The text of a manual · part 3 of 6
DL405 Remote Master/Remote Slave D4-RM, D4-RS, and D4-RSDC, pages 21 to 30
Pages 21 to 30 of 60
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the PLC Direct D4-RM and Koyo D4-RM
Page 21
2--3
Designing the System Filling Out the Remote Slave Worksheet for Slave #1 MasterModule
CPU and PS
The following remote slave worksheet has been filled in to match the first remote I/O base of the example system. Main Base with Master Can go in any slot
Remote Slave Worksheet 16
16
16
16
16
I
I
I
O
O
X0-X17 V40400
X20-X37 V40401
X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501
INPUT
OUTPUT
Slot Number
Module Name
Input Address
No. Inputs
0
08ND3S
X060
8
1
08ND3S
X070
8
Output Address
No. Outputs
8
8
8
8
2
08TD1
Y040
8
I
I
O
O
3
08TD1
Y050
8
X60-X67 X70-X77 V40403
Y40-Y47 Y50-Y57 V40502
Slave Module
4 5 6
2nd Remote
7
16
16
16
16
I
I
O
O
X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503
Slave Module
Y100-Y117 V40504
Remote I/O Designing the System
1st Remote
1 Remote Base Address ___________ (Choose 1--7)
X060 40403 Input Bit Start Address: _______V-Memory Address: V __________ 16 Total Input Points Committed________ Y040 40502 Output Bit Start Address: _______V-Memory Address: V__________ 16 Total Output Points Committed________
3rd Remote 8
8
8
8
I
I
O
O
X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505
X60 - X67
X70 - X77
Y40 - X47
Starting Addresses From Appendix B = V40403 Input
Y50 - Y57
V40502 Output
In this example, the CPU base has 80 points allocated to its input and output modules, which are automatically configured as points X0 thru X57 and Y0 thru Y37. Thus, the starting address for the first remote base inputs can start at X060 (or higher) and the starting address for outputs can be Y040 (or higher). Turning to Appendix B, you look up the V-memory addresses for these points in their respective input and output memory address charts. The far right-hand column of each of these charts shows the “bit start” address. For example, for the bit start address for input X060 you look for 060 on the far left-hand portion of the chart. There you find the cross-referenced register address: 40403. On the output chart, you find cross-reference Y040 with 40502. These numbers are filled in at the bottom of the worksheet. They will be used later in your ladder logic. Now let’s do the same thing for your second remote I/O base.
Installation and Safety Guidelines
Slave Module
Page 22
2--4
Designing the System The following remote slave worksheet has been filled in to match the second remote I/O base of the example system.
Filling Out the Remote Slave Worksheet for Slave #2 MasterModule
Remote I/O Designing the System
CPU and PS
Main Base with Master Remote Slave Worksheet
Can go in any slot
16
16
16
16
16
I
I
I
O
O
X0-X17 V40400
X20-X37 V40401
X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501
1st Remote 8
I
8
I
X60-X67 X70-X77 V40403
8
O
8
O
Y40-Y47 Y50-Y57 V40502
Slave Module
2 Remote Base Address ___________ (Choose 1--7) INPUT
OUTPUT
Slot Number
Module Name
Input Address
No. Inputs
0
16ND2
X100
16
1
16ND2
X120
16
2
16TD1
Y60
16
3
16TD1
Y100
16
Output Address
No. Outputs
4 5 6 7
2nd Remote 16
16
16
16
I
I
O
O
X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503
Slave Module
Y100-Y117 V40504
X100 40404 Input Bit Start Address: _______V-Memory Address: V __________ 32 Total Input Points Committed________ Y60 40503 Output Bit Start Address: _______V-Memory Address: V__________ 32 Total Output Points Committed________
3rd Remote 8
I
8
I
8
O
8
O
Installation and Safety Guidelines
X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505
Slave Module
X100 - X117 X120 - X137
Starting Addresses From Appendix B = V40404 Input
Y60 - Y77
Y100 - Y117
V40503 Output
Remote Slave #1 has points X060 to X077 allocated to its inputs and points Y040 to Y057 allocated to its outputs. This means the starting address for the second remote base inputs is X100 (or higher) and the starting address for outputs is Y060 (or higher). Turning to Appendix B, you look up the V-memory addresses for these points in their respective input and output memory address charts, you find the starting address for the inputs to be V40404. On the output chart, you find cross-reference 060 with V40502. These numbers are filled in at the bottom of the worksheet. Now let’s do the same thing for third remote I/O base.
