For the Kromschroder DG50T

Page 9

Function

3 Function

3.1 Positive pressure measurement M16 x 1.5

Hand wheel (mbar) NC

NO

Screw plug, Rp 1/4" DG

COM

4 Rp 1/8" 2

1

Nozzle, 0.8 mm

Rp 1/4"

Micro switch

3

Measurement point 1/2" NPT conduit

Filter pad/ nozzle, DG..T 0.3 mm

NO

NC

Pilot lamp

COM

4 1/8" NPT

2

Micro switch Measurement point

1 1/4" NPT

The pressure switch DG switches in the event of increasing or decreasing pressure. Once the set switching point is reached, a micro switch is activated in the DG which is designed as a change-over contact. Increasing negative pressure Decreasing negative pressure -6 -5 -4 -3 -2 -1

Increasing pressure Decreasing pressure 0

1

2

3

4

5

6

The switching pressure is adjusted using a hand wheel.

DG · Edition 06.17

The positive pressure is measured in the lower diaphragm chamber, port 1 or 2. The upper diaphragm chamber is ventilated via port 3 or 4.

Hand wheel ("WC/mbar) Sealing plug, 1/4" NPT

Positive pressure measurement is designed, for example, for checking the fan function or measuring the min./max. gas pressure.

3.2 Negative pressure measurement Negative pressure measurement (air, flue gas) is designed, for example, for monitoring a suction pressure blower. The negative pressure is measured in the upper diaphragm chamber, port 3 or 4, and on DG..T via port 4. The lower diaphragm chamber is ventilated via port 1 or 2. In the case of DG..I, the negative pressure (gas, air, flue gas or biogas) is measured in the lower diaphragm chamber, port 1 or 2. The upper diaphragm chamber is ventilated via port 3 or 4.

3.3 Differential pressure measurement Differential pressure measurement is designed, for instance, for safeguarding an air flow rate or for monitoring filters and fans. DG..U, DG..H, DG..N: the higher absolute pressure is connected to port 1 or 2, and the lower absolute pressure to port 3 or 4. The remaining ports must be tightly plugged.

9

Page 10

NO

Function

NC N

N

3.4 Connection diagram L1 3 COM 1 NC

2 NO

0

NC

L1 1 2 NC NO

3 COM

3 COM 2 1 NC NO

1 2 NC NO

3 COM

N

N

3.4.2 Pilot lamp with plug Contacts 3 and 2 close when subject to increasing pressure. Contacts 1 and 3 close when subject to falling pressure. All DG models (except DG..N) switch with rising pressure. The contact switches from NC 1 to NO 2. DG..N switches with falling pressure. The contact switches from NO 2 to NC 1. DG..H and DG..N are locked off in their switched state and can only be unlocked with a manual reset. 3.4.1 Blue pilot lamp for 230 V AC or for 120 V AC L1

1 NO 2 NC NO

3 COM 2 NO

COM

N

N 3

1

2

2

N

3.4.3 Red/green pilot LED for 24 V DC/AC or for 230 V AC +

1 2 NC NO

3 COM 2 NO

3 COM

1 NC

N

–

3.4.4 Pilot LED with plug

NC

3 COM 2 1 NC NO

L1

NO 1

1 2 NC NO

3 COM

COM

NO

2

N

+

+3

N

L1

NO

3

3 COM

1 NC

N

DG · Edition 06.17

L1

– 3

1

NC

1

–

2

10

Page 11

Function

3.5 Wiring

All DG models (except DG..I)

If the DG..G has switched a voltage > 24 V and a current > 0.1 A at cos ϕ = 1 or > 0.05 A at cos ϕ = 0.6 once, the gold plating on the contacts will have been burnt through. It can then only be operated at this power rating or higher power rating. When using silicone tubes, only use silicone tubes which have been sufficiently cured. Vapours containing silicone can adversely affect the functioning of electrical contacts. In the case of low switching capacities, such as 24 V, 8 mA, for example, we recommend using an RC module (22 Ω, 1 µF) in air containing silicone or oil. C = 1 µF NO 2 NC 1

R = 22 Ω COM 3

NO 2 NC 1

COM 3

Contacts 3 and 2 close when subject to increasing pressure. Contacts 1 and 3 close when subject to falling pressure. DG 18I, DG 120I, DG 450I 1 NC

2 NO

NC 1

3 COM 3

NO 2

N COM

µ

Contacts 3 and 2 close when subject to increasing negative pressure. Contacts 1 and 3 close when subject to falling negative pressure.

