The text of a manual · part 3 of 6

DL405 Remote Master/Remote Slave D4-RM, D4-RS, and D4-RSDC, pages 21 to 30

Pages 21 to 30 of 60

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the PLC Direct D4-RM and Koyo D4-RM

Page 21

2--3

Designing the System Filling Out the Remote Slave Worksheet for Slave #1 MasterModule

CPU and PS

The following remote slave worksheet has been filled in to match the first remote I/O base of the example system. Main Base with Master Can go in any slot

Remote Slave Worksheet 16

16

16

16

16

I

I

I

O

O

X0-X17 V40400

X20-X37 V40401

X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501

INPUT

OUTPUT

Slot Number

Module Name

Input Address

No. Inputs

0

08ND3S

X060

8

1

08ND3S

X070

8

Output Address

No. Outputs

8

8

8

8

2

08TD1

Y040

8

I

I

O

O

3

08TD1

Y050

8

X60-X67 X70-X77 V40403

Y40-Y47 Y50-Y57 V40502

Slave Module

4 5 6

2nd Remote

7

16

16

16

16

I

I

O

O

X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503

Slave Module

Y100-Y117 V40504

Remote I/O Designing the System

1st Remote

1 Remote Base Address ___________ (Choose 1--7)

X060 40403 Input Bit Start Address: _______V-Memory Address: V __________ 16 Total Input Points Committed________ Y040 40502 Output Bit Start Address: _______V-Memory Address: V__________ 16 Total Output Points Committed________

3rd Remote 8

8

8

8

I

I

O

O

X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505

X60 - X67

X70 - X77

Y40 - X47

Starting Addresses From Appendix B = V40403 Input

Y50 - Y57

V40502 Output

In this example, the CPU base has 80 points allocated to its input and output modules, which are automatically configured as points X0 thru X57 and Y0 thru Y37. Thus, the starting address for the first remote base inputs can start at X060 (or higher) and the starting address for outputs can be Y040 (or higher). Turning to Appendix B, you look up the V-memory addresses for these points in their respective input and output memory address charts. The far right-hand column of each of these charts shows the “bit start” address. For example, for the bit start address for input X060 you look for 060 on the far left-hand portion of the chart. There you find the cross-referenced register address: 40403. On the output chart, you find cross-reference Y040 with 40502. These numbers are filled in at the bottom of the worksheet. They will be used later in your ladder logic. Now let’s do the same thing for your second remote I/O base.

Installation and Safety Guidelines

Slave Module

Page 22

2--4

Designing the System The following remote slave worksheet has been filled in to match the second remote I/O base of the example system.

Filling Out the Remote Slave Worksheet for Slave #2 MasterModule

Remote I/O Designing the System

CPU and PS

Main Base with Master Remote Slave Worksheet

Can go in any slot

16

16

16

16

16

I

I

I

O

O

X0-X17 V40400

X20-X37 V40401

X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501

1st Remote 8

I

8

I

X60-X67 X70-X77 V40403

8

O

8

O

Y40-Y47 Y50-Y57 V40502

Slave Module

2 Remote Base Address ___________ (Choose 1--7) INPUT

OUTPUT

Slot Number

Module Name

Input Address

No. Inputs

0

16ND2

X100

16

1

16ND2

X120

16

2

16TD1

Y60

16

3

16TD1

Y100

16

Output Address

No. Outputs

4 5 6 7

2nd Remote 16

16

16

16

I

I

O

O

X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503

Slave Module

Y100-Y117 V40504

X100 40404 Input Bit Start Address: _______V-Memory Address: V __________ 32 Total Input Points Committed________ Y60 40503 Output Bit Start Address: _______V-Memory Address: V__________ 32 Total Output Points Committed________

