For the Kromschroder DG50T

Page 25

Technical data

7.1 Adjusting range, switching hysteresis On all DG models (except DG..N), the scale value is set to the switch-on point, and on DG..N, it is set to the switchoff point.

Type

Adjusting range*

Max. inlet Mean switching pressure pmax. = differential at min. and withstand max. setting pressure mbar "WC mbar "WC DG 6..T 0.5 – 6 0.2 – 2.4 0.2 – 0.3 0.08 – 0.12 DG 6U. DG 6B. DG 6S 0.4 – 6 – 0.2 – 0.3 – DG 10T 0.4 – 4 0.1 – 0.16 DG 10U. DG 10B. DG 10S 1 – 10 0.25 – 0.4 DG 30U. DG 30B.DG 30S 2.5 – 30 – 0.35 – 0.9 – DG 50T 1 – 20 0.3 – 0.6 DG 50U. DG 50B. 2.5 – 50 0.8 – 1.5 DG 50S DG 150U. DG 150B. 30 – 150 12 – 60 3–5 1.2 – 2 DG 150S. DG 150T DG 400U. DG 400B. 50 – 400 – 5 – 15 – DG 400S DG 500U. DG 500B. 100 – 500 40 – 200 8 – 17 3.2 – 6.8 DG 500S. DG 500T mbar 600 100 600 500 500 600

600

DG 10H. DG 10N. DG 10HT. DG 10NT DG 50H. DG 50N. DG 50HT. DG 50NT DG 150H. DG 150N. DG 150HT. DG 150NT DG 500H. DG 500N. DG 500HT. DG 500NT psi 8.5

Deviation from the switching point during testing pursuant to EN 1854 Gas pressure Air pressure switch switch ± 15% ± 15% or 0.04 "WC ± 15% ± 15% or 0.1 mbar ± 15% ± 15% or 0.04 "WC ± 15% ± 15% ± 15% ± 15% ± 15% ± 15% mbar – –

"WC – –

– –

– –

–

–

± 15%

± 15%

–

–

± 15%

± 15%

–

–

± 15%

± 15%

8.5

–

–

± 15%

± 15%

8.5

8.5

500 600

Difference between switching pressure and possible reset

8.5

600

1 – 10

0.4 – 4

–

–

600

8.5

0.4 – 1

0.16 – 0.4

± 15%

± 15%

2.5 – 50

1 – 20

–

–

600

8.5

1–2

0.4 – 0.8

± 15%

± 15%

30 – 150

12 – 60

–

–

600

8.5

2–5

0.8 – 2

± 15%

± 15%

100 – 500 40 – 200

–

–

600

8.5

4 – 17

1.6 – 6.8

± 15%

± 15%

* Adjusting tolerance = ± 15% of the scale value.

▼

DG · Edition 06.17

25

Page 26

Technical data Type

Adjusting range* [mbar]

Max. inlet pressure pmax. = withstand pressure [mbar]

DG 1,5I DG 12I DG 18I DG 120I DG 450I

-1.5 to -0.5 and +0.5 to +3 -12 to -1 and +1 to +7 -2 to -18 -10 to -120 -80 to -450

± 100 ± 100 ± 100 ± 600 ± 600

Mean switching differential at min. and max. setting [mbar] 0.2 – 0.5 0.5 – 1 0.5 – 1.5 4 – 11 10 – 30

Deviation from the switching point during testing pursuant to EN 1854 Gas pressure switch

Air pressure switch

± 15% ± 15% ± 15% ± 15% ± 15%

± 15% or 0.4 mbar ± 15% or 0.5 mbar ± 15% or 0.5 mbar ± 15% ± 15%

* Adjusting tolerance = ± 15% of the scale value.

DG · Edition 06.17

26

Page 27

Technical data

7.2 Safety-specific characteristic values for DG For SIL Suitable for Safety Integrity Level Diagnostic coverage DC Type of subsystem Mode of operation For PL Suitable for Performance Level Category Common cause failure CCF Application of essential safety requirements Application of tried-and-tested safety requirements For SIL and PL U = 24 V DC, I = 10 mA; U = 230 V AC, I = 4 mA U = 24 V DC, I = 70 mA; U = 230 V AC, I = 20 mA U = 230 V AC, I = 2 A Hardware fault tolerance (1 component/switch) HFT Hardware fault tolerance (2 components/switches, redundant operation) HFT Safe failure fraction SFF Fraction of undetected common cause failures β

DG · Edition 06.17

SIL 1, 2, 3 0 Type A to EN 61508-2, 7.4.3.1.2 High demand mode pursuant to EN 61508-4, 3.5.12 PL a, b, c, d, e B, 1, 2, 3, 4 > 65 Satisfied

Max. service life under operating conditions: 10 years after date of production, plus max. ½ year in storage prior to first use, or once the given number of operating cycles has been reached, depending on which is achieved first. The pressure switches are suitable for single-channel systems (HFT = 0) up to SIL 2/PL d, and up to SIL 3/PL e when two redundant pressure switches are installed in a double-channel architecture (HFT = 1), provided that the complete system complies with the requirements of EN 61508/ISO 13849. For a glossary of terms, see page 30 (Glossary).

