Page 31
3--4
Installation and Wiring
On the rear of each module is an opening with a 4--position DIP switch. These switches must be set to indicate whether the module is a slave or a master and to specify the proper baud rate (either 38.4 kBaud or 19.2 kBaud).
Remote I/O Installation/Wiring
Getting Started
Step Two: Setting the Rear DIP Switches
DIP Switches
Chart for DIP Switch Settings Position
1
2
3
4
Master
Always ON
ON=38.4 kBaud Always OFF OFF=19.2 kBaud
Always OFF
Remote
Always OFF
ON=38.4 kBaud Always OFF OFF=19.2 kBaud
Always OFF
An arrow showing the ON position is visible on the switch beside Position 1. Position 1 is in the ON position for the DM4-RM. Postion 1 of the DIP switch for the D4-RS and D4-RSDC is always set to the OFF position. Remember, only the D4-RM can be used as a master. Position 2 is ON if you want the faster baud rate, 38.4 kBaud. It is OFF if you want the slower 19.2 kBaud. Of course, Position 2 of the master and slaves have to be set to the same setting in order to communicate. Positions 3 and 4 are not used and are always set in the OFF position.
Page 32
Installation and Wiring Example Showing Proper Setting of Switches MasterModule
3--5
Here’s the way Steps 1 and 2 would be carried out for the example system we established in Chapter 2 if we decided to operate at 38.4 kBaud:
Rotary Switch
Main Base with Master
Dip Switch
Can go in any slot
CPU and PS
16
16
16
16
16
I
I
I
O
O
ON=Master ON =38.4 kBaud OFF=Not Used OFF=Not Used
1st Remote 8
I
8
I
8
O
OFF=Remote ON =38.4 kBaud OFF=Not Used OFF=Not Used
8
O
Slave Module
2nd Remote 16
16
16
I
I
O
O
OFF=Remote ON =38.4 kBaud OFF=Not Used OFF=Not Used
Slave Module
3rd Remote 8
I
8
I
8
O
OFF=Remote ON =38.4 kBaud OFF=Not Used OFF=Not Used
8
O
Slave Module
Chart for DIP Switch Settings Position
1
2
3
4
Master
Always ON
ON=38.4 kBaud Always OFF OFF=19.2 kBaud
Always OFF
Remote
Always OFF
ON=38.4 kBaud Always OFF OFF=19.2 kBaud
Always OFF
Remote I/O Installation/Wiring
16
Page 33
3--6
Installation and Wiring
Getting Started
Step Three: Inserting the Module in the Base The D4-RM can go into any slot in the CPU base. The D4-RS or D4-RSDC must be inserted in the CPU slot of the remote base(s). NOTE: Don’t forget to check your total “power budget” and make sure your total current drawn by the remote modules and other I/O modules do not exceed the total amount allowable for the CPU you are using. See Chapter 2 of this manual or your DL405 User Manual for instructions on how to compute your power budget.
Remote I/O Installation/Wiring
WARNING: To minimize the risk of electrical shock, personal injury, or equipment damage, always disconnect the system power before installing or removing any system component.
D4-RS or D4-RSDC must be inserted in the CPU slot of the remote base.
D4-RM can go into any slot in the local base except the CPU slot.
Notice the modules have plastic tabs at the bottom and a screw at the top. With the module tilted slightly forward, hook the plastic tab on the module into the notch on the base. Next, gently push the top of the module back toward the base until it is firmly seated into the base. Now tighten the screw at the top of the module to secure the module to the base.
Page 34
3--7
Installation and Wiring
Step Four: Connecting the Wiring General Wiring Guidelines
You should consider the following wiring guidelines when wiring your system.
Power Connections for the D4-RS or D4-RSDC
To access the power terminals of the D4-RS or D-RSDC modules, you must first remove the large protective cover from the front of the enclosure. Without power being applied, connect the line voltage or DC power supply wires to the appropriate terminals. Also connect the safety earth ground.