Page 23
2--5
Designing the System
Filling Out the The following remote slave worksheet has been filled in to match the third remote I/O base of the example system. Remote Slave Worksheet for Slave #3 Main Base with Master MasterModule
CPU and PS
Remote Slave Worksheet
Can go in any slot
16
16
16
16
16
I
I
I
O
O
X0-X17 V40400
X20-X37 V40401
X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501
8
I
8
8
8
I
O
O
X60-X67 X70-X77 V40403
Y40-Y47 Y50-Y57 V40502
Slave Module
INPUT
OUTPUT
Slot Number
Module Name
Input Address
No. Inputs
0
08ND3S
X140
8
1
08ND3S
X150
8
2 3
Output Address
No. Outputs
08TD1
Y120
8
08TD1
Y130
8
4 5 6 7
2nd Remote 16
16
16
16
I
I
O
O
X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503
Slave Module
Y100-Y117 V40504
X140 40406 Input Bit Start Address: _______V-Memory Address: V __________
Remote I/O Designing the System
1st Remote
3 Remote Base Address ___________ (Choose 1--7)
16 Total Input Points Committed________ Y120 40505 Output Bit Start Address: _______V-Memory Address: V__________ 16 Total Output Points Committed________
3rd Remote 8
I
8
8
8
I
O
O
X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505 X140 - X147 X150 - X157 Y120 - Y127 Y130 - Y137
Starting Addresses From Appendix B = V40406 Input
V40505 Output
Remote Slave #2 has points X100 to X137 allocated to its inputs and points Y100 to Y117 allocated to its outputs. This means the starting address for the third base inputs is X140 (or higher) and the starting address for outputs is Y120 (or higher). Turning to Appendix B, you look up the V-memory addresses for these points in their respective input and output memory address charts, you find the starting address for the inputs to be V40406. On the output chart, you find cross-reference 120 with V40505. These numbers are filled in at the bottom of the worksheet.
Installation and Safety Guidelines
Slave Module
Page 24
2--6
Designing the System
Calculating the Power Budget
Installation and Safety Guidelines
Remote I/O Designing the System
Managing your Power Resource
When determining the types and quantity of I/O modules you will be using in the DL405 system, it is important to remember there is a limited amount of power available from the power supply to the system. We have provided a chart to help you easily see the amount of power you will have with your CPU, Expansion Unit or Remote Slave selection. At the end of this section you will also find an example of power budgeting and a worksheet showing sample calculations. If the I/O you chose exceeds the maximum power available from the power supply you can resolve the problem by adding another base--either remote or expansion. WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.
CPU Power Specifications
The following chart shows the amount of current supplied by the the DL405 CPU, Expansion unit or Remote Slave unit. Use this to calculate the power budget for your system. The Auxiliary 24V Power Source mentioned in the table can be used to power field devices or DL405 modules that require an external 24VDC. (Check the terminal strip wiring diagrams shown in Chapter 3 for the location of these terminals.)
CPUs
5V Current Supplied in mA.
Auxiliary 24V Power Source Current Supplied in mA.
Remote and Expansion Units
5V Current Supplied in mA.
Auxiliary 24V Power Source Current Supplied in mA.
D4--430
3700
400
D4--EX
4000
400
D4--440
3700
400
D4--EXDC
4000
None
D4--440DC--1
3700
None
D4--RS
3700
400
D4--440DC--2
3700
None
D4--RSDC
3700
None
Module Power Requirements
The chart on the next page shows the amount of maximum current required for each of the DL405 modules. Use this information to calculate the power budget for your system. If an external 24VDC power source is required, you can use the built-in 24VDC auxiliary supply from the CPU or the Remote Slave as long as the power budget is not exceeded. NOTE: Not all of the modules shown in the following table can be used in a Remote base. Check page 2--9 for module placement restrictions.
Page 25
Designing the System
Device
5V Current Required in mA.
External 24V Current Required in mA.
I/O Bases
Device
2--7
5V Current Required in mA.
External 24V Current Required in mA.
Analog Modules 80
None
D4--04AD
200
200
D4--04BNX
80
None
F4--04ADS
270
120
D4--06B
80
None
F4--08AD
75
90
D4--06BNX
80
None
D4--02DA
250
300
D4--08B
80
None
F4--04DA
120
180
D4--08BNX
80
None
F4--08THM--N
75
40
DC Input Modules
Remote I/O
D4--08ND3S
100
None
D4--RM
300
None
D4--16ND2
150
None
D4--SM
300
None
D4--16ND2F
150
None
D4--SS--88
None
100 (250 with HPP)
D4--32ND3--1
150
None
D4--SS--106
None
100 (250 with HPP)
D4--32ND3--2
150
None
D4--SS--16T
None
100 (250 with HPP)
D4--64ND2
300 (max)
None
D4--SS--16N
None
100 (250 with HPP)
F4--SDS
110
None
AC Input Modules D4--08NA
100
None
Communications and Networking
D4--16NA
150
None
D4--DCM
500
None
F4--MAS--MB
235
None
AC/DC Input Modules D4--16NE3
150
None
F4--SLV--MB
235
None
F4--08NE3S
90
None
F4--SLV--MBR
350
None
F4--SLV--TW
250
None
DC Output Modules 150
35
F4--SDN
235
None
D4--16TD1
200
125
FA--UNICON
None
65
D4--16TD2
400
None
CoProcessorsä
D4--32TD1
250
140
F4--CP128
305
None
D4--32TD1--1
250
140 (15V)
F4--CP512
235
None
D4--32TD2
350
120 / (4A max including loads)
F4--CP128--T
