: Short-circuit between 3 and 4 Test mode: Open between 3 and 4 Start / Restart input TEST input M/S SELECT input MPCE MONITOR input E-STOP1 input E-STOP2 input
4
Timing chart ON TEST input OFF
ON FSD OFF 50m Max.
English ENGLISH 4-8
155ms Max
Page 33
Chapter 4 Wiring
4-4 About the Light Interference Prevention Connection 4-4-1 What is the Light Interference Prevention Connection? Be sure to read the “Safety Light Curtain SL-C Series Instruction Manual” if you plan to use this feature. By establishing a light interference prevention connection, you can prevent light interference between 2 or more sets of SL-C Series that are connected to the SL-R11. This feature is active when the total number of connected SL-R11 units is 4 or less. To enable the light interference prevention function, the power to the main SL-R11 units and sub SL-R11 units must be turned on. (If the power supply of a sub unit is turned OFF during operation, this unit and the inferior sub units to it go to lockout condition and their operations are stopped.)
4-4-2 Parts Required for Connection Name Model Connector DF1E-3S-2.5C Crimp terminal DF1B-2022SC
2-wire shielded cable AWG #20 to 22
Cable
4-4-3
Manufacturer HIROSE ELECTRIC CO., LTD.
Quantity 2 6 1 (30 m (98.43 ft.) or less)
Notes KEYENCE also offers OP-42365 as an option (set of 2 connectors and 6 crimp terminals).
4
Supplied by customer.
Main/sub Switching Input Setting
One of the SL-R11 units sharing the light interference prevention connection should be set as the main, while all remaining SL-R11 units are configured as subs. See “4-3-4 Connecting to Main/Sub Select Input Terminal” (➮ page 4-7) for information about how to make this setting.
4-4-4
Wiring Connections Rear of SL-R11
Remove the sticker on the rear of the SL-R11.
3 2 1
Pin No. Description 1 Interference prevention (-) 2 Shielding (0 V) 3 Interference prevention (+)
ENGLISH
Wiring Diagram
3 2 1
3 2 1 Connector
2-wire shielded cable
Connector
4-9
Page 34
Chapter 4 Wiring Connect the SL-R11 units after assembling the connectors, crimp terminals, and cables. <Main>
<Sub>
<Main>
<Sub>
When connecting 2 units
<Sub>
<Sub>
When connecting 4 units
4 WARNING
English ENGLISH 4-10
Using cables other than those specified or with a length in excess of 30m (98.43 ft.) may result in significant harm to machinery operators, including serious injury or death. Do not strip away more than 100mm (3.93") of the shielding wire when connecting system wiring.