Page 11

Remote I/O Getting Started

1--6

Getting Started

Number of Masters In its simplist form, you may want to use only one master in your CPU base and then attach from one to seven remote I/O bases. However, in addition to the simple and Slaves configuration, more than one master can be placed in the CPU base. You may use a Allowed maximum of two masters per CPU base. Here is an example where we have placed two masters in the CPU base and then attached a total of six remote I/O racks.

Two Masters in the Same Base (2--Channel)

Remote Masters

Maximum of 2 per CPU base

CH 1

CH 2

Masters can go in any slot.

Remote Slaves

3300ft (1000m) Max.

Maximum of 7 remote bases per channel.

Allowable distance is from furthest slave to the remote master.

Distance Between Each slave belonging to the same master is hooked together in a daisy chain using a Slaves and Master, shielded twisted pair cable. The last slave unit in the daisy chain cannot be further than 3300 feet from the CPU base. You set switches that designate the slaves as No. Baud Rates 1, No. 2, etc. There is an additional switch on each unit to set the baud rate for communication. You have your choice of either 19.2 kB or 38.4 kB. Slaves and Master must be set to the same baud rate. Let’s now take a closer look at each of the remote I/O modules.

Page 12

Getting Started

1--7

Remote Master (D4-RM) Features

DIAG--Turns ON when there is a hardware failure.

RUN--Turns ON when the module is operating correctly.

Remote Master

PAR--Turns ON when there is a parity error in your communications.

I/O--Turns ON when ladder setup does not match the actual I/O, or the rotary switch is set to 0, 8 or 9, or a slave module controlled by the D4-RM causes an error.

LINK--Turns ON when there is a communications error. UNIT ADRS--Rotary switch for setting the module to be the master or a slave---bases 0 through 7.

MSTR--Turns ON to indicate that it is configured as a master.

T---Terminating point that is connected to point 1 with a jumper at the master and final slave base units. 1--1st wire of twisted pair 2--2nd wire of twisted pair 3--Shield of twisted pair

RUN RELAY--Internal relay that is closed as long as there is a communications link present.

Specifications

G--Ground connection

Number of Masters per CPU

2 max. for DL430 or DL440

Maximum No. Slaves Supported

7

Number of Remote I/O Points per CPU

512

Module Type

Intelligent

Installation Requirements

Any slot, CPU base only

Internal Power Consumption

300 mA maximum

Digital I/O Consumed

None

Run Output Relay Rating

250 VAC at 1A 30 VDC at 1A

Communication Baud Rates

19.2 kB or 38.4 kB (Switch Selectable)

Communication Method

Asynchronous (half-duplex)

Communication Cabling

RS-485 twisted pair Belden 9271 or equivalent

Maximum Transimission Distance

3300 ft. (1000 meters)

Operating Temperature

32 to 140° F (0 to 60_ C)

Storage Temperature

--4 to 158° F (--20 to 70_ C)

Relative Humidity

5 to 95% (non-condensing)

Environmental air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3--304

Remote I/O Getting Started

PWR--Turns ON at power up.

Page 13

1--8

Getting Started

Remote I/O Getting Started

Remote Slave (D4-RS or D4-RSDC) Features I/O--Turns ON when the communications link is set up wrong, or the rotary switch is set to 0, 8 or 9, or a slave module controlled by the D4-RM causes an error. BLINKS when module user power supply fails (e.g. analog module with no 24VDC connected).

Remote Slave

PWR--Turns ON at power up. RUN--Turns ON when the module is operating correctly. DIAG--Turns ON when there is a hardware failure. RUN RELAY

PAR--Turns ON when there is a parity error in your setup. LINK--Turns ON when there is a communications error.

24-VOLT AUXILLARY POWER LOGIC GROUND CHASSIS GROUND

T---Terminating point that is connected to point 1 with a jumper at the final slave base unit.

POWER1 UNIT ADRS--Rotary switch for setting the module to be a slave----bases 1 through 7. DIP SWITCH--On rear of module for setting baud rate.

Specifications

1--1st wire of twisted pair 2--2nd wire of twisted pair 3--Shield of twisted pair G--Ground connection 1Depends on model-- D4-RS=AC, D4-RSDC=DC

Slaves per channel

7

Module Type

Non--intelligent slave

Installation Requirements

CPU slot in any 4, 6 or 8-slot base

Power Required

110 VAC/220 VAC (D4-RS) 24 VDC (D4-RSDC)

Digital I/O Consumed

None Note: Consumes remote I/O points at a rate equal to the number of I/O points in each base.