D4-RS
D4-RSDC
D4- RS 110/220VAC REMOTE I/O
(Earth Ground) (Line Voltage) (Line Neutral)
D4- RS 110/220VAC REMOTE I/O
T 1 2
(Earth Ground) 20--28VDC (+) 3A (--)
T 1 2
3
3
G
G
Remote I/O Installation/Wiring
Step1 -There is a limit to the size of wire the modules can accept. 16 AWG to 24 AWG is recommended. Smaller AWG is acceptable. Step2 -Always use a continuous length of wire, do not combine wires to attain a needed length. Step3 -Use the shortest possible cable length. Step4 -Where possible, use wire trays for routing. Step5 -Avoid running wires near high energy wiring. Step6 -Avoid running input wiring in close proximity to output wiring where possible. Step7 -To minimize voltage drops when wires must run a long distance, consider using multiple wires for the return line. Step8 -Where possible, avoid running DC wiring or communication cabling in close proximity to AC wiring. Step9 -Avoid creating sharp bends in the wires. Step 1 Label all wires.
Page 35
Installation and Wiring The diagram shown below depicts the cabling between the master and its slaves. This is twisted pair cable. The two inner wires are connected to terminals 1 and 2 of each module. The shield wire is connected to terminal 3. Do not connect the shield wire to the Ground terminal. Make sure the the connections between master and all slaves are always 1 to 1, 2 to 2 and 3 to 3. Master
Termination Resistors
Slave 1
Slave 2
Slave 3
1
1
1
1
2
2
2
2
3
3
3
3
At each end of a master/slave system, it is necessary to have a “termination resistor” to prevent signal reflections from interferring with the communications. Although the modules have a 330 ohm resistor built in for this purpose, there are three options to be considered:
Remote I/O Installation/Wiring
Option 1: Use Internal Resistor Only With this configuration, you use the internal resistor of the module to provide all the terminating resistance necessary. A jumper wire is placed between the terminating terminal and terminal 1.
Option 2: Use Internal Resistor and Balance Resistor To better match the impedance of the cabling, you can elect not use the internal resistor; and instead, use a resistor of your choice externally. This is connected between terminals 1 and 2. You do not use the jumper wire in this case.
Internal Wiring
Cabling Between the Master and Slaves
T Internal 330 ohm resistor
1 2
Jumper Wire
3
Internal Wiring
Getting Started
3--8
T Internal 330 ohm resistor
1 2 3
You add your own resistor, using a resistor between 100 and 500 ohms.
Page 36
Option 3: External Resistor in Series With this option, you use an external resisor in series with the internal resistor. The sum resistance should match the cabling impedance.
Internal Wiring
Installation and Wiring
3--9
T Internal 330 ohm resistor
1 2 3
You use an external resistor in series with the internal resistor.
Connecting the Run Output Circuit
3 G Internal relay RUN OUTPUT
The Run Output relay can be wired to a 24 VDC sinking input module so that ladder logic can be written to monitor the communications link. The bottom two terminals for the terminal block are where the wires are connected from the input module.
RUN COMMON
If the RUN relay in the master goes OFF, then the RUN relay in all of the slaves will be taken off-line also. If you choose to wire an input (say, X10) from the Run Output, it is very easy to include a rung of logic to sound an alarm or to stop a process when communication problem occurs: X10
Y23 OUT Alarm Output
Remote I/O Installation/Wiring
D4-RM, D4-RS, and D4-RSDC modules have a normally open relay that closes when communication is successfully made between the master and its slaves. Each module has its own LED indicator that glows when successful communication has been accomplished.
Page 37
Writing the Setup Program In This Chapter. . . ., Getting Started with Your Programming, Writing Your Remote I/O Setup, Special Relays used for Remote I/O, How to Use the Special Relays
14
Page 38
4--2
Setup Programming
Getting Started with Your Programming
Remote I/O Setup Programming
You can write your program using either a handheld programmer or PC loaded software such as DirectSOFT. The examples that follow will show you how this is done using DirectSOFT. To get started, enter DirectSOFT and carry out the normal DirectSOFT setup procedures for communicating with your DL405 CPU. If you do not know how to do this, refer to your DirectSOFT Manual. Chapter 11 of your DL405 User Manual also has a very good coverage of the basic commands available and examples of how the commands are used for writing general ladder logic. We will be showing you in this chapter only those commands that pertain to setting up your remote I/O initialization and its successful utilization. First open DirectSOFT from Windows and establish a link with your CPU. Then enter the Edit Mode for programming. You should now be looking at a screen similar to the one shown below:
The DirectSOFT window shown above depicts a program that has already been written. Your window, of course, will be empty when you first enter it. The pages that follow will show you how to write each part of your initilization program.
