The text of a manual · part 3 of 4
Pressure switch for gas DG, Technical Information, pages 17 to 24
Pages 17 to 24 of 32
The original document is the PDF (3.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Kromschroder DG50T
Page 17
Project planning information
5 Project planning information
The housing must not be in contact with masonry. Minimum clearance 20 mm.
5.1 Installation Installation in the vertical or horizontal position, or sometimes upside down, preferably with vertical diaphragm. If installed in a vertical position, the switching point pS will correspond to the scale value SK set on the hand wheel. If installed in another position, the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel. Switching point pS must be checked.
The DG..S is suitable for oxygen and ammonia only (diaphragm made of IIR). Do not use for fuel gases – diaphragm not resistant! In the case of oxygen, ensure grease-free installation. Continuous operation at high temperatures (e.g. maximum ambient temperature) accelerates the ageing of elastomer materials and reduces the service life (please contact manufacturer). Ozone concentrations exceeding 200 µg/m³ or gases containing more than 0.1%-by-vol. H2S accelerate the ageing of elastomer materials and reduce the service life. 2 p S = SK p S = SK p S = SK p S = SK
All DG models (except DG..I) p S = SK + 0.18 mbar DG 1,5I p S = SK + 0.4 mbar e.g. SK = 1.2: p S = 1.2 + 0,4 = 1.6 mbar e.g. SK = -1.2: p S = - 1.2 + 0,4 = -0.8 mbar DG 12I pS = SK + 0.5 mbar e.g. SK = 5: p S = 5 + 0,5 = 5.5 mbar e.g. SK = -10: p S = - 10 + 0.5 = -9.5 mbar DG 18I, DG 120I, DG 450I DG 18I: p S = SK + 0.5 mbar e.g. SK = - 10: p S = - 10 + 0,5 = - 9.5 mbar DG 120I, DG 450I: p S = SK + 0.2 mbar
DG · Edition 06.17
1 p S = SK - 0.18 mbar
3
4
Ports 3 and 4 are connected to the micro switch chamber. The port that is best protected against soiling (dust/humidity) is to be left open for ventilation (positive pressure measurement) to the atmosphere. If dust exposure in the environment is high, a filter pad, see page 20 (Filter pad set), or a filter are to be used in the open port. Combustion gas or a mixture of combustion gas and air must not be connected to port 3 or 4.
▼
17
Page 18
Project planning information Condensation must not be allowed to get into the housing (if possible, install pipework with an ascending gradient). Otherwise, there is a risk of icing of condensation at subzero temperatures, the switching point shifting or corrosion in the device which can lead to malfunctions. When installing outdoors, place the DG in a roofed area and protect from direct sunlight (even IP 65 version). To avoid condensation, the cover with pressure equalization element can be used, see page 20 (Pressure equalization element). The weather protection cover provides permanent protection when installed outdoors, see page 22 (Weather protection cover). In case of highly fluctuating pressures, install a restrictor orifice, see page 20 (Filter pad set).
DG · Edition 06.17
18
Page 19
Accessories
6 Accessories
1
6.1 Fastening set with screws, U-shape bracket 50 (1.97") 30 (1.18")
.95")
20 ") 9 (0.7
M4 x 10
39 (1.53")
5,2 (0.2") 24 (0.94")
1x
2x
M4 x 12
4
2
1
7")
4,20 +0,1 (0.17")
16 (0.63")
6 (0.24")
10 (0.4")
")
3
(1.8
20 (0.79
45 (1.77") 25 (0.98")
43 -0,3 (1.69")
47,5
40 (1.57")
75 (2
2
2
6.3 External adjustment
In order to set the switching pressure from the outside, the cover for external adjustment (6 mm Allen key) for DG..B, DG..U and DG..I can be retrofitted. Order No.: 74916155 1
2
3
4
64 (2.52")
For DG..B, DG..U, DG..I: Order No.: 74915387
6.2 Connecting set DG..U, DG..H, DG..N, DG..I
For monitoring a minimum and maximum inlet pressure with two pressure switches attached to one another. Order No.: 74912250 DG · Edition 06.17
19
Page 20
Accessories
6.4 Pressure equalization element
6.6 Test key PIA R¼
Rp ¼
To avoid the formation of condensation, the cover with pressure equalization element can be used. The diaphragm in the screw connector is designed to ventilate the cover, without allowing water to enter. Order No.: 74923391