Run Output Relay Rating

250 VAC at 1A 30 VDC at 1A

Communication Baud Rates

19.2 kB or 38.4 kB (Switch Selectable)

Communication Cabling

RS-485 twisted pair Belden 9271 or equivalent

Operating Temperature

32 to 140° F (0 to 60_ C)

Storage Temperature

--4 to 158° F (--20 to 70_ C)

Relative Humidity

5 to 95% (non-condensing)

Environmental air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3--304

Page 14

Getting Started

1--9

Assigning the Remote Input and Output Addresses

Remote I/O Address Assignement MasterModule

Main Base with Master

CPU and PS

Slave Module

16

16

16

16

16

I

I

I

O

O

X0-X17 V40400

X20-X37 V40401

These points are automatically assigned to memory by the CPU for the local base.

8

8

8

I

I

O

O

SP00

Remote #1 Input

X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501

8

X60-X67 X70-X77 V40403

Below is the RLL that maps the remote I/O for unit 1 into memory.

1st Remote

Remote I/O points are not assigned automatically. You have to map them into memory with RLL.

Y40-Y47 Y50-Y57 V40502

Next available starting input address is X60. Next available starting output address is Y40. There are 16 inputs and 16 outputs in the remote base.

SP00

Remote #1 Output

LDA O40403 OUT V7404 LD K16 OUT V7405 LDA O40502 OUT V7406 LD K16 OUT V7407

Remote I/O Getting Started

If you’ve used a DL405 CPU and local (or expansion) I/O before, then you probably know that the CPU will automatically assign the input and output addresses. That is, input points are automatically assigned starting at X0, and output points are automatically assigned starting at Y0. In a Remote I/O system, the input and output points in the remote bases are not automatically assigned in this manner. Instead, you have to add some setup logic to your control program that tells the CPU how to assign the addresses to the remote input and output points. Remote I/O In a local/expansion system, inputs are assigned starting at X0 and outputs are assigned starting at Y0. In a Remote I/O system, you can choose this conventional Data Types method, or you can choose to assign the inputs and outputs to other data types. For example, you could assign the remote inputs and outputs as GX (global) data type, or as the C (control relay) data type. This provides flexibility and becomes especially useful if you have already used all of the available X input and Y output addresses in your local and expansion bases. For example, if you had a local/expansion system that used several 32-point input and output modules, you could easily use the entire limit of 320 X input or 320 Y output points (640 total max. I/O points). Now if you added modules in a Remote I/O system, there may not be any additional X input or Y output addresses available for the remote inputs and outputs. (In the vast majority of remote I/O systems, you will be able to use the X input and Y output addresses, but you can see that there may be occasions when you need a different data type for the remote points. Specify Addresses The DL405 CPUs have specific memory locations (called pointers) that tell the CPU how to assign the remote I/O addresses. First, you use the tables (in Appendix B) to with Setup Logic look up the next available starting address for the data type you want to use. Next, you use a combination of LDA, LD, and OUT store this information in the pointers. Consider the following example. Although it hasn’t been discussed yet, we know that V7404 is the pointer for the 1st Remote base belonging to the 1st Remote Master. If your starting address for the I/O points belonging to the 1st Remote are going to be X60, then you would look in Appendix B to find that the starting memory location for X60 is V40403. Then you would use LDA and OUT commands to map the address into that pointer (V7404). Next you would tell the CPU how many input points are in the Remote base. Then, you repeat the steps for the output points. Later in this manual you will be shown all the pointer addresses in a convenient table and we’ll go into greater detail with additional examples.

You Assign the Addresses

Page 15

1--10

Getting Started

Remote I/O Getting Started

How the CPU Updates Remote I/O Points The CPU and remote master work together to update the remote I/O points. Below is an example showing how scanning and updating takes place. Notice that there are two independent scan cycles going on at the same time, but asynchronously. The CPU module is doing its scan which includes looking at the information that the remote master is writing to its internal buffers. During every CPU scan, the CPU examines the internal buffers of the remote master, and updates input and output data from the remote I/O. It is very possible for the CPU to be scanning faster than the remote master can do its scan. It is largely dependent on the size of the application program, the baud rate you have selected for the data transfer between the slaves and master, as well as the number of I/O points being monitored. Therefore, if you have I/O ppoints that must be monitored on every CPU scan, you should place these critical I/O points in the local or expansion bases. The CPU reads the status of any input points associated with remote I/O and stores the status in the input image register.

CPU Scan

Remote Scan Asynchronous to CPU scan

Read Inputs Mapped into memory using your RLL.

The Remote Master obtains the I/O status from the Remote Slaves.