3rd Remote 8

I

8

I

8

O

8

O

Installation and Safety Guidelines

X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505

Slave Module

X100 - X117 X120 - X137

Starting Addresses From Appendix B = V40404 Input

Y60 - Y77

Y100 - Y117

V40503 Output

Remote Slave #1 has points X060 to X077 allocated to its inputs and points Y040 to Y057 allocated to its outputs. This means the starting address for the second remote base inputs is X100 (or higher) and the starting address for outputs is Y060 (or higher). Turning to Appendix B, you look up the V-memory addresses for these points in their respective input and output memory address charts, you find the starting address for the inputs to be V40404. On the output chart, you find cross-reference 060 with V40502. These numbers are filled in at the bottom of the worksheet. Now let’s do the same thing for third remote I/O base.

Page 23

2--5

Designing the System

Filling Out the The following remote slave worksheet has been filled in to match the third remote I/O base of the example system. Remote Slave Worksheet for Slave #3 Main Base with Master MasterModule

CPU and PS

Remote Slave Worksheet

Can go in any slot

16

16

16

16

16

I

I

I

O

O

X0-X17 V40400

X20-X37 V40401

X40-X57 Y0-Y17 Y20-Y37 V40402 V40500 V40501

8

I

8

8

8

I

O

O

X60-X67 X70-X77 V40403

Y40-Y47 Y50-Y57 V40502

Slave Module

INPUT

OUTPUT

Slot Number

Module Name

Input Address

No. Inputs

0

08ND3S

X140

8

1

08ND3S

X150

8

2 3

Output Address

No. Outputs

08TD1

Y120

8

08TD1

Y130

8

4 5 6 7

2nd Remote 16

16

16

16

I

I

O

O

X100-X117 X120-X137 Y60-Y77 V40404 V40405 V40503

Slave Module

Y100-Y117 V40504

X140 40406 Input Bit Start Address: _______V-Memory Address: V __________

Remote I/O Designing the System

1st Remote

3 Remote Base Address ___________ (Choose 1--7)

16 Total Input Points Committed________ Y120 40505 Output Bit Start Address: _______V-Memory Address: V__________ 16 Total Output Points Committed________

3rd Remote 8

I

8

8

8

I

O

O

X140-X147 X150-X157 Y120-Y127 Y130-Y137 V40406 V40505 X140 - X147 X150 - X157 Y120 - Y127 Y130 - Y137

Starting Addresses From Appendix B = V40406 Input

V40505 Output

Remote Slave #2 has points X100 to X137 allocated to its inputs and points Y100 to Y117 allocated to its outputs. This means the starting address for the third base inputs is X140 (or higher) and the starting address for outputs is Y120 (or higher). Turning to Appendix B, you look up the V-memory addresses for these points in their respective input and output memory address charts, you find the starting address for the inputs to be V40406. On the output chart, you find cross-reference 120 with V40505. These numbers are filled in at the bottom of the worksheet.

Installation and Safety Guidelines

Slave Module

Page 24

2--6

Designing the System

Calculating the Power Budget

Installation and Safety Guidelines

Remote I/O Designing the System

Managing your Power Resource

When determining the types and quantity of I/O modules you will be using in the DL405 system, it is important to remember there is a limited amount of power available from the power supply to the system. We have provided a chart to help you easily see the amount of power you will have with your CPU, Expansion Unit or Remote Slave selection. At the end of this section you will also find an example of power budgeting and a worksheet showing sample calculations. If the I/O you chose exceeds the maximum power available from the power supply you can resolve the problem by adding another base--either remote or expansion. WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.

CPU Power Specifications

The following chart shows the amount of current supplied by the the DL405 CPU, Expansion unit or Remote Slave unit. Use this to calculate the power budget for your system. The Auxiliary 24V Power Source mentioned in the table can be used to power field devices or DL405 modules that require an external 24VDC. (Check the terminal strip wiring diagrams shown in Chapter 3 for the location of these terminals.)

CPUs

5V Current Supplied in mA.

Auxiliary 24V Power Source Current Supplied in mA.

Remote and Expansion Units

5V Current Supplied in mA.

