The text of a manual ยท part 3 of 10
Programmable Controller User's Manual, External character display unit type A6FD, pages 8 to 13
Pages 8 to 13 of 60: 2. SYSTEM CONFIGURATION; 3. SPECIFICATIONS
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Mitsubishi A0J2-E28DT
Page 8
?
/MELSEC
2. SYSTEM CoNFlGuRATloN 2 SYSTEM CONFIGURATION 2.1 System Configuration
AOJ2CPU (P23lR23)
. ,
I10 unit ' AOJ2-E24T-
B u ~ l d ~ nblock g type CPU
A38B A35B A32B
. External dlsplay unlt
Output module AY40 AY41 AY42 AY50 AY51 AY80 AY81
.
A6FD
.,
Extension cable ' a
A68B A65B A58B A55B
Extension base u n ~ t
I
Fig. 2.1 System Configuration
POINT
I
1. If using the A6FD i n a data link system remote I10 station, refer t o Section 6.1"Display Output Timing" (1) and Section 7.2 "Programming Application Example" (4). 2. An extension base unit cannot be connected t o the A32B main base unit which does not have an extension connector.
Page 9
/MELSEC
2. SYSTEM CoNFlGuRATloN 2.2 Equipment
Table 2.1 l ~ s t sthe A serles output and I10 units t o w h i c h t h e AGFD can b e connected. (available at t i m e o f printing): Name
Type
Output unit (for A l , 2, 3CPU)
AY42
Name
110 unit
Output Specifications 16-po~nt,12124V DC trans~storoutput unlt ( S ~ n koutput) (for 0 1 ~ ) 32-po~nt, 12124V DC trans~storoutput unlt (for 0 . 1 ~ ) ( S ~ n koutput) 64-po~nt,12124V DC trans~storoutput unlt (for 0.1A) ( S ~ n koutput) 16-po~nt,12124V DC trans~storoutput unlt (for 0 5A) ( S ~ n koutput) 32-polnt, 12124V DC translstor output unlt (for 0 5A) ( S ~ n koutput) 16-po~nt,12124V DC translstor output unlt (for 0.5A w ~ t hfuse) (Source output) 32-polnt, 12124V DC trans~storoutput unit (for 0 5A wlth fuse) (Source output)
Output Specifications
Type . A0J2-E24T
(for
24 AOJ2-E28DT 12 polnts AOJ2-E56DT 24 p o ~ n t s
12124~DC translstor output unit (for 0.5A) ( S ~ n koutput)
Table 2.1 Unit List
POINT )
.
'
1. Relay output units should not be used due to the duty cycles imposed by the special AGFD control instructions 2. Any I10 slot may be used for the control of the AGFD.
.
Page 10
3. SPECIFICATIONS
3.1 General Specifications
Table 3.1 shows general specifications of the AGFD.
By n o s e s~mulator1500Vpp nolse voltage, IPS n o s e w ~ d t hand 25 t o 60Hz nolse frequency
N o ~ s ed u r a b ~ l ~ t y
D~electr~c withstand
1500V AC for 1 rnlnute across batch of AC external terrn~nals and ground 500V AC for' 1 rnlnute across DC external terrn~nalsand ground lnsulat~on resistance n tester across 5MR or larger by 500V DC ~ n s u l a t ~ oresistance AC external terrn~nalsand ground
Ground~ng
Class 3 ground~ng,ground~ngIS not necessary of the operat~onof the un~t
Operat~ng arnb~ence
Free of corrosive gases Dust should be m ~ n ~ m a l
Cool~ngmethod
Self-cool~ng
7
Table 3.1 General Specifications
I REMARKS I
*
One octave marked ind~catesa change from the ~ n ~ tfrequency ~al to double or half frequency. For example, any of the changes from 10Hz to 20Hz, from 20Hz t o 40Hz, from 40Hz t o 20Hz, and 20Hz t o 10Hz are referred t o as one octave.
"'JIS Japanese Industrial Standard.
Page 11
/MELSEC
3. SPEclFlcATloNs
..- .
- .
3.2 Performance Specifications
Table 3.2 shows the A6FD performance specifications.