V7404=40000 octal V7405=0008 bcd

Read Inputs from Remote I/O ... GX2 GX1 GX0 ... ON OFF OFF Input Image Register Starting Address

00101100

Service Peripherals, Force I/O CPU Bus Communication Update clock, Special Relays Solve the Application Program GX0

Y1

The status of the input image register is used to solve the application program.

Write Outputs Write Outputs to Remote I/O Diagnostics

Remote Master

Remote Master Buffer

0 0 1 1 0 1 0 0

OFF OFF ON ON OFF ON OFF OFF

GX0 GX1

Remote Slave #1

GX2 GX3 GX4 GX5 GX6 GX7

Input Module

In this example, we have 8 inputs using global GX data types in Slave #1. We have designated 40000 (octal) as the starting address for writing the input data. Output data, if there were output points, is handled in a similar fashion.

NOTE: In some cases it may be helpful to understand the update time required for a Remote I/O system. Appendix C shows example calculations.

Page 16

1--11

Getting Started

3 Easy Steps for Setting Up Remote I/O

Main Base

16 16 16 16

I

I O O 8

8

8 16 16

Empty

Master

8

I

8

I O O

Slave 1

I O O

Slave 2

Step Two: Install the Components

Step Three: Write the Setup Program

Install the bases and insert the master(s) and the remote slaves. Wire all of your I/O to match your information in Step 1. Set the hardware switches so that the CPU can identify the master and slave units. This also will set the baud rate for data transfer and designate how the slave units are numbered, i.e. No. 1, No. 2, and so on. Covered in Chapter 3.

Write the RLL setup program that will tell the CPU which address you want to use for the remote input and output points. Covered in Chapter 4.

T 1 2 3 G

SP00

LDA O40403

Read area for Remote 1 Input

OUT V7404 LD

The next two pages provide a complete overview of the entire process for an example remote I/O system. Of course, to learn all of the details, you should read each chapter carefully.

Total Input Points

Write area for Remote 1 Output

Total Output Points

K16

OUT V7405 LDA O40502 OUT V7406 LD

K16

Remote I/O Getting Started

Figure out how much remote I/O you will need. This will, in turn, tell you how many Step One: Design the System remote masters and remote slaves you will need. In Chapter 2, we will show you how to use worksheets to plan and keep track of your data type assignments. We’ll also show you how to determine the correct addresses for reading and writing remote I/O data.

Page 17

Remote I/O Getting Started

1--12

Getting Started

EXAMPLE: 38.4 kBaud, D4-440

Step 1: Design the Remote I/O System

Main Base with Master

MasterModule

Remote Slave Worksheet

Can go in any slot

CPU and PS

16

1 Remote Base Address_________(Choose 1--7)

16

I

I

X0-X17 V40400

X20-X37 V40401

16

16

I

16

O

O

8

I

8

8

8

I

O

O

X60-X67 X70-X77 V40403

Slave Module

0

08ND3S

X060

8

1

08ND3S

X070

8

Output Address

No.Outputs

2

08TD1

Y040

8

3

08TD1

Y050

8

6 7 X060 Input Bit Start Address:________V-Memory Address:V_______ 40403 16 Total Input Points_____

16

16

16

16

I

I

O

O

X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503

Y040 40502 Output Bit Start Address:________V-Memory Address:V_______ 16 Total Output Points_____

Y100-Y117 V40504

Remote Slave Worksheet

3rd Remote I

No. Inputs

5

2nd Remote

8

Input Address

4

Y40-Y47 Y50-Y57 V40502

Slave Module

OUTPUT

Module Name

X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501

1st Remote

INPUT

Slot Number

2 Remote Base Address_________(Choose 1--7)

OUTPUT

8

8

Slot Number

I

O

O

0

16ND2

X100

16

1

16ND2

X120

16

2 3

X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505

Slave Module

Module Name

INPUT

8

Output Address

No.Outputs

16TD1

Y060

16

16TD1

Y100

16

Input Address

No. Inputs

4

Remote Slave Worksheet

5

3 Remote Base Address_________(Choose 1- 7) Slot Number

6

INPUT

7

OUTPUT

Module Name

Input Address

No. Inputs

Output Address

X100 40404 Input Bit Start Address:________V-Memory Address:V_______

No.Outputs

0

08ND3S

X140

8

1

08ND3S

X150

8

2

08TD1

Y120

8

3

08TD1

Y130

8

32 Total Input Points_____ Y060 40503 Output Bit Start Address:________V-Memory Address:V_______ 32 Total Output Points_____

4 5

Note:

6 7 X140 Input Bit Start Address:________V-Memory Address:V_______ 40406 16 Total Input Points_____ Y120 Output Bit Start Address:________V-Memory Address:V_______ 40505 16 Total Output Points_____

The Remote Slave Worksheet is found in Appendix A.