Auxiliary 24V Power Source Current Supplied in mA.

D4--430

3700

400

D4--EX

4000

400

D4--440

3700

400

D4--EXDC

4000

None

D4--440DC--1

3700

None

D4--RS

3700

400

D4--440DC--2

3700

None

D4--RSDC

3700

None

Module Power Requirements

The chart on the next page shows the amount of maximum current required for each of the DL405 modules. Use this information to calculate the power budget for your system. If an external 24VDC power source is required, you can use the built-in 24VDC auxiliary supply from the CPU or the Remote Slave as long as the power budget is not exceeded. NOTE: Not all of the modules shown in the following table can be used in a Remote base. Check page 2--9 for module placement restrictions.

Page 25

Designing the System

Device

5V Current Required in mA.

External 24V Current Required in mA.

I/O Bases

Device

2--7

5V Current Required in mA.

External 24V Current Required in mA.

Analog Modules 80

None

D4--04AD

200

200

D4--04BNX

80

None

F4--04ADS

270

120

D4--06B

80

None

F4--08AD

75

90

D4--06BNX

80

None

D4--02DA

250

300

D4--08B

80

None

F4--04DA

120

180

D4--08BNX

80

None

F4--08THM--N

75

40

DC Input Modules

Remote I/O

D4--08ND3S

100

None

D4--RM

300

None

D4--16ND2

150

None

D4--SM

300

None

D4--16ND2F

150

None

D4--SS--88

None

100 (250 with HPP)

D4--32ND3--1

150

None

D4--SS--106

None

100 (250 with HPP)

D4--32ND3--2

150

None

D4--SS--16T

None

100 (250 with HPP)

D4--64ND2

300 (max)

None

D4--SS--16N

None

100 (250 with HPP)

F4--SDS

110

None

AC Input Modules D4--08NA

100

None

Communications and Networking

D4--16NA

150

None

D4--DCM

500

None

F4--MAS--MB

235

None

AC/DC Input Modules D4--16NE3

150

None

F4--SLV--MB

235

None

F4--08NE3S

90

None

F4--SLV--MBR

350

None

F4--SLV--TW

250

None

DC Output Modules 150

35

F4--SDN

235

None

D4--16TD1

200

125

FA--UNICON

None

65

D4--16TD2

400

None

CoProcessorsä

D4--32TD1

250

140

F4--CP128

305

None

D4--32TD1--1

250

140 (15V)

F4--CP512

235

None

D4--32TD2

350

120 / (4A max including loads)

F4--CP128--T

350

None

D4--64TD1

800 (max)

None

F4--CP128--R

350

None

AC Output Modules

Specialty Modules

D4--08TA

250

None

D4--INT

100

None

D4--16TA

450

None

D4--HSC

300

None

F4--16PID

160

None

F4--08MPI

225

170

D4--16SIM

150

None

F4--4LTC

160

None

320

None

150

None

Relay Output Modules D4--08TR

550

None

F4--08TRS--1

575

None

Programming F4--08TRS--2

575

None

D4--HPP Operator Interface

D4--16TR

1000

None

DV--1000

Installation and Safety Guidelines

D4--08TD1

Remote I/O Designing the System

D4--04B

Page 26

2--8

Designing the System

Power Budget Calculation Example

The following example shows how to calculate the power budget for the first slave unit of a remote I/O system. Slave #

Module Type

5 VDC (mA)

Auxiliary Power Source 24 VDC Output (mA)

1

Remote I/O Designing the System

Remote Slave D4--RS Used

3700

400

Slot 0

D4--08ND3S

100

0

Slot 1

D4--08ND3S

100

0

Slot 2

D4--08TD1

150

0

Slot 3

D4--08TD1

150

0

80

0

580

0

Slot 4 Slot 5 Slot 6 Slot 7 Other Base D4--08B Maximum power required

Installation and Safety Guidelines

Remaining Power Available

3700--580 =3120

400 -- 0

= 400

1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the CPU/Remote Slave, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by either the CPU, Expansion Unit, and Remote Slave since they do differ. Devices which fall into the “Other” category are devices such as the Base and the Handheld programmer which also have power requirements but do not directly plug into the base. 2. Add the current columns starting with Slot 0 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “CPU/Expansion Unit/Remote Slave Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “CPU/Expansion Unit/Remote Slave Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to used this configuration and you will need to restructure your I/O configuration.