▼ In the case of high humidity or aggressive gas components (H2S), we recommend using a pressure switch with gold contact due to its higher resistance to corrosion. Closed-circuit current monitoring is recommended under difficult operating conditions.

DG · Edition 06.17

11

Page 12

Function DG 1,5I and DG 12I The connection of DG 1,5I and DG 12I depends on the positive or negative adjusting range.

. 2, 5 .

ps

2

. . 2. . . .

3

= -1,5 – -0, 5;

-12 ps = -12

–

DG 12I

..

. . 1 ,5 ..

4

7

1

2

6

-1

..

- bar 1m

5

– 7 mbar

5

;1 -1

-1,

-

-3

=

-8

-5 -4

3 mbar

100 P a bar 1m

-9

-6

– 0,5

.. 3

=

-1 0

. . . -1 0, 5 . . . . .- . .

1 7

..

-1

100 P a

1 ..

. . 0.,5. . . .

DG 1,5I

In the negative adjusting range, the template which can be found in the unit displays the connection diagram. 3 COM 1 NC

2 NO

NC 1

3

NO 2

N COM

µ

In the positive adjusting range, remove the template and wire the unit as shown in the engraved connection diagram. NO 2 NC 1

COM 3

3.6 DG in Zone 1 (21) and 2 (22) hazardous areas Pressure switch DG can be used in Zone 1 (21) and 2 (22) hazardous areas if an isolating amplifier is installed upstream in the safe area as “Ex-i” equipment pursuant to EN 60079-11 (VDE 0170-7). DG as “simple electrical equipment” pursuant to EN 60079-11 corresponds to the Temperature class T6, Group II. The internal inductance/capacitance is Li = 0.2 µH/Ci = 8 pF. The isolating amplifier transfers the DG’s signals from the explosion-hazard area to the safe area. Depending on the design of the intrinsically safe circuit, the explosion-hazard area can be monitored for cable faults, cable discontinuities or short-circuits. Ensure that standard-compliant wiring pursuant to EN 60079 is used. When operating in Zones 21 and 22, the ⅛" connecting thread or the tube connection for the surrounding air or medium connection must be protected from dirt particles by a separate filter.

▼

DG · Edition 06.17

12

Page 13

Function Intrinsically safe circuit without monitoring for cable faults DG

Isolating amplifier NO

Intrinsically safe circuit with monitoring for cable faults and short-circuits DG

Isolating amplifier NO

1+

COM

3–

COM

Safe area

Intrinsically safe circuit with monitoring for cable discontinuities DG

Isolating amplifier NO

1+ 10 kΩ

Zone 1 or 2

2+ 3–

400 Ω ≤ R ≤ 2 kΩ

Zone 1 or 2

COM

1+ 10 kΩ

2+

2+ 3–

Safe area

Zone 1 or 2

Safe area

3.7 DG on pipes with Zone 2 (22) explosive atmospheres Pressure switch DG can be connected to pipes/rooms in which Zone 2 (22) explosive gases or dust are present without an isolating amplifier. The connection to Zone 2, Zone 22 must be implemented via one of the two ¼" threads. Even in the unlikely event of a break in the diaphragm, there is no danger of flashback into the system. The pressure compensation holes on the pressure switch (¼" connections) have a defined ignition protection, in terms of the safety measure for “enclosed-break devices for Group IIA gases and vapours”, pursuant to IEC/EN 60079-15. In the case of Zone 22, it must be ensured that dirt particles do not block the pressure supply hole (Ø = 0.8 mm).

DG · Edition 06.17

13

Page 14

Function

3.8 Animation

The interactive animation shows the function of the gas pressure switch DG. Click on the picture. The animation can be controlled using the control bar at the bottom of the window (as on a DVD player).