Page 18

Getting Started

Step 3: Write the Setup Program RLL Program

Table for setting DIP switch Position

1

Master

Always ON

3

4

Always OFF

Always OFF

GTS

Always OFF

Go to remote I/O subroutine

Main Program Body

ON=38.4kB OFF=19.2kB

END SBR

Remote

K1

SP00

2

ON=38.4kB

Always OFF

OFF=19.2kB

K1

Remote I/O Subroutine Note: Write as subroutine only if using D4--440 CPU For D4--430, this must be in main program.

Always OFF SP1

LD K38 There are 56 reserved locations 56 decimal = 38 hex

Master SP1

1=ON 2=ON 3=OFF 4=OFF

From Table Below

LDA O7404

Number of V memory locations in table Where the reserved memory starts

FILL K0

Clear Table

LDA O40403

Starting Address

OUT V7404 LD K16

1st Remote

SP1 1=OFF 2=ON 3=OFF 4=OFF

From Table Below

OUT V7405 LDA O40502

From Table Below

OUT V7406 LD K16

2nd Remote SP1 1=OFF 2=ON 3=OFF 4=OFF

From Table Below

OUT V7410 LD K32

3rd Remote

SP1

1=OFF 2=ON 3=OFF 4=OFF

From Table Below

From Table Below

Second Master Module

K32

From Table Below

Starting Address

Remote #2 Input Starting Address

Remote #2 Output

OUT V7413 LDA O40406

Table of Reserved Memory for Remote I/O Setup First Master Module

OUT V7412 LD

SP1

Remote #1 Output

OUT V7411 LDA O40503

From Table Below

Starting Address

OUT V7407 LDA O40404

From Table Below

Remote #1 Input

OUT V7414 LD

K16

Starting Address

Remote #3 Input

Slave

Input Address

Number of Input Pts

Output Address

Number of Output Pts

Input Address

1

V7404

V7405

V7406

V7407

V7444

V7445

V7446

V7447

2

V7410

V7411

V7412

V7413

V7450

V7451

V7452

V7453

3

V7414

V7415

V7416

V7417

V7454

V7455

V7456

V7457

4

V7420

V7421

V7422

V7423

V7460

V7461

V7462

V7463

5

V7424

V7425

V7426

V7427

V7464

V7465

V7466

V7467

6

V7430

V7431

V7432

V7433

V7470

V7471

V7472

V7473

C670

7

V7434

V7435

V7436

V7437

V7474

V7475

V7476

V7477

SET

Tell CPU that setup is completed

RT

Return to main program.

Number of Output Input Pts Address

Number of Output Pts

= unused memory for this example

SP1

OUT From Table Below V7415 LDA O40505 From Table Below

OUT V7416 LD

From Table Below

K16

Starting Address

Remote #3 Output

OUT V7417

Getting Started

Step 2: Set the Hardware

1--13

Page 19

Designing a Remote I/O System

12

In This Chapter. . . ., Designing Your System, Calculating the Power Budget, What Modules Can Go In the Remote Bases

Page 20

2--2

Designing the System

Designing Your System

Remote I/O Designing the System

Determine I/O Needed and How Many Masters & Slaves

The first step in putting any system together is to at least establish a mental picture of the system components. You may even want to draw a diagram. Below is a drawing of a typical system with: · one master module in the main base. · main base has three input modules and two output modules, each with 16-points. · first remote base has two input and two output modules--each with 8-points. · second remote base has four 16-point modules--two input and two output. · third remote base is identical to the first. MasterModule

CPU and PS

Main Base with Master Can go in any slot

16

16

16

16

16

I

I

I

O

O

X0-X17 V40400

X20-X37 V40401

X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501

1st Remote 8

8

8

8

I

I

O

O

X60-X67 X70-X77 V40403

Y40-Y47 Y50-Y57 V40502

Slave Module

Installation and Safety Guidelines

2nd Remote 16

16

16

16

I

I

O

O

X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503

Slave Module

Y100-Y117 V40504

3rd Remote 8

8

8

8

I

I

O

O

X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505

Slave Module

Better Define Your Idea By Using Worksheets

In Appendix A of this manual you will find a worksheet for planning the design of each of your remote I/O bases. We suggest that you photocopy this sheet and use it to map out the details of your system. Assuming this will be your procedure, this chapter will walk you through the process using the example visualized above. You will need the details from these worksheets when you set the switches on your hardware and you write the configuration code inside your ladder logic program.