Satisfied B10d value 6,689,477 operating cycles 4,414,062 operating cycles 974,800 operating cycles 0 1 > 90% ≥ 2%

27

Page 28

Technical data 7.2.1 Determining the PFHD value, the λD value and the MTTFd value 1 0.1 = PFHD = λD = x nop MTTFd B10d 1 2

PFDavg the = PFH x λD D x 24 x 365 T10d and PFDx avg 7.2.2 Calculating

Switch. cap. 230 V, 2 A nop 5,00 nop 43.800 Cycle time 720 B10d 974.800 T10d 10,0 PFHD (1 DG) 5,129 E-7 PFDavg (1 DG) 0,000 E-0 Suitable for PL d, SIL 2 PFHD (2 DG) 3,239 E-8 PFDavg (2 DG) 0,000 E-0 Suitable for PL e, SIL 3

1/h 1/a s a 1/h

1/h

PFHD = Probability of dangerous failure (HDM = high demand mode) [1/hour] PFDavg = Average probability of dangerous failure on demand (LDM = low demand mode) λD = Mean dangerous failure rate [1/hour] MTTFd = Mean time to dangerous failure [hours] nop = Demand rate (mean number of annual operations) [1/hour]

DG · Edition 06.17

28

Page 29

Maintenance cycles

7.3 Dimensions 43 (1.7") 30 (1.2")

4 x ø 3,61) (ø 0.14") 2,5 (0.1")

Rp ¼ (¼" NPT)

11 (0.43")

17 (0.7")

10,5 (0.41")

76 (3")

ø 4,2 (ø 0.17")

70 (2.76")

64 (2.52")

13,1 (0.52")

Rp 1/8 2) 28,5 (1.12")

36 (1.4 Rp 1/8 2") (1/8" NPT) 50 (2

")

13 (0.51") 30,5 (1.2") M16 x 1,5 (½" NPT Conduit)

1) Holes 10 mm (0.4") deep, for self-tapping screws. 2) For DG..U, DG..H, DG..N, DG..I.

8 Maintenance cycles At least once a year, twice a year in the case of biogas.

DG · Edition 06.17

29

Page 30

Glossary

9 Glossary 9.1 Diagnostic coverage DC Measure of the effectiveness of diagnostics, which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failures NOTE: Diagnostic coverage can exist for the whole or parts of a safety-related system. For example, diagnostic coverage could exist for sensors and/or logic system and/or final elements. Unit:%. see EN ISO 13849-1

9.2 Mode of operation High demand mode or continuous mode Operating mode, where the frequency of demands for operation made on a safety-related system is greater than one per year or greater than twice the proof-test frequency see EN 61508-4

9.3 Category Classification of the safety-related parts of a control system in respect of their resistance to faults and their subsequent behaviour in the fault condition, and which is achieved by the structural arrangement of the parts, fault detection and/or by their reliability

9.4 Common cause failure CCF Failures of different items, resulting from a single event, where these failures are not consequences of each other see EN ISO 13849-1

9.5 Fraction of undetected common cause failures β Fraction of undetected failures of redundant components due to a single event, whereby these failures are not based on mutual causes NOTE: β is expressed as a fraction in the equations and as a percentage elsewhere see EN 61508-6

9.6 B10d value Mean number of cycles until 10% of the components fail dangerously see EN ISO 13849-1

9.7 T10d value Mean time until 10% of the components fail dangerously see EN ISO 13849-1 see EN ISO 13849-1

DG · Edition 06.17

30

Page 31

Glossary

9.8 Hardware fault tolerance HFT A hardware fault tolerance of N means that N + 1 is the minimum number of faults that could cause a loss of the safety function

9.14 Average probability of dangerous failure on demand PFDavg (LDM = 1 – 10 switching cycles/year)

see IEC 61508-2

Average probability of a dangerous failure of the safety function on demand (LDM = low demand mode)

9.9 Mean dangerous failure rate λD see EN 61508-6

Mean rate of dangerous failures during operation time (T10d). Unit: 1/h. see EN ISO 13849-1

9.10 Safe failure fraction SFF Fraction of safe failures related to all failures, which are assumed to appear see EN 13611/A2

9.11 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode. Unit: 1/h. see EN 13611/A2

9.12 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failure see EN ISO 13849-1

9.13 Demand rate nop Mean number of annual operations from EN ISO 13849-1

DG · Edition 06.17

31

Page 32

Feedback

Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs. Clarity Found information quickly Searched for a long time Didn’t find information What is missing? No answer

Comprehension Coherent Too complicated No answer

Scope Too little Sufficient Too wide No answer

Use To get to know the product To choose a product Planning To look for information

Navigation I can find my way around I got “lost” No answer

My scope of functions Technical department Sales No answer

Remarks

Kromschröder AG Michael Rehkamp m.rehkamp@kromschroeder.com Osnabrück

Contact

DG · Edition 06.17

The current addresses of our international agents are available on the Internet: www.kromschroeder.de/Weltweit.20.0.html?&L=1 We reserve the right to make technical modifications in the interests of progress. Copyright © 2017 Elster GmbH All rights reserved.

03250743

Elster GmbH Postfach 2809 · 49018 Osnabrück Strotheweg 1 · 49504 Lotte (Büren) Germany Tel. +49 541 1214-0 Fax +49 541 1214-370 info@kromschroeder.com www.kromschroeder.com