DG · Edition 06.17

To play the animation, you will need Adobe Reader 7 or a newer version. If you do not have Adobe Reader on your system, you can download it from the Internet. If the animation does not start to play, you can download it from the document library (Docuthek) as an independent application.

14

Page 15

Selection

4 Selection 4.1 Selection table DG..B for positive pressure DG..U for positive pressure, negative pressure and differential pressure Type DG

6

10

30

50

150 400 500

B

U

G

-3

-4

-5

-6

-7

-8

-9

K2

T

T2

N

A

-9

K2

T

T2

N

A

T

N

A

= standard, = available

Order example

DG 10UG-3K2

DG..H, DG..N for positive pressure, negative pressure and differential pressure DG..H locks off with rising pressure, DG..N locks off with falling pressure Type DG

6

10

30

50

150 400 500

H

N

G

-3

-4

-5

-6

-7

-8

DG..S for positive pressure, for oxygen and ammonia (without approval) Type DG

6

10

30

50

150

400

500

S

450

I

G

G

-3

-4

-5

-6

-7

-8

-6

-7

-8

-9

K2

DG..I for negative pressure Type DG

1,5

12

18

120

-3

-4

-5

K2

T

N

A

DG..T for positive pressure, negative pressure and differential pressure, with NPT connection Type DG

6

10

50

150

500

T*

G**

S

DG..HT, DG..NT for positive pressure, negative pressure and differential pressure DG..HT locks off with rising pressure, DG..NT locks off with falling pressure Type DG

6

10

50

150 500

H

N

T*

G**

S

* On DG..T, the blue pilot lamp for 120 V AC is fitted. ** On DG..TG, the red/green pilot LED for 24 V DC/AC is fitted. DG · Edition 06.17

15

Page 16

Selection DG..U, DG..H, DG..N, DG..I 2

1

Rp 1/8"

DG..T, DG..HT, DG..NT 2 ¼" NPT

Rp ¼"

Rp ¼"

3

DG..B DG..S

4

Rp ¼"

1

Rp 1/8"

DG..U, DG..H, DG..N, DG..I: ports 1 and 2: Rp ¼" (standard), ports 3 and 4: Rp ⅛" (standard). DG..B, DG..S: port 1: Rp ¼" (standard). DG..T, DG..HT, DG..NT: port 1: ¼” NPT (standard) or ports 1 and 2: ¼" NPT (available), port 4: ⅛" NPT (standard).

¼" NPT

1

4

/ " NPT

18

4.2 Type code Code DG 1,5 6 10 12 18 30 50 120 150 400 450 500 B U H N I S T G -3 -4 -5 -6 -9 K2 T T2 N A

Description Pressure switch for gas Negative pressure, adjusting range -1,5 to -0.5/+0.5 to +3 mbar Adjusting range 0.4 to 6 mbar Adjusting range 1 to 10 mbar Negative pressure, adjusting range -12 to -1/+1 to +7 mbar Negative pressure, adjusting range -2 to -18 mbar Adjusting range 2.5 to 30 mbar Adjusting range 2.5 to 50 mbar Negative pressure, adjusting range -10 to -120 mbar Adjusting range 30 to 150 mbar Adjusting range 50 to 400 mbar Negative pressure, adjusting range -80 to -450 mbar Adjusting range 100 to 500 mbar Positive pressure Positive pressure, negative pressure, differential pressure Locks off with rising pressure Locks off with falling pressure Negative pressure for gas Positive pressure only, for oxygen and ammonia T-product With gold-plated contacts Electrical connection: via screw terminals via screw terminals, IP 65 via 4-pin plug, without socket via 4-pin plug, with socket via 4-pin plug, with socket, IP 65 Red/green pilot LED for 24 V DC/AC Blue pilot lamp for 230 V AC Red/green pilot LED for 230 V AC Blue pilot lamp for 120 V AC External adjustment

Adjusting range, see page 25 (Adjusting range, switching hysteresis)

DG · Edition 06.17

16