To test the min. pressure switch, the DG can be vented in its switched state using the PIA test key (contains non-ferrous metals). Order No.: 74329466 Click
6.5 Filter pad set
TEST
Rp ¼
R¼
Rp 1/4
In the case of high pressure fluctuations, we recommend using a restrictor orifice (contains non-ferrous metals): Hole diameter 0.2 mm, Order No.: 75456321 Hole diameter 0.3 mm, Order No.: 75441317
DG · Edition 06.17
6.7 Filter pad set To protect the electrical contacts in the DG from dirt particles in the surrounding air or in the medium, use a filter pad at the ⅛" negative pressure port. As standard on IP 65 units. 5-piece filter pad set, Order No.: 74916199
20
Page 21
Accessories
6.8 Tube set
To be used with air only. Order No.: 74912952
Pilot lamp, red: 110/120 V AC, I = 1.2 mA, Order No.: 74920430 220/250 V AC, I = 0.6 mA, Order No.: 74920429 Pilot lamp, blue: 110/120 V AC, I = 1.2 mA, Order No.: 74916121 220/250 V AC, I = 0.6 mA, Order No.: 74916122 1
2
3
4
6.9 Standard socket set 6.12 LED set, red/green Order No.: 74915388
6.10 Standard coupler plug 24 V DC, I = 16 mA; 24 V AC, I = 8 mA, Order No.: 74921089 230 V AC, I = 0.6 mA, Order No.: 74923275 Order No.: 74920412
1
2
3
4
6.11 Pilot lamp set, red or blue
DG · Edition 06.17
21
Page 22
Accessories
6.13 Weather protection cover When the DG is installed outdoors, the weather protection cover provides permanent protection against condensation and weathering of housing parts. The weather protection cover is made of 1 mm-thick stainless steel. Installation position: vertical with the cable gland pointing downwards.
E
A
D C B F
2 M4 x 16 screws with 2 cap nuts. The enclosed filter pad is designed to protect the open ⅛" port from the ingress of dirt or insects. Scope of delivery: A 2 x covers, 100 x 100 x 100 mm B 2 x M4 x 16 screws C 4 x nuts D 2 x washers E 2 x cap nuts F 1 x filter pad (⅛" port) Order No.: 74924909.
DG · Edition 06.17
22
Page 23
Technical data
7 Technical data Gas type: natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1%-by-vol. H2S) and air. DG: max. inlet pressure pmax = withstand pressure, see page 25 (Adjusting range, switching hysteresis). Max. test pressure for testing the entire system: temporarily < 15 minutes 2 bar (29 psig). Switching capacity: DG: U = 24 – 250 V AC, I = 0.05 – 5 A at cos ϕ =1, I = 0.05 – 1 A at cos ϕ = 0.6. DG..G: U = 5 – 250 V AC, I = 0.01 – 5 A at cos ϕ = 1, I = 0.01 – 1 A at cos ϕ = 0.6. DG..G: U = 5 – 48 V DC, I = 0.01 – 1 A. DG..T: U = 30 – 240 V AC, I = 5 A at cos ϕ = 1, I = 0.5 A at cos ϕ = 0.6.
DG..TG: U = < 30 V AC, I = 0.1 A at cos ϕ = 1, I = 0.05 A at cos ϕ = 0.6. If the DG (DG..TG) has switched a voltage > 24 V (> 30 V) and a current > 0.1 A at cos ϕ = 1 or > 0.05 A at cos ϕ = 0.6 once, the gold plating on the contacts will have been burnt through. It can then only be operated at this power rating or higher power rating. Maximum medium and ambient temperatures: DG..B, DG..U, DG..I: -20 to +80°C (-4 to +176°F), DG..S: -15 to +60°C (5 to 140°F), DG..H, DG..N: -15 to +60°C (5 to 140°F), DG..T, DG..HT, DG..NT: -40 to +60 °C (-40 to +140 °F). Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life (please contact manufacturer). Storage and transport temperature: DG, DG..T: -20 to +40 °C (-4 to +104 °F). Diaphragm pressure switch, silicone-free. Diaphragm: NBR for DG..U, B, N, H, I, IIR for DG..S. Housing: glass fibre reinforced PBT plastic with low gas release. Lower housing section: AlSi 12.
▼ DG · Edition 06.17
23
Page 24
Technical data Enclosure: IP 54 or IP 65. Safety class: 1. Line diameter: 0.5 to 1.8 mm (AWG 24 to AWG 13). Line entrance: M16 x 1.5, clamping range: diameters of 4 to 10 mm, DG..T, DG..HT, DG..NT with ½" NPT conduit cable gland. Electrical connection type: screw terminals. Recommended tightening torque: Component Cover screws M16 x 1.5 cable gland Rp ⅛ pipe connection, aluminium Rp ¼ (NPT ¼) gas connection Rp ⅛ air connection, switch housing Clamping terminal screws T15 test point screw
Tightening torque [Ncm] 65 50 250 1300 250 80 150
Weight: 270 to 320 g (9.5 to 11.3 oz), depending on equipment.
DG · Edition 06.17
24