User's manual for the Mitsubishi A6FD external character display unit, driven by MELSEC-A output units such as the A0J2-E28DT.

What this file really is

The old site listed this file as a manual for the Mitsubishi A0J2-E28DT. The file is the user's manual for the A6FD external character display unit; the A0J2-E28DT appears only as one of the output units that can drive it.

Download the PDF2.2 MB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Mitsubishi user's manual for the A6FD external character display unit used with MELSEC-A series programmable controllers. It covers system configuration and the output units that can drive the display (AY40 to AY81 and the A0J2-E24T, A0J2-E28DT and A0J2-E56DT I/O units), general, performance, interface and power specifications, handling, mounting and wiring, display control signals and timing, programming examples for A1, A2, A3 and A0J2 CPUs, testing, troubleshooting and maintenance.

Its parts

  1. General Description
  2. System Configuration
  3. Specifications
  4. Handling
  5. Loading and Installation
  6. Display Control Signals and Timing
  7. Programming
  8. Test
  9. Troubleshooting
  10. Maintenance and Inspection

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

User's manual for the Mitsubishi A6FD external character display unit, a 16-character LED display driven by a MELSEC-A series transistor output unit. The site files it under the A0J2-E28DT, which the manual names only as one of the output units that can drive the A6FD. It covers specifications, mounting, wiring, signal timing, programming, testing and troubleshooting.

Read for this summary: pages 1 to 27 and 49 to 60 of 60.

Device
A6FD external character display unit for MELSEC-A series programmable controllers p. 6, 7
Display
Red LED, 16 ASCII characters, each 5 by 7 dots p. 27
Driving output units
Sink: AY40, AY41, AY42, AY50, AY51, A0J2-E24T, A0J2-E28DT, A0J2-E56DT; source: AY80, AY81 p. 11
Data interface
8 data lines (D0 to D7), 1 strobe line, 1 common line p. 11
Input signals
12/24V DC, 4mA at 12V DC, 10mA at 24V DC, photocoupler isolated p. 11
Power supply
Any 85 to 264V AC on TB18 and TB19, 0.12A max p. 13
Reset output
Relay contacts across TB13 and TB14 close when the reset switch is pressed; 100V AC, 200V AC, 5 to 48V DC, 2A max resistive load p. 12
Terminals
20-point terminal connector, M3 screws, wire 2mm2 (14AWG) or less p. 11
Dimensions
290 mm wide, 60 mm high, 145 mm deep p. 11
Operating temperature
0 to 55°C p. 16
Character timing
Strobe on at least 5ms and off at least 10ms, with a cycle of at least 30ms per character p. 24
PR and PRC instructions
Send 16 characters, one every 30ms, 480ms in all, independent of the PC scan time p. 26
Power-up delay
200msec before the A6FD becomes active p. 13
Numeric display software
SWOGHP-UTLP-FN1 package converts numerical data to ASCII p. 51

What this manual walks you through

  • Mounting in a panel cut-out, on a flat surface or with extended brackets p. 17, 18, 19
  • Power supply, I/O and grounding wiring practice p. 20, 21
  • Wiring the A6FD to a sink output unit (AY40 example) p. 22
  • Wiring the A6FD to a source output unit (AY80 example) p. 23
  • Timing the data and strobe signals p. 24
  • Displaying comments with the PR and PRC instructions p. 26, 27
  • Programming example for the A0J2CPU p. 49, 50
  • Displaying numerical values p. 51
  • Pre-test checks before power-up p. 52
  • Troubleshooting a blank display and periodic inspection p. 53, 54

Good to know

  • Relay output units should not be used to drive the A6FD, because of the duty cycles of its control instructions. p. 9
  • In a MELSECNET remote I/O station the PR and PRC instructions cannot be used; the program must drive the data and strobe lines. p. 25
  • Use the same 12/24V DC supply for the A6FD and the transistor output module. p. 12
  • Half the supply voltage appears at the LG terminal (TB20); do not touch it if the unit is not grounded. p. 13
  • Circuit board components are damaged by static electricity; ground yourself and the work bench before handling them. p. 59

Questions this manual answers

Which output units can drive the A6FD display?

Sink output units AY40, AY41, AY42, AY50, AY51, A0J2-E24T, A0J2-E28DT and A0J2-E56DT, or source output units AY80 and AY81. Relay output units should not be used. p. 9, 11

What power supply does the A6FD need?

Any supply between 85 and 264V AC on terminals TB18 and TB19, drawing 0.12A at most. p. 13

How many characters does the A6FD show?

16 ASCII characters on a red LED, each made of 5 by 7 dots. The manual reset button clears the display. p. 27

What should I check when the A6FD shows nothing?

The manual's flowchart checks the AC supply, the PC CPU and the external wiring, then the voltage at the D0 to D7 and STROBE inputs with the CPU set to STOP. p. 53

Can the A6FD be used in a MELSECNET remote I/O station?

Yes, but the PR and PRC instructions cannot be used there; the sequence program must control the data and strobe signals itself. p. 25

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. REVISIONS2
  2. INTRODUCTION3
  3. 1. GENERAL DESCRIPTION6
    1. 1.1 How to Use This Manual6
  4. 2. SYSTEM CONFIGURATION8
    1. 2.1 System Configuration8
    2. 2.2 Equipment9
  5. 3. SPECIFICATIONS10
    1. 3.1 General Specifications10
    2. 3.2 Performance Specifications11
    3. 3.3 Interface Specifications12
    4. 3.4 Power Supply Specifications13
  6. 4. HANDLING14
    1. 4.1 Handling Instructions14
    2. 4.2 Nomenclature15
  7. 5. LOADING AND INSTALLATION16
    1. 5.1 Installation Environment16
    2. 5.2 Mounting17
    3. 5.3 Wiring20
  8. 6. DISPLAY CONTROL SIGNALS AND TIMING24
    1. 6.1 Display Output Timing24
    2. 6.2 Display Method27
  9. 7. PROGRAMMING28
    1. 7.1 Basic Display Programs28
    2. 7.2 Programming Application Examples 1 (For A1, A2, A3CPU)33
    3. 7.3 Programming Application Example 2 (For AOJ2CPU)49
    4. 7.4 Display of Numerical Variables51
  10. 8. TEST52
    1. 8.1 Pre-Test Checks52
    2. 8.2 Test and Adjustment52
  11. 9. TROUBLESHOOTING53
  12. 10. MAINTENANCE AND INSPECTION54
  13. APPENDICES55
    1. APPENDIX 1 External Views55
    2. APPENDIX 2 Character Code List56
    3. APPENDIX 3 Sink Output and Source Output Units57

From the PDF’s own bookmarks.

The whole text · 10 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Pages 4 to 74-7
  3. Pages 8 to 138-13
  4. Pages 14 to 2314-23
  5. 6. DISPLAY CONTROL SIGNALS AND TIMING24-27
  6. 7. PROGRAMMING, pages 28 to 3528-35
  7. 7. PROGRAMMING, pages 36 to 4336-43
  8. 7. PROGRAMMING, pages 44 to 5144-51
  9. Pages 52 to 5452-54
  10. APPENDICES55-60

The file

Revision and size

RevisionIB (NA) 66139, Apr. 1989
PublisherMitsubishi Electric
Pages60
PDF2.2 MB
TextText from the PDF itself; pages 5 and 45 are scans, read by OCR, which may hold reading errors.

The first pages · 3 of 60

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 60
Page 2
Page 2of 60
Page 3
Page 3of 60

More documents · 1

For the same models