Page 14
/MELSEC
4. HANDLING . 4. HANDLING
4.1 Handling Instructions
. Handle the A6FD carefully as described below: (1) Do not subject the unit t o impact loads.
(2) Guard against the e n t r i - o f conductive debris into the unit. If any should enter, switch off the power and remove it. (3) Do not. touch the printed circuit board. .
.
(4) Tighten screws t o the torques given below: .
,
Screw
Torque Range kg cm (Ib ft)
Term~nalblock screws (M3 m e t r ~ cthread)
8 (0 58) to 14 (1.01)
Terrn~nalblock f ~ x ~ nscrews g (M4 ketrlc thread) Unit rnount~ngscrews (M4 rnetr~cthread)
-
8 (0.58)'to 14 (1.01)
5 (0.36) to 8 (0 58)
Page 15
/MELSEC
4. HANDLING 4.2 Nomenclature
F\ront View \
ACFD
(
LED lnd~cator D~splays16 ASCII characters.
"
Manual Reset Swttch
7
Rear View of supply and I10
Bottom View
-
I
Clears and ~ n ~ t ~ a l ithe z e sd~splayand closes the relay output contacts across TB13 and TB14.
Page 16
5. LOADING AND INSTALLATION
/MELSEC
5. LOADING AND INSTALLATION 5.1 Installation Environment
The installation environment should meet the following requirements: (1) Ambient temperature between 0 and 55°C. (2) Ambient humidity between 10 and 90%. (3) No condensation (e.g. due t o sudden temperature changes) (4) No corrosive and/or combustible gases. (5) No airborne conductive or organic powders or mists. (6)Protected from direct exposure t o sunlight. (7) Protected from strong power and magnetic fields. (8) Protected from vibration and shock. (9) Away from, sources of heat such as heating elements. The installation environment should meet the specifications quoted in Section 3.1.
Page 17
5. LOADING AND INSTALLATION
/MELSEC
5.2 Mounting 5.2.1 General precautions
When installing the A6FD in a panel etc. note the follow~ng: (1) Install the unit in a well-ventilated place with the operating ambient temperature less than 55°C. (2) Avoid installing the unit over large sources of heat (such as a large-capacity resistor, transformer, or heater). (3) Do not install the unit near sources of vibration or impact loads such as large magnetic contactors and no-fuse breakers. (4) Ensure any "L" brackets used do not obstruct the air flow for ventilation. (5) When installing the A6FD on a flat surface, ensure that there is sufficient clearance for the connection of solderless terminals to the terminal block. (6) The mountlng holes In the rear of the face plate are tapped for M 4 (Metric thread) screws. Recommended screw length is 5.6mm (0.22inch) plus the panel wall thickness. (7) The mounting holes in the rear of the face plate are tapped for M 4 (Metric thread) screws. Recommended screw length is mounting surface thickness plus 5mm (0.20inch).
Page 18
/MELSE
5. LOADING AND INSTALLATION 5.2.2 Mounting
(1) Installing the unit in a panel cut-out.
Schemat~cD~agram Face plate (plast~cm o l d ~ n g )
Terminal block n ~ mountlng t hole M 4 (metric thread) /Face 0 0
' plate
&
0
4--
M a ~ nu n ~ t (Sheet metal)
Top V ~ e w M4 screw ( m e t r ~ cthread)
+ 5.6mm (0 221nch)
Length = Panel wall th~ckness
(2) Cut-out dimensions and hole centres. 4 (0.16) - 5mm (0.201nch) d ~ a .holes
0 1
--
0
265 5 (10.45)kl .O (0 04)
4
274 (10.79)k0.5 (0.02)
-
4
Refer to the rear view in Appendix 1.
C
U n ~ mm(inch) t
Page 19
/MELSEC
5. LOADING AND INSTALLATION d i
(3) Installation on a flat surface Rubber pads should be used to provide clearance between the flat surface and the AGFD for the face plate and solderless terminal connections, as shown below.
~ u b b e rpads
(4) Installation using extended brackets. See below. , Term~nalblock
Panel
Extended brackets
Extended : bracket A6FD maln unlt
5-4 IB (NA) 66139-A
Page 20
/MELSEC
5. LOADING AND INSTALLATION 5.3 Wiring , ,
5.3.1 Wiring precautions (1) Power supply wiring (a) When line voltage fluctuations are liable t o cause the supply voltage t o go outside the specified range, use a constant voltage transformer. (b) The power supply used should generate minimal noise between lines and between lines and ground. If the noise generated is excessive, an isolation transformer should be used. (c) Separate PC power supply, I10 equipment and main circuit wiring as shown below: Main power
PC power
Ac--LqYlA,"xerF$k
100~
I/O power
2o0~
110 equipment
110 power
I
110 equipment
M a ~ nc~rcuitpower M a ~ ncircuit power
(d) Use twisted wire for 100V AC, 200V AC and 24V DC wiring and use the shortest wire length possible. (e) Use the maximum cable size possible (up t o 2mm2 (14AWG)) t o minimize voltage drops. ( f ) Do not bundle 100V AC and 24V DC wires with the main circuit (high voltage or large current) and I10 signal cables. Avoid running these wires near the main circuit and I10 signal cables and, if possible, keep them more than lOOmm (3.94inch) away. (2) 110 equipment wiring (a) Use 2mm2 (14AWG) wire or smaller for I10 wiring. (b) Run the input wires separately from the output wires. . (c) Keep the I10 signal wires more that 100mm (3.94 inch) away from any main c~rcuitwiring. (d) Where I10 signal wires are run in close proximity t o other wiring, use shielded cable, preferably grounded at the PC end. (e) Ground any piping used to route cables. ( f ) Separate the 24V DC I10 signal lines from 100V AC and/or 200V AC wires.
(3) Grounding wiring (a) Use class 3 grounding (Grounding resistance 1008 or less). Where possible', ground the PC independently of other equipment. (b) Use 2mm2 (14AWG) or larger cable for grounding. (c) The grounding point should be as near to the PC as possible. The grounding cable length should be minimal. (d) The unit will still operate if ~t is not grounded.
Page 21
5. LOADING AND INSTALLATION
/MELSEC
(e) if independent grounding is impractical, use the common grounding method shown below.
equipment equipment
Class 3 grounding
Class 3 grounding
(1) Exclusive grounding. Best
(2) Common grounding. Good
Page 22
/MELSEC
5. LOADING AND INSTALLATION 5.3.2 Output unit wiring
(1) Connect~onwith sink output unit (AY40, AY41, AY42, AY50, AY51, AOJ2-E24T, AOJ2-E28DT, AOJ2-E56DT) Connection with the AY40 output unit is shown below. The I10 numbers used In t h ~ sexample assume that the AY40 is loaded in slot 0 of the main base unit.
TB16
YOD
TB19
12124V DC
TB20
OV
100/200V AC
LG
TB20
-1
(+
12124V DC
-
4
*I
"1: The LG terminal must always be grounded.
Page 23
'
/MELSEC
. 5. LOADING AND INSTALLATION
'
(2) Connection with source output unit(AY80, AY81) Connection with the AY80 output unit is shown below. The I10 numbers used in this example assume that the AY80 is loaded in slot 0 of the main base unit.
. .
* I : The LG terminal must always be grounded.