Item
Specifications
Llne voltage
Input voltage. 100V AC/200V AC (0 12A max )
Applicable llne voltage
85 to 264V AC (50160Hz k 5%)
Appllcable u n ~ t
AY40, AY41, AY42, AY50, AY51, AOJ2-E24T, AOJ2-E28DT, AOJ2-E56DT s ~ n koutput u n ~ t s AY80, AY81 source output unlts 8 data llnes (DO to D7), 1 strobe llne (STROBE), 1 common l ~ n e(COM) 12124V DC 4mA (12V DC), 10rnA (24V DC) 10 2 to 26.4V DC(R1pple ratlo wlthln 5%) Approx. 2.4K R
Interface Rated Input voltage Rated. Input current Appl~cable.voltage lnput resistance ,
I
( lnternal lsolat~on Dlsplay t i p e
I
Control~Gted
[
Photocoupler
1
LED (red) 5 x 7 dots, dynarnlc method, 16 dlglts ~n 1 line ASCII
I a
,
-
Manual reset s w ~ t c h
External connection
20-polnt termlnal connector M3 (Metrlc thread) x 6 screws
Applicable wlre slze
2mm2 (14AWG) or less ( ~ p p ! l c a b l etlghtenlng torque. 7kg cm . . (0.5llb.ft))
Applicable solderless termlnal
Slze mm(1nch)
To f ~ 3mrn t (0 12 Inch) dla. termlnal screws 1 25-3, 1.25-YS3A, 2S3, 2-YS3A, V1 25-3, V1.25-YS3A, V2-S3, V2-YS3A 145(5.71) (D) x 290(11 42) (W) x 60(2 36) (H)
Table 3.2 ~ e i o r m a n c eSpecifications .
*
The AGFD is not guaranteed ageinst.instantaneous power failure.
I REMARKS I Before shipment, the AGFD IS checked to ensure that ~t d~splaysdata properly, uslng a shlelded cable 200m(656 18ft) In length and 0 18mm2(24AWG)CSA
Page 12
/MELSEC
3. SPEciFlcATloNs 3.3 Interface Specifications
The external equipment interface of the AGFD are given below.
If0
Terminal Number
Internal Circuit
Signal
AGFD PC Output (I/O in slot "n") Sink output unit Source output unit +
I
+ + + + + +
DO
DO Yn 0 Dl Yn 4- 1 0 2 .- Yn 2 3 D3 +- Yn D4 .- Yn 4 D5 .- Yn 4- 5 Yn 6 D6 7 D7 +- Yn Yn 4- 8 STROBE Cons~stsof 8 outputs for data s~gnalsYn+O to Yn4-7 (DO to D7), 1 output for strobe (Strobe signal) s~gnalYn+8 (STROBE), and COM (TB11). NC COM Connect Connect (common) 12124~DC. ( f ) 12124V DC. (OV) NC The reset s w ~ t c hclears the A6FD d~splay and outputs a reset s ~ g n afrom l TB13 and RESET2 TB14 to the f ~ e l d TB13 . and TB14 are relay contact outputs NC Refer to Table 3.4 NC + -
D1 D2 D3 D4 D5 D6 D7
Input
7
TB1l
Output Reset swltch
+ -
+ -
+ -
I
Table 3.3 External Interface Specifications
Item
Specifications
Appl~cablevoltage
100V AC, 200V AC, 5 to 48V DC
M ~ n ~ r n ucontact m current value
Im A
M a x ~ m u mcontact current value
2A (Res~storload)
Table 3.4 "Reset" output from A6FD
POINT
1
1. The same 12/24V DC power supply should be used for both the A6FD and the transistor output module. 2. The reset switch clears the display and initializes the unit. It also closes the relay contacts across TB13 and TB14. 3. The "NC" terminals are unused by the A6FD (NC for no connection)
I REMARKS I For the s ~ n kand source output unlts, refer to Append~x3
Page 13
/MELSEC
3. SPEclFlcATloNs 3.4 Power Supply Specifications
The AGFD power supply specifications are given below.
Internal Circuit
Terminal Number
Signal
TB18
100, 200V AC
100, 2OOV AC
LG
Specifications
Any supply of between 85 and 264V AC may be appl~ed to terrn~nalsTB18 and TB19. Input current 0 12A (max.) Frequency. 50160Hz f 5%) lnternal voltage: 5V DC 2A
Power filter ground
Table 3.5 Power Supply Specifications I
.
POINT ( 1. A 200msec delay occurs between power-up and the A6FD becoming active. 2. Half the supply voltage appears at the LG terminal (TB20). Do not touch this terminal if the unit is not grounded.