Manual · Mitsubishi
Programmable Controller User's Manual, External character display unit type A6FD
Manual60 pagesPDF 2.2 MB
User's manual for the Mitsubishi A6FD external character display unit, driven by MELSEC-A output units such as the A0J2-E28DT.
What this file really is
The old site listed this file as a manual for the Mitsubishi A0J2-E28DT. The file is the user's manual for the A6FD external character display unit; the A0J2-E28DT appears only as one of the output units that can drive it.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Mitsubishi user's manual for the A6FD external character display unit used with MELSEC-A series programmable controllers. It covers system configuration and the output units that can drive the display (AY40 to AY81 and the A0J2-E24T, A0J2-E28DT and A0J2-E56DT I/O units), general, performance, interface and power specifications, handling, mounting and wiring, display control signals and timing, programming examples for A1, A2, A3 and A0J2 CPUs, testing, troubleshooting and maintenance.
Its parts
- General Description
- System Configuration
- Specifications
- Handling
- Loading and Installation
- Display Control Signals and Timing
- Programming
- Test
- Troubleshooting
- Maintenance and Inspection
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
User's manual for the Mitsubishi A6FD external character display unit, a 16-character LED display driven by a MELSEC-A series transistor output unit. The site files it under the A0J2-E28DT, which the manual names only as one of the output units that can drive the A6FD. It covers specifications, mounting, wiring, signal timing, programming, testing and troubleshooting.
- Device
- A6FD external character display unit for MELSEC-A series programmable controllers p. 6, 7
- Display
- Red LED, 16 ASCII characters, each 5 by 7 dots p. 27
- Driving output units
- Sink: AY40, AY41, AY42, AY50, AY51, A0J2-E24T, A0J2-E28DT, A0J2-E56DT; source: AY80, AY81 p. 11
- Data interface
- 8 data lines (D0 to D7), 1 strobe line, 1 common line p. 11
- Input signals
- 12/24V DC, 4mA at 12V DC, 10mA at 24V DC, photocoupler isolated p. 11
- Power supply
- Any 85 to 264V AC on TB18 and TB19, 0.12A max p. 13
- Reset output
- Relay contacts across TB13 and TB14 close when the reset switch is pressed; 100V AC, 200V AC, 5 to 48V DC, 2A max resistive load p. 12
- Terminals
- 20-point terminal connector, M3 screws, wire 2mm2 (14AWG) or less p. 11
- Dimensions
- 290 mm wide, 60 mm high, 145 mm deep p. 11
- Operating temperature
- 0 to 55°C p. 16
- Character timing
- Strobe on at least 5ms and off at least 10ms, with a cycle of at least 30ms per character p. 24
- PR and PRC instructions
- Send 16 characters, one every 30ms, 480ms in all, independent of the PC scan time p. 26
- Power-up delay
- 200msec before the A6FD becomes active p. 13
- Numeric display software
- SWOGHP-UTLP-FN1 package converts numerical data to ASCII p. 51
What this manual walks you through
- Mounting in a panel cut-out, on a flat surface or with extended brackets p. 17, 18, 19
- Power supply, I/O and grounding wiring practice p. 20, 21
- Wiring the A6FD to a sink output unit (AY40 example) p. 22
- Wiring the A6FD to a source output unit (AY80 example) p. 23
- Timing the data and strobe signals p. 24
- Displaying comments with the PR and PRC instructions p. 26, 27
- Programming example for the A0J2CPU p. 49, 50
- Displaying numerical values p. 51
- Pre-test checks before power-up p. 52
- Troubleshooting a blank display and periodic inspection p. 53, 54
Good to know
- Relay output units should not be used to drive the A6FD, because of the duty cycles of its control instructions. p. 9
- In a MELSECNET remote I/O station the PR and PRC instructions cannot be used; the program must drive the data and strobe lines. p. 25
- Use the same 12/24V DC supply for the A6FD and the transistor output module. p. 12
- Half the supply voltage appears at the LG terminal (TB20); do not touch it if the unit is not grounded. p. 13
- Circuit board components are damaged by static electricity; ground yourself and the work bench before handling them. p. 59
Questions this manual answers
Which output units can drive the A6FD display?
Sink output units AY40, AY41, AY42, AY50, AY51, A0J2-E24T, A0J2-E28DT and A0J2-E56DT, or source output units AY80 and AY81. Relay output units should not be used. p. 9, 11
What power supply does the A6FD need?
Any supply between 85 and 264V AC on terminals TB18 and TB19, drawing 0.12A at most. p. 13
How many characters does the A6FD show?
16 ASCII characters on a red LED, each made of 5 by 7 dots. The manual reset button clears the display. p. 27
What should I check when the A6FD shows nothing?
The manual's flowchart checks the AC supply, the PC CPU and the external wiring, then the voltage at the D0 to D7 and STROBE inputs with the CPU set to STOP. p. 53
Can the A6FD be used in a MELSECNET remote I/O station?
Yes, but the PR and PRC instructions cannot be used there; the sequence program must control the data and strobe signals itself. p. 25
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 10 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file