Page 39
Setup Programming
4--3
Writing Your Remote I/O Setup Step 1: Decide How You Are Going to Call Your Program
Is your setup logic going to be in the main program body or is it going to be in a subroutine? If you have a DL430, the decision is made for you. The DL430 cannot handle the GTS command for calling a subroutine; and so, you have to write the code in the main body. The DL440, on the other hand, does include the GTS command. A subroutine for your remote I/O setup has an advantage over writing the code into the program’s main body. Some remote I/O setup logic becomes quite lengthy. By putting the setup in a subroutine, you don’t have to scroll through extra logic during routine troubleshooting procedures. If you are using the DL440, we advise you to use a subroutine for your remote I/O initialization. Here’s how: Using the GTS Command for the DL440 SP00
K1 GTS
DirectSOFT Display
Main Program Body Goes Here
END SBR
K1
Subroutine Will Go Down Here
Remote I/O Setup Programming
NOTE: Set Retentive Ranges so that C670 -- C737 and V7404 -- V7477 are not retentive.
Page 40
4--4
Setup Programming
Step 2: Write the Setup Logic for Each Remote Base
SP00
Remote #1 Input SP00
Remote #1 Output SP00
Remote I/O Setup Programming
Remote #2 Input SP00
Remote #2 Output SP00
Remote #3 Input SP00
Remote #3 Output
Whether you choose to write the remote I/O setup program as a subroutine or as a part of the main program, the procedure is still the same. You have two things you have to do: S Tell the CPU where to read and write the remote I/O points in memory. This is done with the use of “address pointers”. S Tell the CPU how many points are located in each base. You can use your worksheets to assist you. In the diagram below, you see how the starting addresses for the points in each remote base (from the tables in Appendix B) are mapped with the proper reserved memory pointers. The chart at the bottom of the page shows the pointer addresses. Notice that the number of points goes in the address immediately following the pointer for the start address. A combination of LDA and OUT commands are used to load and map the V40xxx address into the proper V74xx address. The LD and OUT commands are used to load the number of remote points for each remote base, by placing the number in the address immediately following its pointer. The chart at the bottom also shows the memory locations for storing the number of I/O points for each remote base. LDA O40403 OUT V7404 LD K16 OUT V7405
Remote Slave Worksheet 1
Note:
Remote Base Address_________(Choose 1--7)
The LDA instruction is loading octal numbers and therefor a capital O is placed in front of the number
INPUT
OUTPUT
Slot Number
Module Name
Input Address
No. Inputs
0
08ND3S
X060
8
LD K16
1
08ND3S
X070
8
2
OUT V7407
3
LDA O40502 OUT V7406
LDA O40404
4
OUT V7410
5
Starting Address
OUT V7412
Pointer Address
8
Y050
8
16 Total Input Points_____ Y040 40502 Output Bit Start Address:________V-Memory Address:V_______
No. of I/O Points
16 Total Output Points_____
Pointer Address + 1
LDA O40406
Table of Reserved Memory for Remote I/O Setup
OUT V7414 LD
Y040
08TD1
X060 40403 Input Bit Start Address:________V-Memory Address:V_______
LDA O40503
K32
08TD1
7
OUT V7411
OUT V7413
No.Outputs
6
LD K32
LD
Output Address
First Master Module
K16
Second Master Module
OUT V7415
Slave
LDA O40505
Input Address
Number of Input Pts
Output Address
Number of Output Pts
Input Address
1
V7404
V7405
V7406
V7407
V7444
V7445
V7446
V7447
2
V7410
V7411
V7412
V7413
V7450
V7451
V7452
V7453
3
V7414
V7415
V7416
V7417
V7454
V7455
V7456
V7457
4
V7420
V7421
V7422
V7423
V7460
V7461
V7462
V7463
OUT V7416 LD
K16
OUT V7417
Number of Output Input Pts Address
Number of Output Pts
5
V7424
V7425
V7426
V7427
V7464
V7465
V7466
V7467
6
V7430
V7431
V7432
V7433
V7470
V7471
V7472
V7473
7
V7434
V7435
V7436
V7437
V7474
V7475
V7476
V7477