350
None
D4--64TD1
800 (max)
None
F4--CP128--R
350
None
AC Output Modules
Specialty Modules
D4--08TA
250
None
D4--INT
100
None
D4--16TA
450
None
D4--HSC
300
None
F4--16PID
160
None
F4--08MPI
225
170
D4--16SIM
150
None
F4--4LTC
160
None
320
None
150
None
Relay Output Modules D4--08TR
550
None
F4--08TRS--1
575
None
Programming F4--08TRS--2
575
None
D4--HPP Operator Interface
D4--16TR
1000
None
DV--1000
Installation and Safety Guidelines
D4--08TD1
Remote I/O Designing the System
D4--04B
Page 26
2--8
Designing the System
Power Budget Calculation Example
The following example shows how to calculate the power budget for the first slave unit of a remote I/O system. Slave #
Module Type
5 VDC (mA)
Auxiliary Power Source 24 VDC Output (mA)
1
Remote I/O Designing the System
Remote Slave D4--RS Used
3700
400
Slot 0
D4--08ND3S
100
0
Slot 1
D4--08ND3S
100
0
Slot 2
D4--08TD1
150
0
Slot 3
D4--08TD1
150
0
80
0
580
0
Slot 4 Slot 5 Slot 6 Slot 7 Other Base D4--08B Maximum power required
Installation and Safety Guidelines
Remaining Power Available
3700--580 =3120
400 -- 0
= 400
1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the CPU/Remote Slave, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by either the CPU, Expansion Unit, and Remote Slave since they do differ. Devices which fall into the “Other” category are devices such as the Base and the Handheld programmer which also have power requirements but do not directly plug into the base. 2. Add the current columns starting with Slot 0 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “CPU/Expansion Unit/Remote Slave Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “CPU/Expansion Unit/Remote Slave Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to used this configuration and you will need to restructure your I/O configuration.
Page 27
Designing the System
2--9
Which Modules Can Go In the Remote Bases The most commonly used I/O modules for the DL405 system (AC, DC, AC/DC, Relay and Analog) can be used in the remote I/O bases. The table below lists by category those modules that can be used in the remote I/O base. Module/Unit
Remote Base No
Expansion Units
No
DC Input Modules
Yes
AC Input Modules
Yes
AC/DC Input Modules
Yes
DC Output Modules
Yes
AC Output Modules
Yes
Relay Output Modules
Yes
Analog Modules
Yes
Remote I/O Remote Master Remote Slave Unit
Remote I/O Designing the System
CPUs
No CPU Slot Only
Slice Master
No
Communications and Networking Modules
No
CoProcessor Modules
No
Specialty Modules No
High Speed Counter
No
PID
No
I/O Simulator
Yes
Filler
Yes
NOTE: The User Manual for Analog I/O Modules discusses scan times for updating analog I/O data for modules that have been installed in local or expansion bases. Please be aware that the scan times for updating are different for remote I/O modules installed in remote bases. The CPU scan is asynchronous with the remote scan by the master module. Thus, an analog input module installed in a remote base, for example, may not have its data updated by the CPU “once every scan per channel” as stated in the user manual. The CPU scan may, in fact, cycle several times while the remote scan is taking place. You should take this into account in applications where the timing is critical.
Installation and Safety Guidelines
Interrupt
Page 28
Installation & Field Wiring Guidelines In This Chapter. . . ., Introduction, Setting the Front Rotary Switch, Setting the Rear DIP Switches, Inserting the Module in the Base, Connecting the Wiring
13
Page 29
3--2
Installation and Wiring
Getting Started
Introduction NOTE: It is advised that you read the previous chapter on “Defining Your I/O System ” before you install your remote master and slave units. The decision making process explained in that chapter will help you understand the rotary switches and dip switches covered in this chapter. It will also help you with writing your ladder logic in the next chapter. 4 Easy Steps:
There are four easy steps to install either a D4-RM, D4-RS or D4-RSDC module: Step1 -Set the address on the front rotary switch (i.e. 1 through 7). Step2 -Set the function code and baud rate on the rear DIP switch. Step3 -With no power applied, insert the module into the base. Step 1 With no power applied, connect the wiring.
Remote I/O Installation/Wiring
The text that follows will cover each of these steps in detail.
Page 30
Installation and Wiring
3--3
Step One: Setting the Front Rotary Switch Both the remote master and slave have a small rotary switch on the front of their enclosure. It has the label, “UNIT ADRS” beside it. To access it you must remove the protective cover. This switch is easily rotated using a flathead screwdriver.
REMOTE I/O MASTER PWR RUN PAR DIAG I/O LINK MSTR D4- RM
D4--RS 110/220VAC REMOTE I/O PWR
I/O
RUN
PAR
DIAG
LINK
UNIT ADRS
Rotary Switch
UNIT ADRS
T 1 T
3
1
G
2 3
30VDC 1A CLASS2
G D4--RM
Align the arrow on the switch to 0 if you plan to use the module as a master (D4--RM only). Set it to any number 1--7 if you plan for it to be a slave (D4-RS, or D4-RSDC). Two slaves cannot have the same number if they are linked to the same master. Always use consecutive numbers for slaves, starting with Address 1-- --don’t skip numbers.
Remote I/O Installation/Wiring
2