Page 27

Designing the System

2--9

Which Modules Can Go In the Remote Bases The most commonly used I/O modules for the DL405 system (AC, DC, AC/DC, Relay and Analog) can be used in the remote I/O bases. The table below lists by category those modules that can be used in the remote I/O base. Module/Unit

Remote Base No

Expansion Units

No

DC Input Modules

Yes

AC Input Modules

Yes

AC/DC Input Modules

Yes

DC Output Modules

Yes

AC Output Modules

Yes

Relay Output Modules

Yes

Analog Modules

Yes

Remote I/O Remote Master Remote Slave Unit

Remote I/O Designing the System

CPUs

No CPU Slot Only

Slice Master

No

Communications and Networking Modules

No

CoProcessor Modules

No

Specialty Modules No

High Speed Counter

No

PID

No

I/O Simulator

Yes

Filler

Yes

NOTE: The User Manual for Analog I/O Modules discusses scan times for updating analog I/O data for modules that have been installed in local or expansion bases. Please be aware that the scan times for updating are different for remote I/O modules installed in remote bases. The CPU scan is asynchronous with the remote scan by the master module. Thus, an analog input module installed in a remote base, for example, may not have its data updated by the CPU “once every scan per channel” as stated in the user manual. The CPU scan may, in fact, cycle several times while the remote scan is taking place. You should take this into account in applications where the timing is critical.

Installation and Safety Guidelines

Interrupt

Page 28

Installation & Field Wiring Guidelines In This Chapter. . . ., Introduction, Setting the Front Rotary Switch, Setting the Rear DIP Switches, Inserting the Module in the Base, Connecting the Wiring

13

Page 29

3--2

Installation and Wiring

Getting Started

Introduction NOTE: It is advised that you read the previous chapter on “Defining Your I/O System ” before you install your remote master and slave units. The decision making process explained in that chapter will help you understand the rotary switches and dip switches covered in this chapter. It will also help you with writing your ladder logic in the next chapter. 4 Easy Steps:

There are four easy steps to install either a D4-RM, D4-RS or D4-RSDC module: Step1 -Set the address on the front rotary switch (i.e. 1 through 7). Step2 -Set the function code and baud rate on the rear DIP switch. Step3 -With no power applied, insert the module into the base. Step 1 With no power applied, connect the wiring.

Remote I/O Installation/Wiring

The text that follows will cover each of these steps in detail.

Page 30

Installation and Wiring

3--3

Step One: Setting the Front Rotary Switch Both the remote master and slave have a small rotary switch on the front of their enclosure. It has the label, “UNIT ADRS” beside it. To access it you must remove the protective cover. This switch is easily rotated using a flathead screwdriver.

REMOTE I/O MASTER PWR RUN PAR DIAG I/O LINK MSTR D4- RM

D4--RS 110/220VAC REMOTE I/O PWR

I/O

RUN

PAR

DIAG

LINK

UNIT ADRS

Rotary Switch

UNIT ADRS

T 1 T

3

1

G

2 3

30VDC 1A CLASS2

G D4--RM

Align the arrow on the switch to 0 if you plan to use the module as a master (D4--RM only). Set it to any number 1--7 if you plan for it to be a slave (D4-RS, or D4-RSDC). Two slaves cannot have the same number if they are linked to the same master. Always use consecutive numbers for slaves, starting with Address 1-- --don’t skip numbers.

Remote I/O Installation/Wiring

2